Page 11

RT-PRC014H-E4
11
To obtain product selection, please contact your local Trane sales office with the following 
information:
Table 2 – Mandatory informations to select a rooftop
System type Cooling OnlyHeat pump
Airflow information
Configuration of return duct 1 - Horizontal flow
2 - DownflowOther
........................................
Configuration of supply duct 3 - Horizontal flow
4 - DownflowOther
........................................
Unit airflow
........................................m3/h...

Page 12

RT-PRC014H-E4 12
Table 3 – General data TKD/TKH, YKD/YKH
TKD / TKH
YKD / YKHTKD / TKH
YKD / YKHTKD / TKH
YKD / YKHTKD / TKH
YKD / YKHTKD/H TKD/H TKD/H
155 175 200 250 265 290 340
R410A R410A R410A R410A R410A R410A R410A
Eurovent Performances (1)
Net Cooling Capacity (kW) 44.2 50.6 56.5 67.9 73.6 85.4 94.9
Total Power input in cooling (kW) 14.7 16.8 18.2 21.8 25.4 29.3 34.9
EER 3.01 3.01 3.11 3.11 2.90 2.91 2.72
Eurovent Effi ciency class CoolingAAAABBC
Main Power supply V/Ph/Hz 400/3/50 400/3/50 400/3/50...

Page 13

RT-PRC014H-E4
13
TKD / TKH
YKD / YKHTKD / TKH
YKD / YKHTKD / TKH
YKD / YKHTKD / TKH
YKD / YKHTKD/H TKD/H TKD/H
155 175 200 250 265 290 340
R410A R410A R410A R410A R410A R410A R410A
Indoor Fan
Minimum Airfl ow (m3/h) 6800 7880 8970 11280 11520 12960 14400
Nominal Airfl ow (m3/h) 8500 9850 11210 14100 14400 16200 18000
Maximum Airfl ow (m3/h) 10200 11820 13450 16920 17280 19440 21600
Static pressure available (4) (Pa) 150 75 175 75 75 450 450
Maximum static pressure available (5) (Pa) 350 375 450 375 375 500...

Page 14

RT-PRC014H-E4 14
TKD / TKH
YKD / YKHTKD / TKH
YKD / YKHTKD / TKH
YKD / YKHTKD / TKH
YKD / YKHTKD/H TKD/H TKD/H
155 175 200 250 265 290 340
R410A R410A R410A R410A R410A R410A R410A
Unit construction
Sheet metal / ThicknessType / 
mmGalvaSteel / 
1.2GalvaSteel / 
1.2GalvaSteel / 
1.2GalvaSteel / 
1.2GalvaSteel / 
1.2GalvaSteel / 
1.2GalvaSteel / 
1.2
PaintType / 
RALPolyester / 
9002 Polyester / 
9002 Polyester / 
9002 Polyester / 
9002 Polyester / 
9002 Polyester / 
9002 Polyester / 
9002 
Insulation /...

Page 15

RT-PRC014H-E4
15
Table 4 – General data WKD/WKH, DKD/DKH
WKD / WKH
DKD / DKHWKD / WKH
DKD / DKHWKD / WKH
DKD / DKHWKD / WKH
DKD / DKHWKD / WKH
DKD / DKHWKD / WKH
DKD / DKH
125 155 200 265 290 340
R410A R410A R410A R410A R410A R410A
Eurovent Performances (1)
Net Cooling Capacity (kW) 37.7 45.9 64.5 71.4 78.8 88.8
Total Power input in cooling (kW) 11.4 15.1 20.9 25.8 28.4 33.4
EER 3.30 3.04 3.09 2.77 2.77 2.65
Eurovent Effi ciency class Cooling A A A C C C
Main Power supply V/Ph/Hz 400/3/50 400/3/50...

Page 16

RT-PRC014H-E4 16
WKD / WKH
DKD / DKHWKD / WKH
DKD / DKHWKD / WKH
DKD / DKHWKD / WKH
DKD / DKHWKD / WKH
DKD / DKHWKD / WKH
DKD / DKH
125 155 200 265 290 340
R410A R410A R410A R410A R410A R410A
Indoor Fan
Minimum Airfl ow (m3/h) 5710 6800 8970 11520 12960 14400
Nominal Airfl ow (m3/h) 7140 8500 11210 14400 16200 18000
Maximum Airfl ow (m3/h) 8570 10200 13450 17280 19440 21600
Static pressure available (4) (Pa) 200 175 200 75 450 450
Maximum static pressure available (5) (Pa) 425 325 350 375 500 500
Type FC...

Page 17

RT-PRC014H-E4
17
WKD / WKH
DKD / DKHWKD / WKH
DKD / DKHWKD / WKH
DKD / DKHWKD / WKH
DKD / DKHWKD / WKH
DKD / DKHWKD / WKH
DKD / DKH
125 155 200 265 290 340
R410A R410A R410A R410A R410A R410A
Physical data - Operating (3)
Length (mm) 2726 2726 3107 3107 3987 3987
Width (mm) 1811 1811 2167 2154 2154 2154
Height (mm) 1313 1313 1704 1704 1440 1440
Operating weight  WKD/WKH  (kg) 637 654 819 889 1183 1191
 DKD/DKH (kg) 707 729 898 968 1268 1276
Shipping weight  WKD/WKH  (kg) 685 707 890 954 1248 1256...

Page 18

RT-PRC014H-E4 18
Data given at 250Pa & 35°C ambient for nominal airflow rate
Sound Power Référence = 10E--12 Watt
Table 5 – Overall Outdoor Sound Power level (Env.)
63 Hz 125 Hz 250 Hz 500 Hz 1000 Hz 2000 Hz 4000 Hz 8000 Hz
TKD/H - YKD/H 155 64.2 dBA 67.8 dBA 71.0 dBA 77.2 dBA 79.6 dBA 78.8 dBA 72.7 dBA 68.7 dBA 84 dBA
TKD/H - YKD/H 175 64.2 dBA 67.8 dBA 71.0 dBA 77.1 dBA 79.5 dBA 78.9 dBA 72.3 dBA 68.7 dBA 84 dBA
TKD/H - YKD/H 200 73.2 dBA 72.3 dBA 77.0 dBA 80.7 dBA 81.6 dBA 78.2 dBA 71.3 dBA 55.4 dBA...

Page 19

RT-PRC014H-E4
19
Table 8 – Electrical characteristics
Indoor Fan
Belt DriveIndoor Fan
Direct Drive
Control Compressor 1 / 2Standard 
driveOversized 
driveStandard 
driveOversized 
driveExhaust 
fan Outdoor FanElectric 
Heat
UnitMax 
AmpsMax AmpsStart 
AmpsMax Amps Max Amps Max Amps Qty Max Amps Max Amps
TK* / YK* 155 0.5 18.5 / 11.2 142 / 82 4 6.4 5.4 8.5 3.0 2 1.2 36
TK* / YK* 175 0.5 20.0 / 13.9 142 / 87 6.4 9 5.4 9.8 3.0 2 1.2 36
TK* / YK* 200 0.5 18.5 / 18.5 142 / 142 6.4 9 9.4 12.4 3.0 2 2.5 54
TK*...

Page 20

RT-PRC014H-E4 20
Figure 8Dimensions, Weights and Clearances
Overall unit dimensions, shipping weights and operating weights are given in 
the General Data tables.
Table 10 – Minimum recommended clearances
Minimum clearance
UNIT12345
TK* / YK* 155 1900 1800 1220 1000 1300
TK* / YK* 175 1900 1800 1220 1000 1300
TK* / YK* 200 1900 1800 1220 1000 1300
TK* / YK* 250 1900 1800 1220 1000 1300
TK* 265 1900 1800 1220 1000 1300
TK* 290 1900 1800 1220 1000 1300
TK* 340 1900 1800 1220 1000 1300
WK* / DK* 125 1900...