Page 11
RT-PRC014H-E4 11 To obtain product selection, please contact your local Trane sales office with the following information: Table 2 – Mandatory informations to select a rooftop System type Cooling OnlyHeat pump Airflow information Configuration of return duct 1 - Horizontal flow 2 - DownflowOther ........................................ Configuration of supply duct 3 - Horizontal flow 4 - DownflowOther ........................................ Unit airflow ........................................m3/h...
Page 12
RT-PRC014H-E4 12 Table 3 – General data TKD/TKH, YKD/YKH TKD / TKH YKD / YKHTKD / TKH YKD / YKHTKD / TKH YKD / YKHTKD / TKH YKD / YKHTKD/H TKD/H TKD/H 155 175 200 250 265 290 340 R410A R410A R410A R410A R410A R410A R410A Eurovent Performances (1) Net Cooling Capacity (kW) 44.2 50.6 56.5 67.9 73.6 85.4 94.9 Total Power input in cooling (kW) 14.7 16.8 18.2 21.8 25.4 29.3 34.9 EER 3.01 3.01 3.11 3.11 2.90 2.91 2.72 Eurovent Effi ciency class CoolingAAAABBC Main Power supply V/Ph/Hz 400/3/50 400/3/50 400/3/50...
Page 13
RT-PRC014H-E4 13 TKD / TKH YKD / YKHTKD / TKH YKD / YKHTKD / TKH YKD / YKHTKD / TKH YKD / YKHTKD/H TKD/H TKD/H 155 175 200 250 265 290 340 R410A R410A R410A R410A R410A R410A R410A Indoor Fan Minimum Airfl ow (m3/h) 6800 7880 8970 11280 11520 12960 14400 Nominal Airfl ow (m3/h) 8500 9850 11210 14100 14400 16200 18000 Maximum Airfl ow (m3/h) 10200 11820 13450 16920 17280 19440 21600 Static pressure available (4) (Pa) 150 75 175 75 75 450 450 Maximum static pressure available (5) (Pa) 350 375 450 375 375 500...
Page 14
RT-PRC014H-E4 14 TKD / TKH YKD / YKHTKD / TKH YKD / YKHTKD / TKH YKD / YKHTKD / TKH YKD / YKHTKD/H TKD/H TKD/H 155 175 200 250 265 290 340 R410A R410A R410A R410A R410A R410A R410A Unit construction Sheet metal / ThicknessType / mmGalvaSteel / 1.2GalvaSteel / 1.2GalvaSteel / 1.2GalvaSteel / 1.2GalvaSteel / 1.2GalvaSteel / 1.2GalvaSteel / 1.2 PaintType / RALPolyester / 9002 Polyester / 9002 Polyester / 9002 Polyester / 9002 Polyester / 9002 Polyester / 9002 Polyester / 9002 Insulation /...
Page 15
RT-PRC014H-E4 15 Table 4 – General data WKD/WKH, DKD/DKH WKD / WKH DKD / DKHWKD / WKH DKD / DKHWKD / WKH DKD / DKHWKD / WKH DKD / DKHWKD / WKH DKD / DKHWKD / WKH DKD / DKH 125 155 200 265 290 340 R410A R410A R410A R410A R410A R410A Eurovent Performances (1) Net Cooling Capacity (kW) 37.7 45.9 64.5 71.4 78.8 88.8 Total Power input in cooling (kW) 11.4 15.1 20.9 25.8 28.4 33.4 EER 3.30 3.04 3.09 2.77 2.77 2.65 Eurovent Effi ciency class Cooling A A A C C C Main Power supply V/Ph/Hz 400/3/50 400/3/50...
Page 16
RT-PRC014H-E4 16 WKD / WKH DKD / DKHWKD / WKH DKD / DKHWKD / WKH DKD / DKHWKD / WKH DKD / DKHWKD / WKH DKD / DKHWKD / WKH DKD / DKH 125 155 200 265 290 340 R410A R410A R410A R410A R410A R410A Indoor Fan Minimum Airfl ow (m3/h) 5710 6800 8970 11520 12960 14400 Nominal Airfl ow (m3/h) 7140 8500 11210 14400 16200 18000 Maximum Airfl ow (m3/h) 8570 10200 13450 17280 19440 21600 Static pressure available (4) (Pa) 200 175 200 75 450 450 Maximum static pressure available (5) (Pa) 425 325 350 375 500 500 Type FC...
Page 17
RT-PRC014H-E4 17 WKD / WKH DKD / DKHWKD / WKH DKD / DKHWKD / WKH DKD / DKHWKD / WKH DKD / DKHWKD / WKH DKD / DKHWKD / WKH DKD / DKH 125 155 200 265 290 340 R410A R410A R410A R410A R410A R410A Physical data - Operating (3) Length (mm) 2726 2726 3107 3107 3987 3987 Width (mm) 1811 1811 2167 2154 2154 2154 Height (mm) 1313 1313 1704 1704 1440 1440 Operating weight WKD/WKH (kg) 637 654 819 889 1183 1191 DKD/DKH (kg) 707 729 898 968 1268 1276 Shipping weight WKD/WKH (kg) 685 707 890 954 1248 1256...
Page 18
RT-PRC014H-E4 18 Data given at 250Pa & 35°C ambient for nominal airflow rate Sound Power Référence = 10E--12 Watt Table 5 – Overall Outdoor Sound Power level (Env.) 63 Hz 125 Hz 250 Hz 500 Hz 1000 Hz 2000 Hz 4000 Hz 8000 Hz TKD/H - YKD/H 155 64.2 dBA 67.8 dBA 71.0 dBA 77.2 dBA 79.6 dBA 78.8 dBA 72.7 dBA 68.7 dBA 84 dBA TKD/H - YKD/H 175 64.2 dBA 67.8 dBA 71.0 dBA 77.1 dBA 79.5 dBA 78.9 dBA 72.3 dBA 68.7 dBA 84 dBA TKD/H - YKD/H 200 73.2 dBA 72.3 dBA 77.0 dBA 80.7 dBA 81.6 dBA 78.2 dBA 71.3 dBA 55.4 dBA...
Page 19
RT-PRC014H-E4 19 Table 8 – Electrical characteristics Indoor Fan Belt DriveIndoor Fan Direct Drive Control Compressor 1 / 2Standard driveOversized driveStandard driveOversized driveExhaust fan Outdoor FanElectric Heat UnitMax AmpsMax AmpsStart AmpsMax Amps Max Amps Max Amps Qty Max Amps Max Amps TK* / YK* 155 0.5 18.5 / 11.2 142 / 82 4 6.4 5.4 8.5 3.0 2 1.2 36 TK* / YK* 175 0.5 20.0 / 13.9 142 / 87 6.4 9 5.4 9.8 3.0 2 1.2 36 TK* / YK* 200 0.5 18.5 / 18.5 142 / 142 6.4 9 9.4 12.4 3.0 2 2.5 54 TK*...
Page 20
RT-PRC014H-E4 20 Figure 8Dimensions, Weights and Clearances Overall unit dimensions, shipping weights and operating weights are given in the General Data tables. Table 10 – Minimum recommended clearances Minimum clearance UNIT12345 TK* / YK* 155 1900 1800 1220 1000 1300 TK* / YK* 175 1900 1800 1220 1000 1300 TK* / YK* 200 1900 1800 1220 1000 1300 TK* / YK* 250 1900 1800 1220 1000 1300 TK* 265 1900 1800 1220 1000 1300 TK* 290 1900 1800 1220 1000 1300 TK* 340 1900 1800 1220 1000 1300 WK* / DK* 125 1900...