Altek Model 934 Milliamp Voltage Loop Calibrator Manual
Here you can view all the pages of manual Altek Model 934 Milliamp Voltage Loop Calibrator Manual. The Altek manuals for Calibrator are available online for free. You can easily download all the documents as PDF.
Page 41
6 OPERATING INSTRUCTIONS ENABLING ADDITIONAL RANGES & FUNCTIONS The Model 934 has two additional ranges for displaying % DP Flow and Engineering Units. Additional functions are AUTO- CHEK (automatic stepping of outputs) and AUTO-OFF. These ranges & functions are enabled by configuring DIP Switches (see next page). After the functions are enabled they are available as selections during setup (see OPERATING INSTRUCTIONS, SOURCE or READ). AUTO-OFF The Model 934 can be set up to turn itself off after 30...
Page 42
5 OPERATING INSTRUCTIONS GENERAL FIELD & BENCH USE The Model 934 comes with a carrying case and a built-in tilt stand/hanger. The 934 is held securely in the case by VELCRO ® for use with the carrying case open. The carrying case also has a snap-on belt loop which can also be looped around a pipe or rail. The tilt stand is easily raised by pulling the stand until it locks into place. The stand can also be reversed for use as a hanger to suspend the Model 934. RESTORE DEFAULT SETTINGS The Model 934...
Page 43
4 ROCHESTER NY 14623ALTEK 934SOURCE19.934mA mA/V LOOP CALIBRATOROFF ONHI SET LOMAX READ MIN 9VDC AUTO-CHEK HI MINREAD0.000V SOURCE STOREQUIK-CHEK ®SETUP READ RESETSETUP 500 MAXSOURCESOURCEREAD OPERATING INSTRUCTIONS GENERAL TURN-ON Each time the Model 934 is turned on, the LCD will display all segments for about 1 second. It then displays the most recently selected Source & Read Settings. 1) Move the power switch to ON. All segments on the LCD are turned on during self test. 2) The upper half of...
Page 44
3 GENERAL INFORMATION MILLIAMP CALIBRATION Use at any point in your 4 to 20 milliamp loop. Source milliamps directly into your receivers with loop loads up to 1200 Ohms. Simulate 2-Wire Transmitters for checkout of field wiring and total loop testing. Power and measure 2-Wire or 4-Wire transmitters on the bench before installation. Read Transmitter & Controller outputs up to 52.00 mA. Display directly in milliamps, percent of 4 to 20 mA, percent of DP Flow or engineering units to match the scale of your...
Page 45
2 GENERAL INFORMATION Simultaneously source and read any combination of process milliamp and voltage signals. Alteks Model 934 combines all the functionality of a milliamp and a voltage calibrator! This dual function calibrator continuously displays the output and input signals. The top half of the display indicates the output setting while the lower half of the display shows the signal being measured. Calibrate state of the art equipment such as smart transmitters and indicators to 4 1/2 or more digits...
Page 46
1 FEATURES • DUAL LIQUID CRYSTAL DISPLAY Simultaneous Source and Read • LABORATORY ACCURATE ±(0.012% of Reading + 0.008% of Full Scale Reading) Accurate to ±0.004 mA from 4 to 20 mA • USER SETTABLE “QUIK-CHEK®s” Set any Span & Zero • FULL FIVE DIGIT DISPLAYS Source up to 24.000 mA, 20.000 V or 999.90 mV Read up to 52.000 mA, 99.990 V or 999.90 mV • SCALEABLE DISPLAY Set in engineering units • SPEED SENSITIVE DIGIPOT Fast setting to any desired value • “AUTO-CHEK” TM OUTPUTS Automatically outputs in 2, 3,...
Page 47
ORDERING INFORMATION Part No. MODEL 934 MULTIFUNCTION LOOP CALIBRATOR 934 A carrying case is included with each Model 934 Contents GENERAL INFORMATION......................................................... 2 YOUR NEW CALIBRATOR...................................................... 2 MILLIAMP CALIBRATION...................................................... 3 VOLTAGE CALIBRATION ........................................................ 3 QUIK-CHEK...
Page 48
PN 1886535 Rev A April 2002 ©2002 Altek Industries, Inc. Specifications subject to change without notice. All tights reserved. Printed in U.S.A. Multifunction Loop Calibrator Model 934