Carrier 38mvc018 3 Service Manual
Have a look at the manual Carrier 38mvc018 3 Service Manual online for free. It’s possible to download the document as PDF or print. UserManuals.tech offer 29 Carrier manuals and user’s guides for free. Share the user manual or guide on Facebook, Twitter or Google+.
40MVC / 38MVC 40MVQ / 38MVQ Service Manual High --- Wall Duct Free Split System Sizes 009 To 024 TABLE OF CONTENTS PAGE SAFETY CONSIDERATIONS 1......................... STANDARD FEATURES AND ACCESSORIES 2........... SPECIFICATIONS -- COOLING ONLY 3.................. SPECIFICATIONS -- HEAT PUMP UNITS 4............... DIMENSIONS 5...................................... SERVICE VALVE LOCATIONS 5........................ CLEARANCES 6..................................... SYSTEM OPERATING ENVELOPE 7.................... ELECTRICAL DATA 7................................ WIRING 8........................................... CONNECTION DIAGRAMS 9.......................... WIRING DIAGRAMS 10 -- 16........................... REFRIGERATION CYCLE DIAGRAM 17................. REFRIGERANT LINES 18............................. SYSTEM EVACUATION AND CHARGING 19............. CONTROL SYSTEM 20............................... SYSTEM SAFETIES 20................................ 3MINUTETIMEDELAY 20............................ COMPRESSOR OVERCURRENT PROTECTION 20 -- 21.... SEQUENCE OF OPERATION 21........................ MODES OF OPERATION 22 -- 24........................ TROUBLESHOOTING 25 -- 37.......................... APPENDIX 38 -- 43...................................SAFETY CONSIDERATIONS Improper installation, adjustment, alteration, service, maintenance, or use can cause explosion, fire, electrical shock, or other conditions which may cause death, personal injury, or property damage. Consult a qualified installer, service agency, or your distributor or branch for information or assistance. The qualified installer or agency must use factory -- authorized kits or accessories when modifying this product. Refer to the individual instructions packaged with the kits or accessories when installing. Follow all safety codes. Wear safety glasses, protective clothing, and work gloves. Use quenching cloth for brazing operations. Have fire extinguisher available. Read these instructions thoroughly and follow all warnings or cautions included in literature and attached to the unit. Consult local building codes and National Electrical Code (NEC) for special requirements. Recognize safety information. This is the safety--alert symbol !! When you see this symbol on the unit and in instructions or manuals, be alert to the potential for personal injury. Understand these signal words: DANGER, WARNING, and CAUTION. These words are used with the safety-- alert symbol. DANGER identifies the most serious hazards whichwillresult in severe personal injury or death. WARNING signifies hazards whichcouldresult in personal injury or death. CAUTION is used to identify unsafe practices whichmayresult in minor personal injury or product and property damage. NOTE is used to highlight suggestions whichwillresult in enhanced installation, reliability, or operation. !WARNING ELECTRICAL SHOCK HAZARD Failure to follow this warning could result in personal injury or death. Before installing, modifying, or servicing system, main electrical disconnect switch must be in the OFF position. There may be more than 1 disconnect switch. Lock out and tag switch with a suitable warning label. INTRODUCTION Section 1 of this Service Manual provides the necessary information to service, repair, and maintain the EEZ family of Puron air conditioners and heat pumps. Section 2 of this manual is an appendix with data required to perform troubleshooting. Use the Table of Contents to locate a desired topic.
2 MODEL NUMBER NOMENCLATURE OUTDOOR UNIT 38 MVC 3 --- 01 --- 018 A i r --- C o o l e d C o n d e n s e r Unit Type MVC--- C o o l i n g O n l y MVQ--- H e a t P u m pVo ltage 1--- 1 1 5 --- 1 --- 6 0 3--- 208/230 --- 1 --- 60 Nominal Capacity 009--- 3 / 4 T o n 012--- 1 T o n 018--- 1 --- 1 / 2 T o n 024--- 2 T o n s INDOOR UNIT 40 MVC 3 --- 01 --- 018 Fan Coil Unit Unit Type MVC--- C o o l i n g O n l y MVQ--- H e a t P u m pVo ltage ------ 3 0 V D C 1--- 1 1 5 --- 1 --- 6 0 3--- 208/230 --- 1 --- 60 Nominal Capacity 009--- 3 / 4 T o n 012--- 1 T o n 018--- 1 --- 1 / 2 T o n 024--- 2 T o n s SERIAL NUMBER NOMENCLATURE 01 06 Week of Manufacture Year of Manufacture00001 Serial NumberV Manufacturing Site 38/40MVC, MVQ
3 STANDARD FEATURES AND ACCESSORIES Ease Of Installation Mounting BracketsS Low Voltage ControlsS Comfort Features Microprocessor ControlsS Wireless Remote ControlS Automatic Air SweepS Air Direction ControlS Auto Restart FunctionS Cold Blow Protection On Heat PumpsS Tu r b o M o d e O n S i z e s 9 K a n d 1 2 KS Auto Changeover On Heat PumpsS Energy Saving Features Sleep ModeS Stop/Start TimerS Safety And Reliability 3MinuteTimeDelayForCompressorS Over Current Protection For CompressorS Indoor Coil Freeze ProtectionS Indoor Coil High Temperature Protection On Heat PumpsS Condenser High Temperature Protection On heat Pumps{S Accumulator On Heat PumpsS Ease Of Service And Maintenance Cleanable FiltersS DiagnosticsS Liquid Line Pressure TapsS Suction And Discharge Pressure Taps (Sizes 18 and 24K)S Application Flexibility Low Ambient Controls ( --- 20° F)A Condensate PumpsA Crankcase HeaterA Wind BafflesF Warranty 5 --- Year Compressor WarrantyS 1 --- Parts WarrantyS Compressor Extended Warranty Years 6 Thru 10O All Parts And Labor Years 2 Thru 5O All Parts And Labor Years 2 Thru 5, Compressor Years 6 Thru 10O {Sizes 18k & 24k Legend SStandard A Accessory OOptional F Field Fabricated INDOOR UNITS A07892 Fig. 1 – Condensate Pump On high wall fan coils, the condensate pump has a lift capability of 18 ft (5.5 m) or the discharge side with the pump mounted in the fan coil or 6 ft (1.8 m) on the suction side if the pump must be remote mounted. The pump mounts inside the unit with quick plug--in connections, and is recommended when adequate drain line pitch cannot be provided, or when the condensate must move up to exit. NOTE: An external 115v power source will be required to run the pump on unit sizes 9k and 12k. OUTDOOR UNITS LOW AMBIENT KIT The kit controls condenser fan cycling using a pressure switch. It is specifically designed to control fan--motor cycles in response to saturated condensing pressure. This device maintains a constant saturated condensing temperature of 100_F±10_F (37.78_C± --12.22_C) at outdoor--air temperatures between 55_F and --20_F (12.78_C±--12.22_C), and can be used on all outdoor units without changing the outdoor fan motor. CRANKCASE HEATER Available for units with rotary compressors. Heater clamps around compressor oil sump. Recommended for low--ambient applications on sizes 9, 12 , 18, 24 and long line applications. 38/40MVC, MVQ
4 SPECIFICATIONS -- COOLING ONLY UNITS System System Model Number5 3 M V C 0 0 9 --- --- --- 15 3 M V C 0 1 2 --- --- --- 15 3 M V C 0 1 2 --- --- --- 35 3 M V C 0 1 8 --- --- --- 3 System Voltage115 V115 V208/230208/230 Control Voltage0 --- 1 2 P u l s e D C0 --- 1 2 P u l s e D C0 --- 1 2 P u l s e D CPulse DC Capacity (Btuh)9000120001200018000 SEER13.013.013.013.0 Refrigerant Refrigerant TypeR --- 410A Design Pressure (PSIG)550550550550 Metering DeviceCapillary Tube in Outdoor Unit Charge (lb)2.32.93.04.4 Compressor Ty p eRotary ModelEA82X1C --- 1FZDU1EA108X1C --- 1FZDU1PA108X1C --- 3FZDUPA150X2CS --- 3KUU O i l C h a r g e ( P O E --- o z )11.811.811.825.4 Capacitor45µF/250VAC45µF/250VAC35µF/370VAC40µF/370VAC Rated Current (RLA)7.59.95.27.3 Locked Rotor Amp (LRA)40472132.6 Outdoor Motor Rpm/CFM900/1060900/1090900/1120840/1470 Diameter (in) .. No. of Blades15.8…315.8…315.8…318.1…3 Motor (hp)0.1020.1020.1020.224 Capacitor6.5µF/260VAC6.5µF/260VAC2.5µF/450VAC3µF/450VAC Outdoor Coil Face Area (sq. ft)4.053.943.945.51 No. Rows2224 Fins per inch17171718 Circuits4444 Indoor Motor Motor Watts/HP20/.03420/.03420/.03425/.044 Rpm/Cfm (High)1250/3251270/4251270/4251070/630 Rpm/Cfm (Medium)1000/2601100/3651100/3651000/570 Rpm/Cfm (Low)800/1901000/3401000/340960/500 Blower Diameter…Length (in)3.84…25.874.17…25.24.17…25.24.21…37.6 Indoor Coil Face Area (sq. ft)2.152.542.544.36 No. Rows2222 Fins per inch19.519.519.519.5 Circuits2336 Refrigerant Lines Connection TypeFlare Liquid (Mix Phase) (in) OD1/4”1/4”1/4”1/4” Vapor Line (in) OD3/8”1/2”1/2”1/2” Condensate Drain (in).65 (OD) .53 (ID).65 (OD) .53 (ID).65 (OD) .53 (ID).65 (OD) .53 (ID) Maximum Length (ft)656565100 Max Lift (Fan Coil Above) (ft)35353550 Max Drop (Fan Coil Below) (ft)35353550 38/40MVC, MVQ
5 SPECIFICATIONS -- HEAT PUMP UNITS System System Model Number5 3 M V Q 0 0 9 --- --- --- 15 3 M V Q 0 1 2 --- --- --- 15 3 M V Q 0 1 2 --- --- --- 35 3 M V Q 0 1 8 --- --- --- 3 System Voltage115 V115 V208/230208/230 Control Voltage0 --- 1 2 P u l s e D C0 --- 1 2 P u l s e D C0 --- 1 2 P u l s e D CPulse DC Capacity (Btuh)9000120001200018000 SEER13.013.013.013.0 HSPF7.77.77.77.7 Refrigerant Refrigerant TypeR --- 410A Design Pressure (PSIG)550550550550 Metering DeviceCapillary Tubes in Outdoor Unit Charge (lb)2.353.03.0 Compressor Ty p eRotary ModelEA82X1C --- 1FZDU1EA108X1C --- 1FZDU1PA108X1C --- 3FZDUPA150X2CS --- 3KUU O i l C h a r g e ( P O E --- o z )11.811.811.825.4 Capacitor45µF/250VAC45µF/250VAC35µF/370VAC40µF/370VAC Rated Current (RLA)7.59.95.27.3 Locked Rotor Amp (LRA)40472132.6 Outdoor Motor Rpm/CFM900/1060900/1090900/1120840/1470 Diameter (in) .. No. of Blades15.8…315.8…315.8…318.1…3 Motor (hp)0.1020.1020.1020.224 Capacitor6.5µF/260VAC6.5µF/260VAC2.5µF/450VAC3µF/450VAC Outdoor Coil Face Area (sq. ft)4.053.943.945.51 No. Rows2224 Fins per inch17171718 Circuits4444 Indoor Motor Motor Watts/HP20/.03420/.03420/.03425/.044 Rpm/Cfm (High)1250/3251270/4251270/4251070/630 Rpm/Cfm (Medium)1000/2601100/3651100/3651000/570 Rpm/Cfm (Low)800/1901000/3401000/340960/500 Blower Diameter…Length (in)3.84…25.874.17…25.24.17…25.24.21…37.6 Indoor Coil Face Area (sq. ft)2.152.542.544.36 No. Rows2222 Fins per inch19.519.519.519.5 Circuits2336 Refrigerant Lines Connection TypeFlare Liquid (Mix Phase) (in) OD1/4”1/4”1/4”1/4” Vapor Line (in) OD3/8”1/2”1/2”1/2” Condensate Drain (in).65 (OD) .53 (ID).65 (OD) .53 (ID).65 (OD) .53 (ID).65 (OD) .53 (ID) Maximum Length (ft)656565100 Max Lift (Fan Coil Above) (ft)35353550 Max Drop (Fan Coil Below) (ft)35353550 38/40MVC, MVQ
6 DIMENSIONS -- INDOOR A07336 Model SizeW in. (mm)H in. (mm)D in. (mm)Weight lb (kg) 9K32.09 (815)11.02 (280)7.68 (195)24.2 (11) 12K35.67 (906)11.26 (286)9.25 (235)33.0 (15)18K49.21 (1250)12.80 (325)9.06 (230)55.0 (25) 24K49.21 (1250)12.80 (325)9.06 (230)55.0 (25) DIMENSIONS -- OUTDOOR L1 L2 35 W H Air Flow L3 A07337 Model SizeW in. (mm)H in. (mm)L1 in. (mm)L2 in. (mm)L3 in. (mm)Weight lb (kg) Cooling OnlyWeight lb (kg) Heat Pumps 9K30.71 (780)21.26 (540)21.61 (549)11.81 (300)10.87 (276)77.0 (35)79.2 (36) 12K29.92 (760)23.23 (590)20.87 (530)12.40 (315)11.42 (290)85.8 (39)90.2 (41)18K33.07 (840)27.36 (695)22.05 (560)14.17 (360)13.19 (335)125.4 (57)125.4 (57) 24K31.16 (893)33.86 (860)23.11 (588)13.98 (355)13.11 (333)159.5 (72)160.6 (73) SERVICE VALVE LOCATIONS JK 9K12K18K24KJKJKKJ A07376a Service Valve Locations9K in. (mm)12K in. (mm)18K in. (mm)24K in. (mm) J3.46 (88)3.19 (81)3.46 (88)4.02 (102)K3.46 (88)5.63 (143)3.62 (92)6.57 (167) 38/40MVC, MVQ
7 CLEARANCES -- INDOOR 6 (0.15m) min. 5 (0.13m) min. 6 5 (0.13m) min. (1.8m) A07891 Fig. 2 – Indoor unit clearance CLEARANCES -- OUTDOOR A DB Air-outlet Air-inlet C E A07894 UNIT9k and 12k in. (mm)18k and 24k in. (mm)A24 (610)24 (610)B24 (610)36 (914)C24 (610)24 (610)D4 (102)12 (305)E12 (305)12 (305) Fig. 3 – Outdoor Unit Clearance 38/40MVC, MVQ
8 SYSTEM OPERATING ENVELOPE 53MVC/MVQ System Operating Envelope Chart 40 50 60 70 80 90 100 110 120 -10 0 10 20 30 40 50 60 70 80 90 100 110 120 130 140 Outdoor Temperature (ºF) Indoor Temperature (ºF) 0 5 10 15 20 25 30 35 40 45 50 55 60 -40-35-30-25-20-15-10-5 0 5 1015202530354045505560 Outdoor Temperature (ºC) Indoor Temperature (ºC) Cooling Continuous Operation Heating Continuous Operation 85º F 62ºF 55º75ºF 55ºF 5ºF 80ºF 125º Use low ambient control if the unit will operate in cooling at ambient conditions below 55_F (12.78_C). A08180 Fig. 4 – System Operating Enevelope ELECTRICAL DATA UNIT SIZEOPERATING VOLTAGE*COMPRESSOROUTDOOR FANINDOOR FANMCAMAX FUSE/CB AMP MAX/MINV O L T S --- P H --- H ZRLALRAFLAHPWVOLTSFLAHPW 009127/1041 1 5 --- 1 --- 6 07.5400.600.1022335 DC1.10.034201220 0129.9471.180.044251525 012 253/187208/230 --- 1 --- 60 5.2210.380.1163635 DC1.180.04425915 0187.332.60.780.22453208/230 --- 1 --- 600.260.075311120 0249.734.80.620.2181000.390.112501425 *Permissible limits of the voltage range at which the unit will operate satisfactorily LEGEND FLA--- F u l l L o a d A m p s LRA--- L o c k e d R o t o r A m p s MCA--- Minimum Circuit Amps RLA---RatedLoadAmps 38/40MVC, MVQ
9 WIRING The main power is supplied to the outdoor unit. The field supplied connecting cable from the outdoor unit to indoor unit consists of four wires and provides the power for the indoor unit as well as the communication signal between the outdoor unit and indoor unit. Voltage drop on the connecting cable should be kept to a minimum. Use cable size and max length below: 18 AWG50 ft. (16 m) 16 AWG100 ft. (33 m) CONNECTION DIAGRAMS CONNECTING CABLE CONNECTING CABLECONNECTING CABLE CONTROL CONTROL Notes: 1. Do not use thermostat wire for any connection between indoor and outdoor units. 2. All connections between indoor and outdoor units must be as shown. The connections are sensitive to polarity. 3. On the 18k and 24k units, the “S” terminal “CONTROL” output is pulse DC with a potential AC voltage shock hazard. A07654 Fig. 5 – Connection Diagrams 38/40MVC, MVQ
10 WIRING DIAGRAMS Fig. 6 – Wiring Diagram 38MVC009-- -- --1 W/ 40MVC009-- -- --1 38/40MVC, MVQ