Home > Aimco Brakes > AcraDyne > Aimco Brakes AcraDyne iEC iControl DC Tool Controller Users Guide

Aimco Brakes AcraDyne iEC iControl DC Tool Controller Users Guide

    Download as PDF Print this page Share this page

    Have a look at the manual Aimco Brakes AcraDyne iEC iControl DC Tool Controller Users Guide online for free. It’s possible to download the document as PDF or print. UserManuals.tech offer 85 Aimco Brakes manuals and user’s guides for free. Share the user manual or guide on Facebook, Twitter or Google+.

    							31 
     
    Networking 
    Optionally the controller can include the fastening 
    results in the output image. Including the fastening 
    results increases the output size to thirty four bytes of data. 
     
    Each value will be sent as a real (IEEE 754 float) and  can be configured as little or big endian to match 
    the receiving equipment. 
     
     
       
      
    Controller Outputs
     
        
    Bit 
         
    7  6 5 4 3 2 1 0 
    Byte   0 
                      Tool 
    Ready  Tool 
    Enable 
    1           Bypass  Batch 
    Com-
    plete   
    Status 
    NOK  Status 
    OK 
    2-5  
    Final Torque (Real) 
    6-9  
    Torque Low Limit (Real) 
    10-13  Torque Target (Real) 
    14-17  Torque High Limit (Real) 
    18-21  Final Angle (Real) 
    22-25  Angle Low Limit (Real) 
    26-29  Angle Target (Real) 
    30-33  Angle High Limit (Real) 
    Byte Bit Name  Function 
    0  0 
    Tool Enable  The enabled state of the tool. 
    1  Tool Ready  On if the tool is ready to run.  Will
     be off if tool is disabled or there is a fault 
    on the controller. 
    2-7  Not used    
    1  0 
    Status OK  Rundown status on for an accept. This bit is timed and will be on for ½ sec-
    ond. 
    1  Status NOK  Rundown status on for a reject. This bit is timed and will be on for ½ sec-
    ond. 
    2  Not used    
    3  Batch Complete  Indicates the batch is complete.  Will go off when batch is reset or when the 
    tool enable is turned off. 
    4  Bypass  State of the bypass input. 
    5-7  Not used 
       
    						
    							32 
     
    Networking 
    The reading of the results data sh
    ould be done at the rising edge of  the “Status OK” and “Status NOK”.  
    This will insure the correct results are captured cons istently.   All the results are zeroed after the “Status 
    OK” and “Status NOK” are turned off. 
     
    The controller consumes thirty two by tes of inputs (Assembly instance 112). 
     
     
       
      
    Controller Inputs
     
        
    Bit 
         
    7  6  5 4  3 2  1 0 
    Byte   0 
    PSET 
    1    PLC 
    Enable  White 
    Flash  Pause           Tool 
    Enable 
    2-11  Sequence Number 
    12-31  Serial Number 
    Byte Bit Name  Function 
    0 0-7  PSET  Set the active parameter set of 1-32.  If 0 the active parameter set is left un-
    changed. 
    1  0 
    Tool Enable  If PLC Enable is 0 this input is ignored.  If PLC Enable is 1 this bit can be used 
    to enable or disable the tool. 
    1-3  Not used    
    4  Pause  Setting Pause to 1 cause the light stack to strobe.  Setting it to 0 put the light 
    stack back into its normal operation. 
    5  White Flash  Setting White Flash to 1 cause the light stack to flash the white light.  Setting it 
    to 0 put the light stack back into its normal operation. 
    6  PLC Enable  Setting PLC Enable to 1 allows the T
    ool Enable bit.  Setting it to 0 disables the 
    Tool Enable function. 
    7  Not used    
    2-11 0-7  Sequence Number  10 character Sequence Number. 
    12-31 0-7  Serial Number 
    20 character Serial Number.  
    						
    							33 
     
    Error Proofing 
    Barcode Reader 
    The max length of a barcode is 20 characters if it is longer the leading  characters will be lost and the last 
    20 will be used.  Since barcode readers  send their characters in burst there is no need to program in a 
    length.  The software just waits for the reader to st op sending.  Once the barcode is read the results are 
    stored as the VIN. 
     
    Barcode Options
     
    When a good barcode is received it can optionally re set the batch and/or enable the tool.  A good bar-
    code is determined by the VIN Pattern Matching opt ion.  If the barcode matches one of the parameter 
    sets VIN matching patterns it will be considered a good read. 
     
      Reset Batch on Good Barcode scan 
      If enabled, controller w ill reset the batch count on a good barcode scan. 
     
      Enable Tool on Good Barcode scan 
      If enabled, controller will enable t he tool on a good barcode scan. 
     
    VIN Pattern Matching
     
    All new VINs from barcod e readers,  Profibus,  DeviceNET, Ether net/IP or protocols are checked against 
    for a  VIN match against each PSET  (starting from #1 and through #8).  If a match is found the PSET is 
    changed.  In order to qualify as a match the rece ived barcode must be at least as long as the match 
    string.  The match string can contain  “don’t care” characters (‘.’) as a wild card.  In the example below a 
    barcode of “Abc123” selects PSET  #1, “abc567” selects PSET #2, “def” selects PSET #4, “ABc” selects 
    PSET #5, and “AB” does nothing. 
     
     
      
    						
    							34 
     
    APPENDIX A: Error Codes & Descriptions 
     
    Error Code #
     Fault   Description      
     
    AUT1
     
    1      TID Timeout    Tool ID board communication timeout 
    32    Tool GND    Ground circuit problem between controller and tool 
    64      Power On Throttle  RUN command on during power up 
    128     Button Timeout    Button (run, fwd, rev) communication timeout 
    256   Button State  Illegal bu tton state (example fwd and rev) 
    512     Undefined Voltage  Tool voltage parameter undefined 
    2048    Tool Update Req’d.  Tool parameter file  is not compatible with controller version 
    4096    Illegal Tool    Tool type is not compatible with controller 
     
     
    CYC1
     
    1      Free Run Timeout  Tool has run below threshold level with no load for 5+ seconds 
    2      Load Run Timeout  Tool has run above threshold level for 15+ seconds 
    4      Hall Error    Motor communication signal error 
    8      Tool Offset    Tool cannot reach target torque due to transducer error 
    64      Tool Level    Tool transducer output beyond electrical limits 
    512   Locked Rotor  Motor ha s stalled for 100+ milliseconds 
    1024    Drive Fault    Motor drive shut down or not responding 
     
     
    EXT1
     
    1      PSet Value    Illegal parameter set value 
    8      TID Param Value  Tool ID board communication error 
    32      TID Param Timeout  Tool ID board communication error 
    4096    Target Value Fault  Torque target  out of range of tool capabilities 
     
     
    EXT2
     
    1    TID EE Write    Communication timeout while writing to tool memory 
    2    Drive Comm    Communication timeout reading / writing to motor drive 
    4    Vbus      Measured controller voltage is not within required limits 
    8   Drive Update Req
      Drive firmware not compatible with low speed control  
     
    NOTE
    —Multiple Error Codes will be displayed as the sum of each error code number indicated in 
    the table above; for example, AUT1: 129 represe nts AUT1: 128 and AUT1: 1, which would be a 
    tool ID board timeout and a button timeout  
    						
    							35 
     
    Appendix B: KDM Menu Structures 
    Main Menu Structure 
    Parameter Set-up Menu  
    						
    							36 
     
    APPENDIX B: KDM Menu Structures 
    Administration Menu  
    						
    							37 
     
    APPENDIX C: I/O Diagram & Definitions 
    1 2 
    10 
    9 8 7 6 5 4 3 
    25 
    19 18 17 16 15 14  13 12 
    11  
    24 23 22 21 20 
    1 
    25 
    14  13 
    Pin #  
    Definition 
    1    Output—Accept 
    2    Output—Reject 
    3      Output—In Cycle 
    4      Output—Torque High 
    5      Output—1-4 Common 
     
    6      Input—Run Forward 
    7      Input—Run Reverse 
    8      Input—Disable Tool 
    9       Input—PSET Bit 1 
    10      Input—PSET Bit 2 
    11       Input—PSET Bit 3 
    12     Input—Reset Batch 
    13     Input—Decrement  Batch  Pin #  
    Definition 
    14   Output—Torque Low 
    15   Output—Angle High 
    16   Output—Angle Low 
    17   Output—Batch Complete 
    18   Output—5-8 Common 
     
    19   Input—Analog 1 
    20   Input—Analog 2 
     
    21   GND 
    22   GND 
    23   +24VDC 
    24   +24VDC 
    25   +24VDC 
     
      
    iEC2, iEC3 and iEC4 series controllers have a range of Input / Output (I/O) capab\
    ilities.   
    By referencing the diagram below , the user can access the controllers I/O functions for  
    a variety of line control and error proofing functions.  A connector kit is available (PT # 
    23490)  from AIMCO to make connection to the I/O port on the iEC controller easier;  
    contact your AIMCO sales representative for ordering information.  
    						
    							38 
     
    LOGIC I/O CONNECTIONS 
     
    NOTE: Turn off the system before connecting to the LOGIC  I/O port.  There may be risk of damaging the controller. 
     
    24Vdc Supply:  The internal 24Vdc power can supply up to 2 amps. 
     
    Inputs:   The inputs are a sinking configuration with the common connected to the ground pins. 24V dc is logic ON and 0Vdc is logic OFF. 
     
     
    LOGIC I/O CONNECTIONS 
     
     
    Outputs:  The outputs are normally open relay contacts. The relays are rated for 24Vdc, 1 amp. 
     
    Note: If the outputs are driving an inductive load such as a solenoi d or large relay, it is recommended to add a diode in parallel with the load  
    to prevent voltage surges. 
     
     
     
    APPENDIX C: I/O Diagram & Definitions  
    						
    							39 
     
    APPENDIX C: I/O Diagram & Definitions 
    I/O Definitions 
     
    Output 1, Accept  
     
    DB25 pin 1.  The relay closes after achieving the target torque 
    or target angle.  The output is programmable for latched or 
    timed operation using ToolWare. 
     
    Output 2, Reject 
     
    DB25 pin 2.  The relay closes if the final torque or angle is  outside of the High/Low limits.  The output is programmable for 
    latched or timed operation using ToolWare. 
     
    Output 3, In Cycle 
     
    DB25 pin 3.  The relay is programmable for operating at threshold torque or on throttle pull.  The relay closes when the 
    torque level passes the threshold torque value when setup for “at threshold”.  The relay closes when the throttle is pulled 
    when setup for “at throttle”. 
     
    Output 4, Torque High 
     
    DB25 pin 4.  The relay closes if the final torque exceeds t he torque high level.  The output is programmable for latched or 
    timed operation using ToolWare. 
     
    Output 5, Torque Low 
     
    DB25 pin 14.  The relay closes if the final torque falls below  the torque low level.  The output is programmable for latched 
    or timed operation using ToolWare. 
     
    Output 6, Angle High 
     
    DB25 pin 15.  The relay closes if the final angle exceeds t he angle high level.  The angle is measured from the torque 
    threshold level.  The output is programmable for latched or timed operation using ToolWare. 
     
    Output 7, Angle Low 
     
    DB25 pin 16.  The relay closes if the final angle falls below  the angle low level.  The angle is measured from the torque 
    threshold level.  The output is programmable for latched or timed operation using ToolWare. 
     
    Output 8, Batch Done 
     
    DB25 pin 17.  The relay closes after completing the batch count.  The output is programmable for latched or timed opera-
    tion using ToolWare.  The batch count is also set using ToolWare. 
     
    Output 1-4 Common 
     
    DB25 pin 5.  Connects to the co mmon pins of output relays 1-4. 
     
    Output 5-8 Common 
     
    DB25 pin 18.  Connects to the common pins of output relays 5-8. 
     
    Analog In 1 
     
    DB25 pin 19.  Analog input 1, for future use.  
    						
    							40 
     
    APPENDIX C: I/O Diagram & Definitions 
    Analog In 2 
     
    DB25 pin 20.  Analog input 2, for future use.
     
     
    Input 1, Run Forward 
     
    DB25 pin 6.  Runs tool forward.  Buttons from I/O must be selected using ToolWare. 
     
    Input 2, Run Reverse 
     
    DB25 pin 7.  Runs tool reverse.  Buttons  from I/O must be selected using ToolWare. 
     
    Input 3, Disable Tool 
     
    DB25 pin 8.  Prevents the tool from running. 
     
    Input 4, Pset Bit 1 
     
    DB25 pin 9.  Binary bit one for selecting parameter sets.  See chart below. 
     
    Input 5, Pset Bit 2 
     
    DB25 pin 10.  Binary bit two for selecting parameter sets.  See chart below. 
     
    Input 6, Pset Bit 3 
     
    DB25 pin 11.  Binary bit three for selecting parameter sets.  See chart below. 
     
    Input 7, Reset Batch 
     
    DB25 pin 12.  Sets the batch count to zero. 
     
    Input 8, Decrement Batch 
     
    DB25 pin 13. Decreases the batch count by one. 
     
    GND 
     
    DB25 pins 21 and 22.  0VDC. 
     
    +24VDC 
     
    DB25 pins 23-25.  +24VDC 
     
     
    Parameter selection chart 
     
       
      Pset 
    1  Pset 
    2  Pset 
    3  Pset 
    4  Pset 
    5  Pset 
    6  Pset 
    7  Pset 
    8 
    Bit 1   0  1  0  1  0  1  0  1 
    Bit 2   0  0  1  1  0  0  1  1 
    Bit 3   0  0  0  0  1  1  1  1  
    						
    All Aimco Brakes manuals Comments (0)

    Related Manuals for Aimco Brakes AcraDyne iEC iControl DC Tool Controller Users Guide