Page 21
6 720 644 894 Installation instructions21 Natural GasLiquid propane Altitude (above sea level)Vent terminalTotal equivalent vent length1)Minimum power fan speed (P2)Maximum power fan speed (P1)Maximum power fan speed (P1) 0 - 2000 ft (0 - 610 m) Concentric 6 - 25 ft 13 No modification required No modification required For operation at eleva- tions above 2,000 ft (610 m) the equip- ment ratings shall be reduced at the rate of 4% for each 1,000 ft (305 m) above sea level 26 - 46 ft 13...
Page 22
6 720 644 89422 Installation instructions Adjusting minimum power fan speed (P2) To select fan speed: B Press ON/OFF button into OFF. B Press and hold Program button and press ON/OFF button to turn appliance ON. Fig. 24 B As soon as 188 is displayed, release Program button , and the display reads P2. B Press to enter P2 adjustment. The current set- ting will appear on the display (factory default: 12). B Press or to choose the fan speed suitable with your installation,...
Page 23
6 720 644 894 Installation instructions23 Attention residents of the Commonwealth of Massachu setts: In the Commonwealth of Massachusetts the following regulation went into effect on 12/30/2005: (a)For all side wall horizontally vented gas fueled equipment installed in every dwelling, building or structure used in whole or in part for residential purposes, including those owned or operated by the Commonwealth and where the side wall exhaust vent termination is...
Page 24
6 720 644 89424 Installation instructions 3.4 Combustion air requirements Twin pipe and Concentric pipe The water heater is designed as a sealed combustion appliance. It is recommended that the combustion ai r be provided by a dedicated 3” or 4” pipe from the outside (twin pipe) or by connecting to the Concent ric vent kit (see Fig. 8). The combustion air pipe may b e PVC or any other rigid sealed 3 or 4 pipe. The combustion air piping must pitch down...
Page 25
6 720 644 894 Installation instructions25 3.5 Proper location for installing your heater Carefully select the location of the water heater. For your safety and for proper heater operation, you mu st provide combustion air to the heater and a proper exhaust vent system. Follow the guidelines below: B 1. Locate the heater where venting, gas and plumbing connections are feasible and convenient. B 2. The hot water lines should be kept short and insulated to save...
Page 26
6 720 644 89426 Installation instructions Fig. 27 Leveling wall mounting bracket Fig. 28 Mounting the heater 3.8Gas piping & connections Before connecting the gas supply, check the rating plate on the right side of the heater to be sure th at the heater is rated for the same gas to which it will b e connected. In the United States: The installation must conform with local codes or, in the absence of local codes, the National Fuel Gas Code ANSI Z223.1/NFPA 54. In Canada:...
Page 27
6 720 644 894 Installation instructions27 Fig. 29 Gas connection Once connections are made, check for gas leaks at a ll joints. Apply some gas leak detection solution to a ll gas fittings. Bubbles are a sign of a leak. A combustib le gas detector may also be used to detect for leaks. GAS LINE SIZING The gas supply piping for a single heater should be sized for a maximum draw of 199,000 BTUH. Measure the length of gas supply line from the buildings g as main to the heater and...
Page 28
6 720 644 89428 Installation instructions FOR NATURAL GAS Maximum Capacity of pipe in Cubic Feet of Gas per H our for Gas Pressure of 0.5 Psig or less and a Pressure drop of 0.3” in Water Column (0.75mbar).(Based on a 0.60 Specific Gravity Gas) Btu numbers given in thousands. Fig. 31 Follow boxed numbers for piping just one C 1050 ES (example: ¾” B.I. Natural Gas pipe for 10 ft (3.0m). will handle 278,000 btu’s (81.5 kWh). For multiple appliances combine the total maximum btu input load and then...
Page 29
6 720 644 894 Installation instructions29 3.9 Water connections BWhen facing the heater, the ¾” cold connection is o n the bottom right and the hot connection is on the b ot- tom left. Centrally locating the water heater is re com- mended to keep hot water distribution times even throughout the structure. Fig. 32 Fig. 33 Water filter 1 Water valve with engine 2 Water filter BThe use of unions when connecting both water pipes to the inlet and outlet connections is required. This will...
Page 30
6 720 644 89430 Installation instructions Connecting the pressure relief valve (PRV) A listed pressure relief valve must be installed at the time of installation. No valve is to be placed between the PRV and the heater . No reducing coupling or other restriction may be installed in the discharge line. The discharge line must be a minimum of 4” above a drain and installed such that it allows complete dr ainage of both the PRV and the line. The discharge line mu st...