Page 31
GE Energy GE I-210+cElectronic Meter Product Description and Operation, Maintenance,and Upgrade Instructions GEH-7101-2.00-131 Daily Maximum Demand Rate A,B Time TOU Maximum Demand Time for Peaks 1 and 2 TOU Maximum Demand Rate A,B for Peaks 1 and 2 TOU Test Mode Thermal Interval Type: “0” = 15 min., “1” = 1 min. All Maximum Demand Rate A,B Date for Peaks 1 and 2TOU Test Mode Accumulating Demand 1,2 UOM All Maximum Demand Rate A,B Time for Peaks 1 and 2TOU Test Mode Power Factor All Cumulative Demand...
Page 32
GE I-210+cElectronic Meter Product Description and Operation, Maintenance,and Upgrade Instructions GE Energy 32GEH-7101-2.00-1 Time of Last Time Change TOU Current Time TEST MODETime Remaining in Demand (Sub)interval in minutes (Not valid for thermal demands)TOU Test Mode Demand Interval length in minutes (block)AllReal-Time Pricing time remaining until activation in min.TOU/ DmdLP Test Mode Demand No of Subintervals. (rolling only)All Test Mode Demand Subint. length in minutes (rolling)All Test Mode...
Page 33
GE Energy GE I-210+cElectronic Meter Product Description and Operation, Maintenance,and Upgrade Instructions GEH-7101-2.00-133 Figure 6 Alternate Display Mode Switch 3.2.1.2 Normal Display Mode In Normal Display mode, the meter display scrolls continually through the Normal Display items until one of the following occurs: Demand reset is invoked. Display Switch is actuated. Communication is initiated. Test mode is invoked. A frozen error or caution message is triggered. Note:The test mode push...
Page 34
GE I-210+cElectronic Meter Product Description and Operation, Maintenance,and Upgrade Instructions GE Energy 34GEH-7101-2.00-1 3.2.1.3 Alternate Display Mode The Alternate Display is used to display information for the meter technician that is not contained in the Normal Display. Display items:Selected during MeterMate™program development Initiate:Actuate the display switch for more than 3 seconds. Scroll:The meter automatically scrolls through the Alternate Display items. Exit:The meter...
Page 35
GE Energy GE I-210+cElectronic Meter Product Description and Operation, Maintenance,and Upgrade Instructions GEH-7101-2.00-135 3.2.1.5 Frozen Display Mode The Frozen Display mode stops the Normal Display to draw attention to an error, caution, or diagnostic in the meter. DisplayItems: Select errors, cautions, and diagnostics to freeze the display during MeterMate™program development. Initiate: Automatic when the meter detects a frozen error, caution, or diagnostic Scroll: Use a magnet to activate...
Page 36
GE I-210+cElectronic Meter Product Description and Operation, Maintenance,and Upgrade Instructions GE Energy 36GEH-7101-2.00-1 When displayed, the C annunciator indicates the C voltage is present at the meter. If this annunciator is blinking, C voltage is low (Network meters only). 8. The left-right arrows indicate watt hour direction of energy flow. The right arrow will be lit if the energy is delivered; the left arrow will be lit if the energy is received. The up-down arrows indicate var hour...
Page 37
GE Energy GE I-210+cElectronic Meter Product Description and Operation, Maintenance,and Upgrade Instructions GEH-7101-2.00-137 3.2.3.1 kWh Display Figure 9 kWh Display Figure 9shows the following conditions: The Display Label is 01. Five-digit display of energy (kWh) Phase A voltage is present. End-of-demand-interval indication—This indicator is lit at the end of each demand subinterval. Displayed quantity is measured in kilowatt hours. Energy is being delivered to the load. The one block...
Page 38
GE I-210+cElectronic Meter Product Description and Operation, Maintenance,and Upgrade Instructions GE Energy 38GEH-7101-2.00-1 3.2.3.2 Alternate Display Mode Figure 10 Alternate Display Figure 10shows the following conditions: Meter is in Alternate Display mode. Display label 108 is displayed. Phase A and C voltages are present. Six-digit display of quadergy (kvarh) Displayed quantity is measured in kvarh. The two blocks indicate State 1 of the magnitude indicator. Quadergy (kvarh) is...
Page 39
GE Energy GE I-210+cElectronic Meter Product Description and Operation, Maintenance,and Upgrade Instructions GEH-7101-2.00-139 3.2.3.3 Test Mode Display Figure 11 Test Mode Display Figure 11shows the following conditions: Meter is in TEST mode. Display label is 905. Meter display is a six-digit demand display (kW) with three digits to the right of the decimal point. Phase A voltage is present. Energy is being delivered to the load. The three blocks indicate State 2 of the magnitude...
Page 40
GE I-210+cElectronic Meter Product Description and Operation, Maintenance,and Upgrade Instructions GE Energy 40GEH-7101-2.00-1 4 Maintenance Instructions Warning:The information contained within this document is intended to be an aid to qualified metering personnel. It is not intended to replace the extensive training necessary to install or remove meters from service.Any work on or near energized meters, meter sockets, or other metering equipment presents the danger of electrical shock.All work on...