Page 51

GE Energy
GE I-210+cElectronic Meter
Product Description and Operation, Maintenance,and Upgrade Instructions
GEH-7101-2.00-151
Table 6 Batter Failure & Power Outage Error Code Display
Date & TimeLost
Load Profile recording: Stopped
Register Function: Remains TOU, but operates as a demand meterwith a default TOU rate
Program: OK
TOU schedule: Stopped
TOU calendar: Stopped
Billing Data: Total summations and max. Demands are OK
(rolling billing period demand if enabled will
cease, and traditional demand...

Page 52

GE I-210+cElectronic Meter
Product Description and Operation, Maintenance,and Upgrade Instructions
GE Energy
52GEH-7101-2.00-1
Table 8 Er 000200—Non-volatile Data Error
Date & Time: OK
Load Profile recording: May be corrupt
Register Functions: Unchanged
Program: May be corrupt
TOU schedule: May be corrupt
TOU calendar: May be corrupt
Billing Data: May be corrupt
4.13.1.4 Er 001000—Firmware Code Error
The Firmware Code error indicates a failure in the memory used to store firmware. When the
meter is not...

Page 53

GE Energy
GE I-210+cElectronic Meter
Product Description and Operation, Maintenance,and Upgrade Instructions
GEH-7101-2.00-153
4.13.2 Caution Reporting
The meter also checks other conditions that are of concern but do not indicate a problem with the
meter hardware. The meter reports these as cautions. Individual cautions may be enabled or
disabled selectively. If a caution is enabled, it can be configured to be displayed and optionally
freeze the display.
Table 11 Caution Code Display
Caution...

Page 54

GE I-210+cElectronic Meter
Product Description and Operation, Maintenance,and Upgrade Instructions
GE Energy
54GEH-7101-2.00-1
4.13.2.1 CA 000001—Low Battery
The Low Battery caution indicates a weak or missing battery. The meter periodically tests the
battery. The meter sets the Low Battery caution if the battery voltage is low. The Low Battery
caution is cleared when the battery test passes. The meter tests the battery under the following
conditions:
Power up
1st of each month (00:16)
Activation...

Page 55

GE Energy
GE I-210+cElectronic Meter
Product Description and Operation, Maintenance,and Upgrade Instructions
GEH-7101-2.00-155
4.13.2.6 CA 000400—Low Potential
The Low Potential caution indicates that measured voltage falls below the programmed
tolerance. The voltage is tested every five seconds using the voltage from the previous second.
The meter sets the Low Potential caution when the test fails three consecutive times. The meter
automatically clears the Low Potential caution when all active phases...

Page 56

GE I-210+cElectronic Meter
Product Description and Operation, Maintenance,and Upgrade Instructions
GE Energy
56GEH-7101-2.00-1
Table 12 Fault Symptoms Without Codes
Caution DisplayProbable CauseRemedy
High/low demand
registration
a. Socket wiring error
b. Meter internal wiring defective
c. Defective sensor
a. Rewire according to applicable
diagram.
b. Check that voltage and currentconnectors are seated properly. Check
the leads for damage.
c. Replace meter.
Meter overheats a. Meter socket has...

Page 57

GE Energy
GE I-210+cElectronic Meter
Product Description and Operation, Maintenance,and Upgrade Instructions
GEH-7101-2.00-157
5 Upgrading
5.1 General
Warning:The GE I-210+c™meter contains lethal voltages. The meter must be
completely disconnected from any external circuits before disassembly is attempted. Failure to
observe this practice can result in serious injury or death.
For instructions on how to install and enable software, refer to theMeterMate™MMCOMM
Instruction Book(GEH-5084S or most current...

Page 58

GE I-210+cElectronic Meter
Product Description and Operation, Maintenance,and Upgrade Instructions
GE Energy
58GEH-7101-2.00-1
5.2.2 Event Log—E2 Softswitch
The Event Log softswitch allows the meter to track the most recent 200 events. Use
MeterMate™Program Manager, Diagnostics Editor, to select the event types to be logged and
how many occurrences should be tracked, up to a maximum of 200 events. Date and time stamps
are included on logged events for Demand/LP or TOU meters. Logged events include the...

Page 59

GE Energy
GE I-210+cElectronic Meter
Product Description and Operation, Maintenance,and Upgrade Instructions
GEH-7101-2.00-159
5.2.5 Power Quality Measurements—Q2 Softswitch
The Power Quality Measurements softswitch enables the following:
Voltage (L-N): VA (max, min, store) for summations, demand, and load profile recording
RMS voltage measurement for reading and display
Low potential caution
5.2.6 Basic Recording—R2 Softswitch
The Basic Recording Softswitch enables up to four channels of load...

Page 60

GE I-210+cElectronic Meter
Product Description and Operation, Maintenance,and Upgrade Instructions
GE Energy
60GEH-7101-2.00-1
Interval LengthNumber of Channels
1234
Expanded Memory
1 25.9313.079.807.13days
2 51.8726.1319.6014.27days
3 77.8039.2029.4021.40days
4 103.7352.2739.2028.53days
5 129.6765.3349.0035.67days
6 155.6078.4058.8042.80days
10 259.33130.6798.0071.33days
12 311.20156.80117.6085.60days
15 389.00196.00147.00107.00days
20 518.67261.33196.00142.67days
30 778.00392.00294.00214.00days
60...