6 720 644 894 Installation instructions11 Fig. 8 Concentric vent kit example 3.3.2 Vent specifications Establish vent clearances that comply with the vent manufacturers specifications and all applicable national/local codes. Venting specifications * ULC S636-95, UL1738 certified Condensate drain requirements An external condensate drain (not supplied with the heater) must be installed under the following conditions: • All vertical terminating vent installations. •...
Page 12
6 720 644 89412 Installation instructions Maximum combustion air and exhaust pipe length The following tables display the maximum allowable straight pipe lengths for combustion air and exhaus t piping with consideration to the number of elbows used. Reduce the equivalent length for each elbow used from the maximum allowable length depending on the system used. Refer to table 5 if using 3 diamet er venting. Refer to table 6 if using 4 diameter venti ng.Use of...
Page 13
6 720 644 894 Installation instructions13 Calculation example for 3 venting: Exhaust Combustion air Calculation example for 4 venting: Exhaust Combustion air System usedConcentric Number of 90° elbows needed: 1 Number of 45° elbows needed: 2 Table 8 Calculation of example Max. length 23’ 90 ° elbow reduction - 5’ sub-total = 18’ 45 ° elbow reduction - 6’ Total = 12’ Table 9 i For this example, the maximum allowable exhaust pipe length is 12 feet. System usedConcentric Number of 90° elbows...
Page 14
6 720 644 89414 Installation instructions Required direct vent terminal clearances (twin pipe / concentric penetration) Fig. 9 * For clearances not specified in ANSI Z223.1 / NFPA 54 or CSA-B149.1, one of the following shall be indicated: a) A minimum clearance value determined by testing in accordance with section 2.20, or; b) A reference to the following footnote: “Clearance in accordance with local installation co des and the requirements of the gas supplier.” 6720608836-23.1Av Canadian...
Page 15
6 720 644 894 Installation instructions15 Required other than direct vent terminal clearances (single pipe penetration) Fig. 10 * For clearances not specified in ANSI Z223.1 / NFPA 54 or CSA-B149.1, one of the following shall be indicated: a) A minimum clearance value determined by testing in accordance with section 2.20, or; b) A reference to the following footnote: “Clearance in accordance with local installation co des and the requirements of the gas supplier.” 6720608836-23.1Av Canadian...
Page 16
6 720 644 89416 Installation instructions 3.3.3 Vent configuration examples Below are approved examples of vertical and horizon tal venting installations. Fig. 11 Vertical venting system (single pipe penetra - tion) Fig. 12 Horizontal venting installation (combustion air piping not shown) Warning: Single pipe penetration should be used in non-freezing climates only! Fig. 13 Horizontal venting system (concentric vent) Fig. 14 Horizontal parallel venting system (twin pip e direct vent)...
Page 17
6 720 644 894 Installation instructions17 Fig. 15 Horizontal venting system (single pipe pene- tration) *Warning: Single pipe penetration should be used in non-freezing climates only! 3.3.4 Vent connections Attaching the exhaust and air inlet connection adaptors to the top of the heater B Attach the flue gas exhaust accessory to the top of the unit Fig. 16 (position 1) using the 4 screws an d gasket provided, and fully insert vent pipe into th e accessory. If using 4 venting, a 3 to 4 increase r...
Page 18
6 720 644 89418 Installation instructions Appliance condensate drain installation The appliance comes equipped with an internal condensate drain and siphon. This drains condensati on formed in the secondary heat exchanger. Piping must be installed under the condensate drain outlet on t he water heater and piped for disposal in accordance w ith local codes. Fig. 18 Appliance drain installation External condensate drain installation If an external condensate drain (installer...
Page 19
6 720 644 894 Installation instructions19 Backdraft reducer The Heat Fab backdraft reducer (9301BFP) is the pre - ferred option for limiting backdraft (see Fig. 20). Note: The following solution is available only for 3 diameter venting. Fig. 20 Part nr 9301BFP Installation For this solution to be effective, the internal fla pper must be 100% closed when the water heater is not running . Refer to Figures 22 and 23 for preferred installation positions in the vent system. Installation...
Page 20
6 720 644 89420 Installation instructions 3.3.7 Fan speed adjustment ! IMPORTANT INFORMATION: Natural gas heaters with installation altitudes below 2,000 ft above sea level disregard this section. Installation adjustment: After installing the tankless water heater, the fan speed values for minimum power (P2) and maximum power (P1) may need adjustment due to variations in altit ude and vent pipe length. Failure to make necessary adjustments to fan speed values may...