    							40MVC / 38MVC
    40MVQ / 38MVQ
    Service Manual
    High --- Wall Duct Free Split System
    Sizes 009 To 024
    TABLE OF CONTENTS
    PAGE
    SAFETY CONSIDERATIONS 1.........................
    STANDARD FEATURES AND ACCESSORIES 2...........
    SPECIFICATIONS -- COOLING ONLY 3..................
    SPECIFICATIONS -- HEAT PUMP UNITS 4...............
    DIMENSIONS 5......................................
    SERVICE VALVE LOCATIONS 5........................
    CLEARANCES 6.....................................
    SYSTEM OPERATING ENVELOPE 7....................
    ELECTRICAL DATA 7................................
    WIRING 8...........................................
    CONNECTION DIAGRAMS 9..........................
    WIRING DIAGRAMS 10 -- 16...........................
    REFRIGERATION CYCLE DIAGRAM 17.................
    REFRIGERANT LINES 18.............................
    SYSTEM EVACUATION AND CHARGING 19.............
    CONTROL SYSTEM 20...............................
    SYSTEM SAFETIES 20................................
    3MINUTETIMEDELAY 20............................
    COMPRESSOR OVERCURRENT PROTECTION 20 -- 21....
    SEQUENCE OF OPERATION 21........................
    MODES OF OPERATION 22 -- 24........................
    TROUBLESHOOTING 25 -- 37..........................
    APPENDIX 38 -- 43...................................SAFETY CONSIDERATIONS
    Improper installation, adjustment, alteration, service, maintenance,
    or use can cause explosion, fire, electrical shock, or other
    conditions which may cause death, personal injury, or property
    damage. Consult a qualified installer, service agency, or your
    distributor or branch for information or assistance. The qualified
    installer or agency must use factory -- authorized kits or accessories
    when modifying this product. Refer to the individual instructions
    packaged with the kits or accessories when installing.
    Follow all safety codes. Wear safety glasses, protective clothing,
    and work gloves. Use quenching cloth for brazing operations.
    Have fire extinguisher available. Read these instructions
    thoroughly and follow all warnings or cautions included in
    literature and attached to the unit. Consult local building codes and
    National Electrical Code (NEC) for special requirements.
    Recognize safety information. This is the safety--alert symbol
    !!
    When you see this symbol on the unit and in instructions or
    manuals, be alert to the potential for personal injury.
    Understand these signal words: DANGER, WARNING, and
    CAUTION. These words are used with the safety-- alert symbol.
    DANGER identifies the most serious hazards whichwillresult in
    severe personal injury or death. WARNING signifies hazards
    whichcouldresult in personal injury or death. CAUTION is used
    to identify unsafe practices whichmayresult in minor personal
    injury or product and property damage. NOTE is used to highlight
    suggestions whichwillresult in enhanced installation, reliability, or
    operation.
    !WARNING
    ELECTRICAL SHOCK HAZARD
    Failure to follow this warning could result in personal injury
    or death.
    Before installing, modifying, or servicing system, main
    electrical disconnect switch must be in the OFF position.
    There may be more than 1 disconnect switch. Lock out and
    tag switch with a suitable warning label.
    INTRODUCTION
    Section 1 of this Service Manual provides the necessary
    information to service, repair, and maintain the EEZ family of
    Puron air conditioners and heat pumps. Section 2 of this manual is
    an appendix with data required to perform troubleshooting. Use
    the Table of Contents to locate a desired topic. 
    						
    							2
    MODEL NUMBER NOMENCLATURE
    OUTDOOR UNIT
    38 MVC 3 --- 01
    --- 018
    A i r --- C o o l e d C o n d e n s e r
    Unit Type
    MVC--- C o o l i n g O n l y
    MVQ--- H e a t P u m pVo ltage
    1--- 1 1 5 --- 1 --- 6 0
    3--- 208/230 --- 1 --- 60
    Nominal Capacity
    009--- 3 / 4 T o n
    012--- 1 T o n
    018--- 1 --- 1 / 2 T o n
    024--- 2 T o n s
    INDOOR UNIT
    40 MVC 3 --- 01
    --- 018
    Fan Coil Unit
    Unit Type
    MVC--- C o o l i n g O n l y
    MVQ--- H e a t P u m pVo ltage
    ------ 3 0 V D C
    1--- 1 1 5 --- 1 --- 6 0
    3--- 208/230 --- 1 --- 60
    Nominal Capacity
    009--- 3 / 4 T o n
    012--- 1 T o n
    018--- 1 --- 1 / 2 T o n
    024--- 2 T o n s
    SERIAL NUMBER NOMENCLATURE
    01 06
    Week of Manufacture
    Year of Manufacture00001
    Serial NumberV
    Manufacturing Site
    38/40MVC, MVQ 
    						
    							3
    STANDARD FEATURES AND ACCESSORIES
    Ease Of Installation
    Mounting BracketsS
    Low Voltage ControlsS
    Comfort Features
    Microprocessor ControlsS
    Wireless Remote ControlS
    Automatic Air SweepS
    Air Direction ControlS
    Auto Restart FunctionS
    Cold Blow Protection On Heat PumpsS
    Tu r b o M o d e O n S i z e s 9 K a n d 1 2 KS
    Auto Changeover On Heat PumpsS
    Energy Saving Features
    Sleep ModeS
    Stop/Start TimerS
    Safety And Reliability
    3MinuteTimeDelayForCompressorS
    Over Current Protection For CompressorS
    Indoor Coil Freeze ProtectionS
    Indoor Coil High Temperature Protection On Heat PumpsS
    Condenser High Temperature Protection On heat Pumps{S
    Accumulator On Heat PumpsS
    Ease Of Service And Maintenance
    Cleanable FiltersS
    DiagnosticsS
    Liquid Line Pressure TapsS
    Suction And Discharge Pressure Taps (Sizes 18 and 24K)S
    Application Flexibility
    Low Ambient Controls ( --- 20° F)A
    Condensate PumpsA
    Crankcase HeaterA
    Wind BafflesF
    Warranty
    5 --- Year Compressor WarrantyS
    1 --- Parts WarrantyS
    Compressor Extended Warranty Years 6 Thru 10O
    All Parts And Labor Years 2 Thru 5O
    All Parts And Labor Years 2 Thru 5, Compressor Years 6
    Thru 10O
    {Sizes 18k & 24k
    Legend
    SStandard
    A Accessory
    OOptional
    F Field Fabricated
    INDOOR UNITS
    A07892
    Fig. 1 – Condensate Pump
    On high wall fan coils, the condensate pump has a lift capability of
    18 ft (5.5 m) or the discharge side with the pump mounted in the
    fan coil or 6 ft (1.8 m) on the suction side if the pump must be
    remote mounted. The pump mounts inside the unit with quick
    plug--in connections, and is recommended when adequate drain
    line pitch cannot be provided, or when the condensate must move
    up to exit.
    NOTE: An external 115v power source will be required to run the
    pump on unit sizes 9k and 12k.
    OUTDOOR UNITS
    LOW AMBIENT KIT
    The kit controls condenser fan cycling using a pressure switch. It is
    specifically designed to control fan--motor cycles in response to
    saturated condensing pressure. This device maintains a constant
    saturated condensing temperature of 100_F±10_F (37.78_C±
    --12.22_C) at outdoor--air temperatures between 55_F and --20_F
    (12.78_C±--12.22_C), and can be used on all outdoor units
    without changing the outdoor fan motor.
    CRANKCASE HEATER
    Available for units with rotary compressors. Heater clamps around
    compressor oil sump. Recommended for low--ambient applications
    on sizes 9, 12 , 18, 24 and long line applications.
    38/40MVC, MVQ 
    						
    							4
    SPECIFICATIONS -- COOLING ONLY UNITS
    System
    System Model Number5 3 M V C 0 0 9 --- --- --- 15 3 M V C 0 1 2 --- --- --- 15 3 M V C 0 1 2 --- --- --- 35 3 M V C 0 1 8 --- --- --- 3
    System Voltage115 V115 V208/230208/230
    Control Voltage0 --- 1 2 P u l s e D C0 --- 1 2 P u l s e D C0 --- 1 2 P u l s e D CPulse DC
    Capacity (Btuh)9000120001200018000
    SEER13.013.013.013.0
    Refrigerant
    Refrigerant TypeR --- 410A
    Design Pressure (PSIG)550550550550
    Metering DeviceCapillary Tube in Outdoor Unit
    Charge (lb)2.32.93.04.4
    Compressor
    Ty p eRotary
    ModelEA82X1C --- 1FZDU1EA108X1C --- 1FZDU1PA108X1C --- 3FZDUPA150X2CS --- 3KUU
    O i l C h a r g e ( P O E --- o z )11.811.811.825.4
    Capacitor45µF/250VAC45µF/250VAC35µF/370VAC40µF/370VAC
    Rated Current (RLA)7.59.95.27.3
    Locked Rotor Amp (LRA)40472132.6
    Outdoor
    Motor
    Rpm/CFM900/1060900/1090900/1120840/1470
    Diameter (in) .. No. of Blades15.8…315.8…315.8…318.1…3
    Motor (hp)0.1020.1020.1020.224
    Capacitor6.5µF/260VAC6.5µF/260VAC2.5µF/450VAC3µF/450VAC
    Outdoor Coil
    Face Area (sq. ft)4.053.943.945.51
    No. Rows2224
    Fins per inch17171718
    Circuits4444
    Indoor Motor
    Motor Watts/HP20/.03420/.03420/.03425/.044
    Rpm/Cfm (High)1250/3251270/4251270/4251070/630
    Rpm/Cfm (Medium)1000/2601100/3651100/3651000/570
    Rpm/Cfm (Low)800/1901000/3401000/340960/500
    Blower Diameter…Length (in)3.84…25.874.17…25.24.17…25.24.21…37.6
    Indoor
    Coil
    Face Area (sq. ft)2.152.542.544.36
    No. Rows2222
    Fins per inch19.519.519.519.5
    Circuits2336
    Refrigerant
    Lines
    Connection TypeFlare
    Liquid (Mix Phase) (in) OD1/4”1/4”1/4”1/4”
    Vapor Line (in) OD3/8”1/2”1/2”1/2”
    Condensate Drain (in).65 (OD) .53 (ID).65 (OD) .53 (ID).65 (OD) .53 (ID).65 (OD) .53 (ID)
    Maximum Length (ft)656565100
    Max Lift (Fan Coil Above) (ft)35353550
    Max Drop (Fan Coil Below) (ft)35353550
    38/40MVC, MVQ 
    						
    							5
    SPECIFICATIONS -- HEAT PUMP UNITS
    System
    System Model Number5 3 M V Q 0 0 9 --- --- --- 15 3 M V Q 0 1 2 --- --- --- 15 3 M V Q 0 1 2 --- --- --- 35 3 M V Q 0 1 8 --- --- --- 3
    System Voltage115 V115 V208/230208/230
    Control Voltage0 --- 1 2 P u l s e D C0 --- 1 2 P u l s e D C0 --- 1 2 P u l s e D CPulse DC
    Capacity (Btuh)9000120001200018000
    SEER13.013.013.013.0
    HSPF7.77.77.77.7
    Refrigerant
    Refrigerant TypeR --- 410A
    Design Pressure (PSIG)550550550550
    Metering DeviceCapillary Tubes in Outdoor Unit
    Charge (lb)2.353.03.0
    Compressor
    Ty p eRotary
    ModelEA82X1C --- 1FZDU1EA108X1C --- 1FZDU1PA108X1C --- 3FZDUPA150X2CS --- 3KUU
    O i l C h a r g e ( P O E --- o z )11.811.811.825.4
    Capacitor45µF/250VAC45µF/250VAC35µF/370VAC40µF/370VAC
    Rated Current (RLA)7.59.95.27.3
    Locked Rotor Amp (LRA)40472132.6
    Outdoor Motor
    Rpm/CFM900/1060900/1090900/1120840/1470
    Diameter (in) .. No. of Blades15.8…315.8…315.8…318.1…3
    Motor (hp)0.1020.1020.1020.224
    Capacitor6.5µF/260VAC6.5µF/260VAC2.5µF/450VAC3µF/450VAC
    Outdoor Coil
    Face Area (sq. ft)4.053.943.945.51
    No. Rows2224
    Fins per inch17171718
    Circuits4444
    Indoor
    Motor
    Motor Watts/HP20/.03420/.03420/.03425/.044
    Rpm/Cfm (High)1250/3251270/4251270/4251070/630
    Rpm/Cfm (Medium)1000/2601100/3651100/3651000/570
    Rpm/Cfm (Low)800/1901000/3401000/340960/500
    Blower Diameter…Length (in)3.84…25.874.17…25.24.17…25.24.21…37.6
    Indoor
    Coil
    Face Area (sq. ft)2.152.542.544.36
    No. Rows2222
    Fins per inch19.519.519.519.5
    Circuits2336
    Refrigerant
    Lines
    Connection TypeFlare
    Liquid (Mix Phase) (in) OD1/4”1/4”1/4”1/4”
    Vapor Line (in) OD3/8”1/2”1/2”1/2”
    Condensate Drain (in).65 (OD) .53 (ID).65 (OD) .53 (ID).65 (OD) .53 (ID).65 (OD) .53 (ID)
    Maximum Length (ft)656565100
    Max Lift (Fan Coil Above) (ft)35353550
    Max Drop (Fan Coil Below) (ft)35353550
    38/40MVC, MVQ 
    						
    							6
    DIMENSIONS -- INDOOR
    A07336
    Model SizeW
    in. (mm)H
    in. (mm)D
    in. (mm)Weight lb (kg)
    9K32.09 (815)11.02 (280)7.68 (195)24.2 (11)
    12K35.67 (906)11.26 (286)9.25 (235)33.0 (15)18K49.21 (1250)12.80 (325)9.06 (230)55.0 (25)
    24K49.21 (1250)12.80 (325)9.06 (230)55.0 (25)
    DIMENSIONS -- OUTDOOR
    L1
    L2
    35
    W
    H
    Air Flow
    L3
    A07337
    Model SizeW
    in. (mm)H
    in. (mm)L1
    in. (mm)L2
    in. (mm)L3
    in. (mm)Weight lb (kg)
    Cooling OnlyWeight lb (kg)
    Heat Pumps
    9K30.71 (780)21.26 (540)21.61 (549)11.81 (300)10.87 (276)77.0 (35)79.2 (36)
    12K29.92 (760)23.23 (590)20.87 (530)12.40 (315)11.42 (290)85.8 (39)90.2 (41)18K33.07 (840)27.36 (695)22.05 (560)14.17 (360)13.19 (335)125.4 (57)125.4 (57)
    24K31.16 (893)33.86 (860)23.11 (588)13.98 (355)13.11 (333)159.5 (72)160.6 (73)
    SERVICE VALVE LOCATIONS
    JK 9K12K18K24KJKJKKJ
    A07376a
    Service Valve Locations9K
    in. (mm)12K
    in. (mm)18K
    in. (mm)24K
    in. (mm)
    J3.46 (88)3.19 (81)3.46 (88)4.02 (102)K3.46 (88)5.63 (143)3.62 (92)6.57 (167)
    38/40MVC, MVQ 
    						
    							7
    CLEARANCES -- INDOOR
    6 (0.15m) min.
    5
    
    (0.13m)
    min.
    6
    5
    (0.13m)
    min.
    (1.8m)
    A07891
    Fig. 2 – Indoor unit clearance
    CLEARANCES -- OUTDOOR
    A
    DB
    Air-outlet
    Air-inlet
    C
    E
    A07894
    UNIT9k and 12k in. (mm)18k and 24k in. (mm)A24 (610)24 (610)B24 (610)36 (914)C24 (610)24 (610)D4 (102)12 (305)E12 (305)12 (305)
    Fig. 3 – Outdoor Unit Clearance
    38/40MVC, MVQ 
    						
    							8
    SYSTEM OPERATING ENVELOPE
    53MVC/MVQ System Operating Envelope Chart
    40 50 60 70 80 90 100 110 120
    -10 0 10 20 30 40 50 60 70 80 90 100 110 120 130 140
    Outdoor Temperature (ºF)
    Indoor Temperature (ºF)
    0 5
    10
    15
    20
    25 30 35 40
    45
    50
    55
    60 -40-35-30-25-20-15-10-5 0 5 1015202530354045505560
    Outdoor Temperature (ºC)
    Indoor Temperature (ºC)
          Cooling
       Continuous
        Operation
          Heating
       Continuous
        Operation
    85º
    F
    62ºF
    55º75ºF
    55ºF
    5ºF
    80ºF
    125º
    Use low ambient control if the unit will operate in cooling at ambient conditions below 55_F (12.78_C).
    A08180
    Fig. 4 – System Operating Enevelope
    ELECTRICAL DATA
    UNIT
    SIZEOPERATING
    VOLTAGE*COMPRESSOROUTDOOR FANINDOOR FANMCAMAX
    FUSE/CB
    AMP
    MAX/MINV O L T S --- P H --- H ZRLALRAFLAHPWVOLTSFLAHPW
    009127/1041 1 5 --- 1 --- 6 07.5400.600.1022335 DC1.10.034201220
    0129.9471.180.044251525
    012
    253/187208/230 --- 1 --- 60
    5.2210.380.1163635 DC1.180.04425915
    0187.332.60.780.22453208/230 --- 1 --- 600.260.075311120
    0249.734.80.620.2181000.390.112501425
    *Permissible limits of the voltage range at which the unit will operate satisfactorily
    LEGEND
    FLA--- F u l l L o a d A m p s
    LRA--- L o c k e d R o t o r A m p s
    MCA--- Minimum Circuit Amps
    RLA---RatedLoadAmps
    38/40MVC, MVQ 
    						
    							9
    WIRING
    The main power is supplied to the outdoor unit. The field supplied connecting cable from the outdoor unit to indoor unit consists of four
    wires and provides the power for the indoor unit as well as the communication signal between the outdoor unit and indoor unit.
    Voltage drop on the connecting cable should be kept to a minimum. Use cable size and max length below:
    18 AWG50 ft. (16 m)
    16 AWG100 ft. (33 m)
    CONNECTION DIAGRAMS
    CONNECTING CABLE CONNECTING CABLECONNECTING CABLE
    CONTROL
    CONTROL
    Notes:
    1. Do not use thermostat wire for any connection between indoor and outdoor units.
    2. All connections between indoor and outdoor units must be as shown. The connections are sensitive to polarity.
    3. On the 18k and 24k units, the “S” terminal “CONTROL” output is pulse DC with a potential AC voltage shock hazard.
    A07654
    Fig. 5 – Connection Diagrams
    38/40MVC, MVQ 
    						
    							10
    WIRING DIAGRAMS
    Fig. 6 – Wiring Diagram 38MVC009-- -- --1 W/ 40MVC009-- -- --1
    38/40MVC, MVQ 
    						