Home > Honeywell > Scanner > Honeywell 1250g2 Manual

Honeywell 1250g2 Manual

    Download as PDF Print this page Share this page

    Have a look at the manual Honeywell 1250g2 Manual online for free. It’s possible to download the document as PDF or print. UserManuals.tech offer 178 Honeywell manuals and user’s guides for free. Share the user manual or guide on Facebook, Twitter or Google+.

    							3 - 15
    Character Deactivation Mode
    If you have sent a character from the host to trigger the scanner to begin scan-
    ning, you can also send a deactivation character to stop scanning.  Scan the On 
    bar code below to use character deactivation, then use Deactivation Character 
    (following) to select the character you will send from the host to terminate scan-
    ning.  Default = Off.
    Deactivation Character
    This sets the character used to terminate scanning when using Character 
    Deactivation Mode.  On the ASCII Conversion Chart (Code Page 1252)on 
    page A-3, find the hex value that represents the character you want to use 
    to terminate scanning.  Scan the bar code below, then use the 
    Programming Chart to read the alphanumeric combination that represents 
    that ASCII character.  Scan Save to finish.
    * Off
    On
    Deactivation Character 
    						
    							3 - 16
    Reread Delay
    This sets the time period before the scanner can read the same bar code a sec-
    ond time.  Setting a reread delay protects against accidental rereads of the 
    same bar code.  Longer delays are effective in minimizing accidental rereads.  
    Use shorter delays in applications where repetitive bar code scanning is 
    required.  Default = Medium.  
    User-Specified Reread Delay
    If you want to set your own length for the reread delay, scan the bar code below, 
    then set the delay (from 0-30,000 milliseconds) by scanning digits from the 
    Programming Chart, then scanning Save. 
    Output Sequence Overview
    Output Sequence Editor
    This programming selection allows you to program the scanner to output 
    data (when scanning more than one symbol) in whatever order your appli-
    cation requires, regardless of the order in which the bar codes are 
    scanned.  Reading the Default Sequence symbol programs the scanner to 
    Short (500 ms)
    * Medium (750 ms)
    Long (1000 ms)
    Extra Long (2000 ms)
    User-Specified Reread Delay 
    						
    							3 - 17
    the Universal values, shown below.  These are the defaults.  Be certain 
    you want to delete or clear all formats before you read the Default 
    Sequence symbol.
    Note: If CodeGate is enabled, you must hold the trigger while reading each 
    bar code in a sequence.
    Note: To make Output Sequence Editor selections, you’ll need to know the 
    code I.D., code length, and character match(es) your application 
    requires.  Use the Alphanumeric symbols on the Programming Chart 
    to read these options.
    To Add an Output Sequence
    1. Scan the Enter Sequence symbol (see Require Output 
    Sequence, page 3-20).
    2.Code I.D.
    On the Symbology Chartson page A-1, find the symbology to which you 
    want to apply the output sequence format.  Locate the Hex value for that 
    symbology and scan the 2 digit hex value from the Programming Chart 
    (inside back cover).
    3.Length
    Specify what length (up to 9999 characters) of data output will be 
    acceptable for this symbology.  Scan the four digit data length from the 
    Programming Chart.  (Note:  50 characters is entered as 0050.  9999 is 
    a universal number, indicating all lengths.)  When calculating the length, 
    you must count any programmed prefixes, suffixes, or formatted 
    characters as part of the length (unless using 9999).
    4.Character Match Sequences
    On the ASCII Conversion Chart (Code Page 1252)on page A-3, find 
    the Hex value that represents the character(s) you want to match.  Use 
    the Programming Chart to read the alphanumeric combination that 
    represents the ASCII characters.  (99 is the Universal number, 
    indicating all characters.)
    5.End Output Sequence Editor
    Scan F F to enter an Output Sequence for an additional symbology, or 
    Save to save your entries.
    Other Programming Selections
    Discard 
    This exits without saving any Output Sequence changes. 
    						
    							3 - 18
    Output Sequence Example
    In this example, you are scanning Code 93, Code 128, and Code 39 bar 
    codes, but you want the scanner to output Code 39 1st, Code 128 2nd, and 
    Code 93 3rd, as shown below.
    Note: Code 93 must be enabled to use this example.
    You would set up the sequence editor with the following command line:
    SEQBLK62999941FF6A999942FF69999943FF
    The breakdown of the command line is shown below:
    SEQBLKsequence editor start command
    62 code identifier for Code 39
    9999 code length that must match for Code 39, 9999 = all lengths
    41 start character match for Code 39, 41h = “A”
    FF termination string for first code
    6A code identifier for Code 128
    9999 code length that must match for Code 128, 9999 = all lengths
    42 start character match for Code 128, 42h = “B”
    FF termination string for second code
    69 code identifier for Code 93
    9999 code length that must match for Code 93, 9999 = all lengths
    43 start character match for Code 93, 43h = “C”
    FF termination string for third code
    To program the previous example using specific lengths, you would have to 
    count any programmed prefixes, suffixes, or formatted characters as part of 
    the length.  If you use the example on page 3-18, but assume a  suf-
    fix and specific code lengths, you would use the following command line:
    SEQBLK62001241FF6A001342FF69001243FF
    The breakdown of the command line is shown below:
    A - Code 39
    B - Code 128
    C - Code 93 
    						
    							3 - 19
    SEQBLKsequence editor start command
    62 code identifier for Code 39
    0012 A - Code 39 sample length (11) plus CR suffix (1) = 12
    41 start character match for Code 39, 41h = “A”
    FF termination string for first code
    6A code identifier for Code 128
    0013 B - Code 128 sample length (12) plus CR suffix (1) = 13
    42 start character match for Code 128, 42h = “B”
    FF termination string for second code
    69 code identifier for Code 93
    0012 C - Code 93 sample length (11) plus CR suffix (1) = 12
    43 start character match for Code 93, 43h = “C”
    FF termination string for third code
    Output Sequence Editor   
    Sequence Timeout
    You may wish to set the maximum time between bar code scans in an out-
    put sequence.  If that maximum time is not met, the output sequence oper-
    ation is terminated.  Set the length (in milliseconds) for a timeout by 
    scanning the bar code below, then setting the timeout (from 1-65535 milli-
    seconds) by scanning digits from the Programming Chart, then scanning 
    Save.  Default = 5000 msec.
    Default Sequence
    Enter Sequence
    Sequence Timeout 
    						
    							3 - 20
    Sequence Match Beeper
    By default, the scanner beeps when a sequence match is found.  If you 
    want the scanner to remain silent, scan the Sequence Match Beeper Off 
    bar code below.  Default = Sequence Match Beeper On. 
    Partial Sequence
    If an output sequence operation is terminated before all your output 
    sequence criteria are met, the bar code data acquired to that point is a 
    “partial sequence.”   
    Scan Discard Partial Sequence to discard partial sequences  when the 
    output sequence operation is terminated before completion.  
    Scan Transmit Partial Sequence to transmit partial sequences.  (Any 
    fields in the sequence where no data match occurred will be skipped in the 
    output.)
      If you have programmed a Sequence Timeout (page 3-19) and 
    the timeout is reached, the partial sequence is transmitted. Default = Dis-
    card Partial Sequence.
    Require Output Sequence
    When an output sequence is Required, all output data must conform to an 
    edited sequence or the scanner will not transmit the output data to the host 
    device.  When it’s On/Not Required, the scanner will attempt to get the 
    output data to conform to an edited sequence but, if it cannot, the scanner 
    transmits all output data to the host device as is.
    Sequence Match Beeper Off
    * Sequence Match Beeper On
    Transmit Partial Sequence
    * Discard Partial Sequence 
    						
    							3 - 21
    When the output sequence is Off, the bar code data is output to the host as 
    the scanner decodes it.  Default = Off. 
    No Read
    With No Read turned On, the scanner notifies you if a code cannot be read.  If 
    using an EZConfig-Scanning Tool Scan Data Window (see page 8-2), an “NR” 
    appears when a code cannot be read.  If No Read is turned Off, the “NR” will 
    not appear.  Default = Off.
    If you want a different notation than “NR,” for example, “Error,” or “Bad Code,” 
    you can edit the output message (see Data Formatting beginning on page 5-1).  
    The hex code for the No Read symbol is 9C.  
     Required
     On/Not Required
     *Off
    On
    * Off 
    						
    							4 - 1
    4
    Data Editing
    Prefix/Suffix Overview
    When a bar code is scanned, additional information is sent to the host computer 
    along with the bar code data.  This group of bar code data and additional, 
    user-defined data is called a “message string.”  The selections in this section 
    are used to build the user-defined data into the message string.
    Prefix and Suffix characters are data characters that can be sent before and 
    after scanned data.  You can specify if they should be sent with all symbologies, 
    or only with specific symbologies.  The following illustration shows the break-
    down of a message string:
    Points to Keep In Mind
     It is not necessary to build a message string.  The selections in this 
    chapter are only used if you wish to alter the default settings.  Default 
    prefix = None.  Default suffix is dependent on interface.
     A prefix or suffix may be added or cleared from one symbology or all 
    symbologies.
     You can add any prefix or suffix from the ASCII Conversion Chart (Code 
    Page 1252), beginning on page A-3, plus Code I.D. and AIM I.D.
     You can string together several entries for several symbologies at one 
    time.
     Enter prefixes and suffixes in the order in which you want them to appear 
    on the output.
     When setting up for specific symbologies (as opposed to all 
    symbologies), the specific symbology ID value counts as an added prefix 
    or suffix character.
     The maximum size of a prefix or suffix configuration is 32 characters, 
    which includes header information.
    To Add a Prefix or Suffix:
    Step 1.Scan the Add Prefix or Add Suffix symbol (page 4-3).
    Step 2.Determine the 2 digit Hex value from the Symbology Chart 
    (included in the Symbology Charts, beginning on page A-1) for the 
    Pref ix
    Scanned Data
    Suffix
    1-11
    alpha numeric &
    control characters variable length 1-11
    alpha numeric &
    control characters 
    						
    							4 - 2
    symbology to which you want to apply the prefix or suffix.  For 
    example, for Code 128, Code ID is “j” and Hex ID is “6A”.
    Step 3.Scan the 2 hex digits from the Programming Chart inside the back 
    cover of this manual or scan 9, 9 for all symbologies.
    Step 4.Determine the hex value from the ASCII Conversion Chart (Code 
    Page 1252)on page A-3, for the prefix or suffix you wish to enter. 
    Step 5.Scan the 2 digit hex value from the Programming Chart inside the 
    back cover of this manual.
    Step 6.Repeat Steps 4 and 5 for every prefix or suffix character.
    Step 7.To add the Code I.D., scan 5, C, 8, 0.
     To add AIM I.D., scan 5, C, 8, 1.
     To add a backslash (\), scan 5, C, 5, C.
    Note: To add a backslash (\) as in Step 7, you must scan 5C twice – once 
    to create the leading backslash and then to create the backslash 
    itself.
    Step 8.Scan Save to exit and save, or scan Discard to exit without saving.
    Repeat Steps 1-6 to add a prefix or suffix for another symbology.
    Example: Add a Suffix to a specific symbology
    To send a CR (carriage return) Suffix for U.P.C. only:
    Step 1.Scan Add Suffix.
    Step 2.Determine the 2 digit hex value from the Symbology Chart 
    (included in the Symbology Charts, beginning on page A-1) for 
    U.P.C.
    Step 3.Scan 6, 3 from the Programming Chart inside the back cover of this 
    manual.
    Step 4.Determine the hex value from the ASCII Conversion Chart (Code 
    Page 1252)on page A-3, for the CR (carriage return). 
    Step 5.Scan 0, D from the Programming Chart inside the back cover of this 
    manual.
    Step 6.Scan Save, or scan Discard to exit without saving.
    To Clear One or All Prefixes or Suffixes
    You can clear a single prefix or suffix, or clear all prefixes/suffixes for a 
    symbology.  If you have been entering prefixes and suffixes for single sym-
    bologies, you can use Clear One Prefix (Suffix) to delete a specific char-
    acter from a symbology.  When you Clear All Prefixes (Suffixes), all the 
    prefixes or suffixes for a symbology are deleted. 
    						
    All Honeywell manuals Comments (0)

    Related Manuals for Honeywell 1250g2 Manual