Carrier 38mvc018 3 Service Manual
Here you can view all the pages of manual Carrier 38mvc018 3 Service Manual. The Carrier manuals for Air Conditioner are available online for free. You can easily download all the documents as PDF.
Page 21
21 REFRIGERANT LINES General refrigerant linesizing: 1. The 38MVC/MVQ units are shipped with a full charge of R410A refrigerant. All charges, line sizing, and capacities are based on runs of 25 ft (7.6 m). For runs over 25 ft (7.6 m), consult long--line section on this page for proper charge adjustments. 2. Minimum refrigerant line length between the indoor and outdoor units is 10 ft. (3 m). 3. Refrigerant lines should not be buried in the ground. If it is necessary to bury the lines, not more than...
Page 22
22 SYSTEM EVACUATION AND CHARGING UNIT DAMAGE HAZARD Failure to follow this caution may result in equipment damage or improper operation. Never use the system compressor as a vacuum pump. CAUTION! Refrigerant tubes and indoor coil should be evacuated using the recommended deep vacuum method of 500 microns. The alternate triple evacuation method may be used if the procedure outlined below is followed. Always break a vacuum with dry nitrogen. SYSTEM VACUUM AND CHARGE Using VacuumPump 1. Completely tighten...
Page 23
23 CONTROL SYSTEM The 40MVC/MVQ unit is equipped with a microprocessor control to perform two functions: 1. Provide safety for the system 2. Control the system and provide optimum levels of comfort and efficiency The main microprocessor is located on the control board of the fan coil unit (outdoor units have a microprocessor too) with thermistors located in the fan coil air inlet and on the indoor coil. Heat pump units have a thermistor on the outdoor coil. These thermistors monitor the system operation...
Page 24
24 Indoor Coil Freeze Protection The indoor coil can freeze due to any of the following: SLow system charge SReduced indoor airflow SRestricted refrigerant flow SLow ambient temperature (outdoor) SLow load (indoor) In cooling mode, the thermistor located on a return bend of the indoor coil monitors the coil temperature continuously. Any time the coil temperature drops below the TE5 limit for five consecutive minutes, the compressor and outdoor fan will be switched off until the coil temperature rises...
Page 25
25 MODES OF OPERATION The units have 5 main operating modes: 1. Fan Only 2. Cooling 3. Heating (heat pumps only) 4. Auto 5. Dehumidification (Dry) The units have 2 other modes (manual operation) that are operated in unique situations: 1. Auto Forced Mode (Emergency) 2. Test Mode Fan Mode Only In this mode, the system circulates the room air without changing the room air temperature. Cooling Mode In this mode, the system cools and dries the room air with the fan running continuously, either at a selected...
Page 26
26 Auto Fan When the fan speed is set to Auto, the fan will run at either the medium or low speed based on the difference between the room temperature and the set point temperature as shown below: Room temp. upRoom temp. down T- Ts0 Med. SpeedLow. Speed 3.6°FT = Room Temperature Ts = Set Point Temperature A08112 Fig. 31 – Auto Fan -- Heating Mode Manual Indoor Fan The indoor fan will run continuously in heating at the set fan speed (even if the compressor cycles off) unless the indoor coil temperature...
Page 27
27 Dry (Dehumidification) Mode When more humidity control is desired, the Dry setting can be selected. Lower humidity is achieved when the microprocessor adjusts the indoor fan speed and compressor cycling by comparing the room temperature (T) and the set point temperature (TS). There are two different control algorithms: Size 9k and 12 k units: T = TS + 3.6 -- the compressor will run for 6 minutes and the indoor fan will run at low speed. The compressor will be off for 4 minutes and the indoor fan will...
Page 28
28 TROUBLESHOOTING This section provides the required flow charts to troubleshoot problems that may arise. NOTE:Information required in the diagnoses can be found either on the wiring diagrams or in the appendix. Required Tools: The following tools are needed when diagnosing the units: SDigital multimeter SScrew drivers (Phillips and straight head) SNeedle-- nose pliers Recommended Steps 1. Refer to the diagnostic hierarchy chart below and determine the problem at hand. 2. Go to the chart listed in the...
Page 29
29 CHART 1 -- INDOOR FAN SPEED OUT OF CONTROL Reset main power and restart system using remote. Problem persists? Replace indoor fan motor No further action is requiredNo Yes Check IFM output and input on indoor board. Values good? Yes Check motor connection. Connection good? No Fix connection Yes No Replace indoor board Reset main power and restart system using remote. Problem persists? Replace indoor fan motor No further action is requiredNo Yes Yes Check motor connection. Connection good? No Fix...
Page 30
30 CHART 2 -- TEMPERATURE SENSOR Reset main power and restart system using remote. Problem persists? Appendix 6 No further action is requiredNo Yes Check input and output on indoor or outdoor board. Yes Check sensor connector at ID or OD board Connection good? No Fix connection Yes No Replace board Check sensor resistance. No Yes Yes No Yes No No Replace sensor No Double check connection, for corrosion or high resistance. YesYes A08167 38/40MVC, MVQ