Home > Trane > Cooler > Trane Voyager 2 Manual

Trane Voyager 2 Manual

    Download as PDF Print this page Share this page

    Have a look at the manual Trane Voyager 2 Manual online for free. It’s possible to download the document as PDF or print. UserManuals.tech offer 12 Trane manuals and user’s guides for free. Share the user manual or guide on Facebook, Twitter or Google+.

    							RT-PRC014H-E4
    11
    To obtain product selection, please contact your local Trane sales office with the following 
    information:
    Table 2 – Mandatory informations to select a rooftop
    System type Cooling OnlyHeat pump
    Airflow information
    Configuration of return duct 1 - Horizontal flow
    2 - DownflowOther
    ........................................
    Configuration of supply duct 3 - Horizontal flow
    4 - DownflowOther
    ........................................
    Unit airflow
    ........................................m3/h
    Fresh air rate 
    ........................................m3/h
    ........................................% of nominal airflow
    External static pressure on 
    return duct
    ........................................Pa
    External static pressure on 
    supply duct
    ........................................Pa
    Cooling mode design conditions
    Unit cooling capacity
    ........................................kW
    Indoor air Dry Bulb
    ........................................°C
    Indoor air wet Bulb / Relative 
    Humidity
    ........................................°C
    ........................................%
    Outdoor air Dry Bulb
    ........................................°C
    Heating mode design conditions
    Heating capacity
    ........................................kW
    Auxiliary heat type
    Electric Heat
    Gas Heat Hot Water coil
    Gas type
    Natural gas G20Natural gas G25Propane gas G31
    Auxiliary heating capacity
    ........................................kW
    Indoor air Dry Bulb
    ........................................°C
    Outdoor air Dry Bulb
    ........................................°C
    Outdoor air wet Bulb / Relative 
    Humidity
    ........................................°C
    ........................................% (only for Heat pump)
    Options
    Air filter class
    ........................................
    Variable speed drive
    With
    Without
    Economizer type
    WithoutManual fresh airComparative enthalpy 
    economizer
    Energy recovery on exhaust / 
    fresh airWithoutRotary heat wheel Plate heat exchanger
    Fresh air control
    ConstantRemote referenceCO2 sensor controled
    Unit controlLocal control without 
    schedulingLocal control with 
    schedulingMulti-unit centralized 
    controlRemote relay interface 
    control
    Remote control communication 
    interfaceLONModbusBacnetTrane
    Smoke detector
    WithWithoutFire detector
    WithWithoutDisconnect switch
    WithWithoutDirty filter switch
    WithWithoutFan fail switch
    WithWithoutOutdoor coil corrosion 
    protectionWithoutEpoxy coating
    Indoor coil corrosion protection
    WithoutEpoxy coating
    Roofcurb
    NoneFlatAdjustable pitch
    Selection Procedure 
    						
    							RT-PRC014H-E4 12
    Table 3 – General data TKD/TKH, YKD/YKH
    TKD / TKH
    YKD / YKHTKD / TKH
    YKD / YKHTKD / TKH
    YKD / YKHTKD / TKH
    YKD / YKHTKD/H TKD/H TKD/H
    155 175 200 250 265 290 340
    R410A R410A R410A R410A R410A R410A R410A
    Eurovent Performances (1)
    Net Cooling Capacity (kW) 44.2 50.6 56.5 67.9 73.6 85.4 94.9
    Total Power input in cooling (kW) 14.7 16.8 18.2 21.8 25.4 29.3 34.9
    EER 3.01 3.01 3.11 3.11 2.90 2.91 2.72
    Eurovent Effi ciency class CoolingAAAABBC
    Main Power supply V/Ph/Hz 400/3/50 400/3/50 400/3/50 400/3/50 400/3/50 400/3/50 400/3/50
    Outdoor sound power level env. (dBA) 84 84 86 86 86 88 89
    Indoor sound power level in duct (dBA) 74 77 77 82 83 83 85
    Outdoor sound pressure level env. (6) (dBA) 52 52 54 54 54 56 57
    Unit amps
    Unit max amps (3) (A) 39,0 45,8 51,5 54,5 62,5 75,7 83,3
    Unit start-up amps (A) 163 168 175 177 187 209 251
    Unit power factor (1) 0,75 0,72 0,74 0,77 0,79 0,79 0,8
    Short circuit current (kA) 10 10 10 10 10 10 10
    Electric Heater (TKD / TKH)
    Heating Capacity (kW) 25 25 37.5 37.5 37.5 37.5 37.5
    Capacity steps (kW) 12.5 / 12.5 12.5 / 12.5 25 / 12.5 25 / 12.5 25 / 12.5 25 / 12.5 25 / 12.5
    Max Amps (2) (A) 36 36 54 54 54 54 54
    Gas burner (YKD / YKH)
    Heating Models G350 G350 G350 G350 N/A N/A N/A
    Heating Input (G20) (kW) 77 77 77 77 - - -
    Heating Output (kW) 69,3 69,3 69,3 69,3 - - -
    Steady State Effi ciency (%) 90 90 90 90 - - -
    No. Burners #1111 - - -
    No. Stages #2222 - - -
    Gas Connection Pipe Size 3/4 NPT 3/4 NPT 3/4 NPT 3/4 NPT - - -
    Compressor
    Number #2222222
    Type Scroll Scroll Scroll Scroll Scroll Scroll Scroll
    Model 5T / 9T 6T / 10T 9T / 9T 10T / 10T 12T / 12T 13T / 13T 15T / 15T
    Max Amps(2) (A) 18.5 / 11.2 20 / 13.9 18.5 / 18.5 20 / 20 23 / 23 25.2 / 25.2 29 / 29
    Locked rotor Amps (2) (A) 142 / 82 142 / 87 142 / 142 142 / 142 147 / 147 158 / 158 197 / 197
    Outdoor Coil
    Type Wavy Wavy Wavy Wavy Wavy Wavy Wavy
    Tube Size OD (mm)  9.52 9.52 9.52 9.52 9.52 9.52 9.52
    Face Area (m²) 2.23 2.62 3.00 3.39 3.39 4.26 4.26
    Rows / Fin series # / FPF 2 / 192 2 / 192 2 / 192 2 / 192 2 / 192 2 / 192 2 / 192
    Indoor Coil
    Type Wavy Wavy Wavy Wavy Wavy Wavy Wavy
    Tube Size OD (mm)  9.52 9.52 9.52 9.52 9.52 9.52 9.52
    Face Area (m²) 1.63 1.63 2.42 2.42 2.42 2.42 2.42
    Rows / Fin series # / FPF 3 / 180 3 / 180 2 / 180 3 / 168 3 / 168 4 / 168 4 / 168
    Refrigerant Control Exp.Valve Exp.Valve Exp.Valve Exp.Valve Exp.Valve Exp.Valve Exp.Valve
    Drain Connection No./Size (mm)  1 / 3/4 NPT 1 / 3/4 NPT 1 / 3/4 NPT 1 / 3/4 NPT 1 / 3/4 NPT 1 / 3/4 NPT 1 / 3/4 NPT
    Outdoor Fan
    Nominal Airfl ow (m3/h) 17300 18000 26700 27300 27300 39500 39500
    Type Axial Axial Axial Axial Axial Axial Axial
    Diameter (mm) 630 630 710 710 710 710 710
    Drive type Direct Direct Direct Direct Direct Direct Direct
    Number #2222233
    Motor HP (kW) 0.6 0.6 1.1 1.1 1.1 1.1 1.1
    Motor Max Amps(1) (A) 1.2 1.2 2.5 2.5 2.5 2.5 2.5
    Motor RPM (rpm) 900 900 900 900 900 900 900
    (1)  At Eurovent rating conditions : Indoor return Air (27°C DB / 19°C WB) - Ambiant 35°C 
    according to EN14511:2013
    (2) Per motor under 400V
    (3) For standard unit, with oversized drive, without electric heater options 
    (4) At the nominal air ow with standard drive(5) At the nominal air ow with oversized drive when available
    (6) At 10m from the unit in a free  eld
    Electrical & refrigerant charge Data are subject to change without notice. 
    Please refer to unit nameplate data.
    General Data 
    						
    							RT-PRC014H-E4
    13
    TKD / TKH
    YKD / YKHTKD / TKH
    YKD / YKHTKD / TKH
    YKD / YKHTKD / TKH
    YKD / YKHTKD/H TKD/H TKD/H
    155 175 200 250 265 290 340
    R410A R410A R410A R410A R410A R410A R410A
    Indoor Fan
    Minimum Airfl ow (m3/h) 6800 7880 8970 11280 11520 12960 14400
    Nominal Airfl ow (m3/h) 8500 9850 11210 14100 14400 16200 18000
    Maximum Airfl ow (m3/h) 10200 11820 13450 16920 17280 19440 21600
    Static pressure available (4) (Pa) 150 75 175 75 75 450 450
    Maximum static pressure available (5) (Pa) 350 375 450 375 375 500 500
    Type FC Centrifugal FC Centrifugal FC Centrifugal FC Centrifugal FC Centrifugal FC Centrifugal FC Centrifugal
    Number #1111111
    Diameter / Width (in / in) 15 / 15 15 / 15 18 / 18 18 / 18 18 / 18 18 / 18 18 / 18
    Belt driven fan version
    Motor HP (Standard/Oversized) (kW) 1.8 / 3.0 3.0 / 4.6 3.0 / 4.6 4.6 / - 4.6 / 5.5 7.5 / 9 7.5 / 9
    Motor Max Amps(Standard/Oversized) (A) 4 / 6.4 6.4 / 9 6.4 / 9 9 / 9 9 / 11 15 / 17.3 15 / 17.3
    Motor Locked rotor Amps (Standard/
    Oversized)(A) 36.4 / 57 57 / 71.9 57 / 71.9 71.9 / - 69 / 95 128 / 149 128 / 149
    Motor RPM (Standard/Oversized) (rpm) 1450 / 2870 2870 / 2900 2870 / 2900 2900 / - 2900 / 2900 2900 / 2900 2900 / 2900
    Direct driven fan version
    Number #1111111
    Motor HP (Standard/Oversized) (kW) 2.2 / 5.5 2.2 / 5.5 4 / 5.5 7.5 / 5.5 7.5 / 5.5 7.5 / 15 7.5 / 15
    Motor Max Amps(Standard/Oversized) (A) 5.4 / 8.5 5.4 / 9.8 9.4 / 12.4 11.3 / 13.3 11.3 / 13.5 16.4 / 23.3 16.6 / 22.9
    Motor RPM (Standard/Oversized) (rpm) 957 / 1455 957 / 1455 963 / 963 1455 / 963 1455 / 963 970 / 1457 970 / 1457
    Energy Recovery Module (5)
    Plate Heat exchanger version
    Heat recovery effi ciency at 10% / 
    50% fresh air(%) 51% / 50% 51% / 50% 56% / 54% 56% / 53% 57% / 54% 57% / 54% 57% / 53%
    Air pressure drop at 10% / 
    50% fresh air(Pa) 2Pa / 43Pa 2Pa / 56Pa 3Pa / 70Pa 6Pa / 105Pa 2Pa / 63Pa 3Pa / 77Pa 4Pa / 93Pa
    Exhaust fan kW at 10% / 
    50% fresh air(kW)0.1kW / 
    0.4kW0.1kW / 
    0.7kW0.2kW / 
    0.5kW0.2kW / 
    0.9kW0.3kW / 
    0.7kW0.3kW / 
    0.9kW0.3kW / 
    1.1kW
    Length (Downfl ow / Horizontal fl ow) (mm) 2440 / 2288 2440 / 2288 2745 / 2745 2745 / 2745 2745 / 3050 2745 / 3050 2745 / 3050
    Width (Downfl ow / Horizontal fl ow) (mm) 1838 / 1838 1838 / 1838 2143 / 2143 2143 / 2143 2295 / 2143 2295 / 2143 2295 / 2143
    Height (Downfl ow / Horizontal fl ow) (mm) 1553 / 1350 1553 / 1350 1553 / 1503 1553 / 1503 1705 / 1503 1705 / 1503 1705 / 1503
    Weight (Downfl ow / Horizontal fl ow) (kg) 592 / 543 592 / 543 786 / 779 786 / 779 862 / 889 862 / 889 862 / 889
    Rotary Wheel Heat exchanger version
    Heat recovery effi ciency at 10% / 
    50% fresh air(%) 84% / 69% 84% / 65% 85% / 68% 84% / 65% 81% / 70% 80% / 67% 80% / 67%
    Air pressure drop at 10% / 
    50% fresh air(Pa) 13Pa / 109Pa 17Pa / 130Pa 14Pa / 109Pa 19Pa / 144Pa 9Pa / 87Pa 11Pa / 101Pa 13Pa / 115Pa
    Exhaust fan kW at 10% / 
    50% fresh air(kW)0.2kW / 
    0.5kW0.2kW / 
    0.6kW0.2kW / 
    0.6kW0.2kW / 
    0.8kW0.2kW / 
    0.9kW
    0.3kW / 
    0.9kW0.3kW / 
    1.1kW
    Length (Downfl ow / Horizontal fl ow) (mm) 2593 / 1778 2593 / 1778 2745 / 2745 2745 / 2745 2898 / 2898 2898 / 2898 2898 / 2898
    Width (Downfl ow / Horizontal fl ow) (mm) 1838 / 1563 1838 / 1563 2143 / 2143 2143 / 2143 1990 / 2143 1990 / 2143 1990 / 2143
    Height (Downfl ow / Horizontal fl ow) (mm) 1553 / 2293 1553 / 2293 1705 / 1655 1705 / 1655 2010 / 1960 2010 / 1960 2010 / 1960
    Weight (Downfl ow / Horizontal fl ow) (kg) 686 / 710 686 / 710 846 / 906 846 / 906 973 / 1095 973 / 1095 973 / 1095
    Filters
    Type Furnished 2 Throwaway 2 Throwaway 2 Throwaway 2 Throwaway 2 Throwaway 2 Throwaway 2 Throwaway
    (No.) Size Recommended
    TKH / YKH * #2x 
    (500x500x50)2x 
    (500x500x50)8x 
    (500x625x50)8x 
    (500x625x50)8x 
    (500x625x50)8x 
    (500x625x50)8x 
    (500x625x50)
    ++4x 
    (500x625x50)+4x 
    (500x625x50)
    TKD / YKD * #2x 
    (500x500x50)2x 
    (500x500x50)4x 
    (500x500x50)4x 
    (500x500x50)4x 
    (500x500x50)4x 
    (500x500x50)4x 
    (500x500x50)
    ++4x 
    (500x625x50)+4x 
    (500x625x50)+4x 
    (500x625x50)+4x 
    (500x625x50)+4x 
    (500x625x50)+4x 
    (500x625x50)+4x 
    (500x625x50)
    Operating limits
    Minimum operating outdoor air temp. °C -18 -18 -18 -18 -18 -18 -18
    Maximum operating outdoor air temp. °C 50 50 50 50 50 50 50
    Minimum intake air temp. on the 
    indoor coil °C 18 18 18 18 18 18 18
    Physical data - Operating (3)
    Length (mm) 2726 2726 3107 3107 3107 3987 3987
    Width (mm) 1811 1811 2167 2167 2154 2154 2154
    Height (mm) 1313 1313 1704 1704 1704 1704 1704
    Operating weight  TKD/TKH  (kg) 598 631 768 789 869 1140 1148
     YKD/YKH (kg) 673 706 847 869
    Shipping weight  TKD/TKH  (kg) 652 666 819 864 934 1205 1213
     YKD/YKH (kg) 693 726 902 948
    (1)  At Eurovent rating conditions : Indoor return Air (27°C DB / 19°C WB) - Ambiant 35°C 
    according to EN14511:2013
    (2) Per motor under 400V
    (3) For standard unit, with oversized drive, without electric heater options 
    (4) At the nominal air ow with standard drive(5) At the nominal air ow with oversized drive when available
    (6) At 10m from the unit in a free  eld
    Electrical & refrigerant charge Data are subject to change without notice. 
    Please refer to unit nameplate data.
    General Data
    Table 3 – General data TKD/TKH, YKD/YKH (Continued) 
    						
    							RT-PRC014H-E4 14
    TKD / TKH
    YKD / YKHTKD / TKH
    YKD / YKHTKD / TKH
    YKD / YKHTKD / TKH
    YKD / YKHTKD/H TKD/H TKD/H
    155 175 200 250 265 290 340
    R410A R410A R410A R410A R410A R410A R410A
    Unit construction
    Sheet metal / ThicknessType / 
    mmGalvaSteel / 
    1.2GalvaSteel / 
    1.2GalvaSteel / 
    1.2GalvaSteel / 
    1.2GalvaSteel / 
    1.2GalvaSteel / 
    1.2GalvaSteel / 
    1.2
    PaintType / 
    RALPolyester / 
    9002 Polyester / 
    9002 Polyester / 
    9002 Polyester / 
    9002 Polyester / 
    9002 Polyester / 
    9002 Polyester / 
    9002 
    Insulation / ThicknessType / 
    mmM0 / 25 M0 / 25 M0 / 25 M0 / 25 M0 / 25 M0 / 25 M0 / 25
    System Data
    Refrigerant circuit #2222222
    Capacity steps % 60 / 40 60 / 40 50 / 50 50 / 50 50 / 50 50 / 50 50 / 50
    Refrigerant Charge (3)
    Circuit A (YKD / YKH) (kg) 3.8 4.2 6.4 7.6 7.6 9.2 9.2
    Circuit B (YKD / YKH) (kg) 6.3 6.9 6.4 7.6 7.6 9.2 9.2
    (1)  At Eurovent rating conditions : Indoor return Air (27°C DB / 19°C WB) - Ambiant 35°C 
    according to EN14511:2013
    (2) Per motor under 400V
    (3) For standard unit, with oversized drive, without electric heater options 
    (4) At the nominal air ow with standard drive(5) At the nominal air ow with oversized drive when available
    (6) At 10m from the unit in a free  eld
    Electrical & refrigerant charge Data are subject to change without notice. 
    Please refer to unit nameplate data.
    Table 3 – General data TKD/TKH, YKD/YKH (Continued)
    General Data 
    						
    							RT-PRC014H-E4
    15
    Table 4 – General data WKD/WKH, DKD/DKH
    WKD / WKH
    DKD / DKHWKD / WKH
    DKD / DKHWKD / WKH
    DKD / DKHWKD / WKH
    DKD / DKHWKD / WKH
    DKD / DKHWKD / WKH
    DKD / DKH
    125 155 200 265 290 340
    R410A R410A R410A R410A R410A R410A
    Eurovent Performances (1)
    Net Cooling Capacity (kW) 37.7 45.9 64.5 71.4 78.8 88.8
    Total Power input in cooling (kW) 11.4 15.1 20.9 25.8 28.4 33.4
    EER 3.30 3.04 3.09 2.77 2.77 2.65
    Eurovent Effi ciency class Cooling A A A C C C
    Main Power supply V/Ph/Hz 400/3/50 400/3/50 400/3/50 400/3/50 400/3/50 400/3/50
    Net Heating Capacity (kW) 35.5 46.5 57.8 66.0 77.5 86.7
    Total Power input in Heating (kW) 10.1 13.5 17.5 20.2 23.2 27.0
    COP 3.53 3.45 3.30 3.26 3.34 3.21
    Eurovent Effi ciency class Heating A A B B B B
    Outdoor sound power level env. (dBA) 84 84 86 86 87 88
    Indoor sound power level in duct (dBA) 79 74 81 83 83 85
    Outdoor sound pressure level env. (6) (dBA) 52 52 54 54 55 56
    Unit amps
    Unit max amps (3) (A) 37.1 39.7 54.5 62.5 73.0 80.6
    Unit start-up amps (A) 110 123 177 187 206 249
    Unit power factor (1) 0.67 0.72 0.76 0.80 0.80 0.80
    Short circuit current (kA) 10 10 10 10 10 10
    Electric Heater (WKD / WKH)
    Heating Capacity (kW) 25 25 37.5 37.5 37.5 37.5
    Capacity steps (kW) 12.5 / 12.5 12.5 / 12.5 25 / 12.5 25 / 12.5 25 / 12.5 25 / 12.5
    Max Amps (2) (A) 36 36 54 54 54 54
    Gas burner (DKD / DKH)
    Heating Models G250 G350 G350 G350 G400 G400
    Heating Input (G20) (kW) 53 77 77 77 85 85
    Heating Output (kW) 48,2 69,3 69,3 69,3 77,4 77,4
    Steady State Effi ciency (%) 91 90 90 90 91 91
    No. Burners #111111
    No. Stages #222222
    Gas Connection Pipe Size 3/4 NPT 3/4 NPT 3/4 NPT 3/4 NPT 3/4 NPT 3/4 NPT
    Compressor
    Number #222222
    Type Scroll Scroll Scroll Scroll Scroll Scroll
    Model 6T / 6T 7.5T / 7.5T 10T / 10T 12T / 12T 13T / 13T 15T / 15T
    Max Amps (2) (A) 13.9 / 13.9 15.2 / 15.2 20 / 20 23 / 23 25.2 / 25.2 29 / 29
    Locked rotor Amps (2) (A) 87 / 87 98 / 98 142 / 142 147 / 147 158 / 158 197 / 197
    Outdoor Coil
    Type Wavy Wavy Wavy Wavy Wavy Wavy
    Tube Size OD (mm)  9.52 9.52 9.52 9.52 9.52 9.52
    Face Area (m²) 2.23 2.62 3.39 3.39 4.26 4.26
    Rows / Fin series # / FPF 2 / 192 2 / 192 2 / 192 2 / 192 2 / 192 2 / 192
    Refrigerant Control Exp.Valve Exp.Valve Exp.Valve Exp.Valve Exp.Valve Exp.Valve
    Indoor Coil
    Type Wavy Wavy Wavy Wavy Wavy Wavy
    Tube Size OD (mm)  9.52 9.52 9.52 9.52 9.52 9.52
    Face Area (WKD / WKH) (m²) 1.63 1.63 2.42 2.42 2.42 2.42
    Rows / Fin series # / FPF 3 / 180 3 / 180 3 / 168 3 / 168 4 / 168 4 / 168
    Refrigerant Control Exp.Valve Exp.Valve Exp.Valve Exp.Valve Exp.Valve Exp.Valve
    Drain Connection No./Size (mm)  1 / 3/4 NPT 1 / 3/4 NPT 1 / 3/4 NPT 1 / 3/4 NPT 1 / 3/4 NPT 1 / 3/4 NPT
    Outdoor Fan
    Nominal Airfl ow (m3/h) 17400 18000 27300 25400 34000 34000
    Type Axial Axial Axial Axial Axial Axial
    Diameter (mm) 630 630 710 710 630 630
    Drive type Direct Direct Direct Direct Direct Direct
    Number #222244
    Motor HP (kW) 0.6 0.6 1.1 1.1 0.6 0.6
    Motor Max Amps(1) (A) 1.2 1.2 2.5 2.5 1.2 1.2
    Motor RPM (rpm) 900 900 900 900 900 900
    (1)  At Eurovent rating conditions : Indoor return Air (27°C DB / 19°C WB) - Ambiant 35°C 
    according to EN14511:2013
    (2) Per motor under 400V
    (3) For standard unit, with oversized drive, without electric heater options 
    (4) At the nominal air ow with standard drive(5) At the nominal air ow with oversized drive when available
    (6) At 10m from the unit in a free  eld
    Electrical & refrigerant charge Data are subject to change without notice. 
    Please refer to unit nameplate data.
    General Data 
    						
    							RT-PRC014H-E4 16
    WKD / WKH
    DKD / DKHWKD / WKH
    DKD / DKHWKD / WKH
    DKD / DKHWKD / WKH
    DKD / DKHWKD / WKH
    DKD / DKHWKD / WKH
    DKD / DKH
    125 155 200 265 290 340
    R410A R410A R410A R410A R410A R410A
    Indoor Fan
    Minimum Airfl ow (m3/h) 5710 6800 8970 11520 12960 14400
    Nominal Airfl ow (m3/h) 7140 8500 11210 14400 16200 18000
    Maximum Airfl ow (m3/h) 8570 10200 13450 17280 19440 21600
    Static pressure available (4) (Pa) 200 175 200 75 450 450
    Maximum static pressure available (5) (Pa) 425 325 350 375 500 500
    Type FC Centrifugal FC Centrifugal FC Centrifugal FC Centrifugal FC Centrifugal FC Centrifugal
    Number #111111
    Diameter / Width (in / in) 15 / 15 15 / 15 18 / 18 18 / 18 18 / 18 18 / 18
    Belt driven fan version
    Motor HP (Standard/Oversized) (kW) 1.8 / 3.0 1.8 / 3.0 3.0 / 4.6 4.6 / 5.5 7.5 / 9 7.5 / 9
    Motor Max Amps(Standard/Oversized) (A) 4.0 / 6.4 4.0 / 6.4 6.4 / 9.0 9.0 / 10.5 14.7 / 17.3 14.7 / 17.3
    Motor Locked rotor Amps (Standard/
    Oversized)(A) 36.4 / 57 36.4 / 57 57 / 71.9 69 / 95 128 / 149 128 / 149
    Motor RPM (Standard/Oversized) (rpm) 1450 / 2870 1450 / 2870 2870 / 2900 2900 / 2900 2900 / 2900 2900 / 2900
    Direct driven fan version
    Motor HP (Standard/Oversized) (kW) 2.2 / 5.5 2.2 / 5.5 4 / 5.5 7.5 / 5.5 7.5 / 15 7.5 / 15
    Motor Max Amps(Standard/Oversized) (A) 5.5 / 7.9 5.4 / 8.5 9.4 / 12.4 11.3 / 13.5 16.4 / 23.3 16.6 / 22.9
    Motor RPM (Standard/Oversized) (rpm) 957 / 1455 957 / 1455 963 / 963 1455 / 963 970 / 1457 970 / 1457
    Energy Recovery Module (5)
    Plate Heat exchanger version
    Heat recovery effi ciency at 10% / 
    50% fresh air(%) 51% / 50% 51% / 50% 56% / 54% 57% / 54% 57% / 54% 57% / 53%
    Air pressure drop at 10% / 
    50% fresh air(Pa) 1Pa / 32Pa 2Pa / 43Pa 3Pa / 70Pa 2Pa / 63Pa 3Pa / 77Pa 4Pa / 93Pa
    Exhaust fan kW at 10% / 
    50% fresh air(kW) 0.1kW / 0.3kW 0.1kW / 0.4kW 0.2kW / 0.5kW 0.3kW / 0.7kW 0.3kW / 0.9kW 0.3kW / 1.1kW
    Length (Downfl ow / Horizontal fl ow) (mm) 2440 / 2288 2440 / 2288 2745 / 2745 2745 / 3050 2745 / 3050 2745 / 3050
    Width (Downfl ow / Horizontal fl ow) (mm) 1838 / 1838 1838 / 1838 2143 / 2143 2295 / 2143 2295 / 2143 2295 / 2143
    Height (Downfl ow / Horizontal fl ow) (mm) 1553 / 1350 1553 / 1350 1553 / 1503 1705 / 1503 1705 / 1503 1705 / 1503
    Weight (Downfl ow / Horizontal fl ow) (kg) 592 / 543 592 / 543 786 / 779 862 / 889 862 / 889 862 / 889
    Rotary Wheel Heat exchanger version
    Heat recovery effi ciency at 10% / 
    50% fresh air(%) 86% / 70% 84% / 69% 85% / 68% 81% / 70% 80% / 67% 80% / 67%
    Air pressure drop at 10% / 
    50% fresh air(Pa) 10Pa / 88Pa 13Pa / 109Pa 14Pa / 109Pa 9Pa / 87Pa 11Pa / 101Pa 13Pa / 115Pa
    Exhaust fan kW at 10% / 
    50% fresh air(kW) 0.2kW / 0.4kW 0.2kW / 0.5kW 0.2kW / 0.6kW 0.2kW / 0.9kW 0.3kW / 0.9kW 0.3kW / 1.1kW
    Length (Downfl ow / Horizontal fl ow) (mm) 2593 / 1778 2593 / 1778 2745 / 2745 2898 / 2898 2898 / 2898 2898 / 2898
    Width (Downfl ow / Horizontal fl ow) (mm) 1838 / 1563 1838 / 1563 2143 / 2143 1990 / 2143 1990 / 2143 1990 / 2143
    Height (Downfl ow / Horizontal fl ow) (mm) 1553 / 2293 1553 / 2293 1705 / 1655 2010 / 1960 2010 / 1960 2010 / 1960
    Weight (Downfl ow / Horizontal fl ow) (kg) 686 / 710 686 / 710 846 / 906 973 / 1095 973 / 1095 973 / 1095
    Filters
    Type Furnished 2 Throwaway 2 Throwaway 2 Throwaway 2 Throwaway 2 Throwaway 2 Throwaway
    (No.) Size Recommended
    WKH / DKH * #
    2x(500x500x50) 2x(500x500x50) 8x(500x625x50) 8x(500x625x50) 8x(500x625x50) 8x(500x625x50)
    + +4x(500x625x50) +4x(500x625x50)
    WKD / DKD * #2x(500x500x50) 2x(500x500x50) 4x(500x500x50) 4x(500x500x50) 4x(500x500x50) 4x(500x500x50)
    + +4x(500x625x50) +4x(500x625x50) +4x(500x625x50) +4x(500x625x50) +4x(500x625x50) +4x(500x625x50)
    Operating limits
    Minimum operating outdoor air temp. 
    (Cooling)°C -18 -18 -18 -18 -18 -18
    Minimum operating outdoor air temp. 
    (Heating)°C -15 -15 -15 -15 -15 -15
    Maximum operating outdoor air temp. 
    (Cooling)°C 50 50 50 50 48 48
    Maximum operating outdoor air temp. 
    (Heating)°C 18 18 18 18 18 18
    Minimum intake air temp. on the 
    indoor coil (Cooling)°C 18 18 18 18 18 18
    Minimum intake air temp. on the 
    indoor coil (Heating)°C 10 10 10 10 10 10
    (1)  At Eurovent rating conditions : Indoor return Air (27°C DB / 19°C WB) - Ambiant 35°C 
    according to EN14511:2013
    (2) Per motor under 400V
    (3) For standard unit, with oversized drive, without electric heater options 
    (4) At the nominal air ow with standard drive(5) At the nominal air ow with oversized drive when available
    (6) At 10m from the unit in a free  eld
    Electrical & refrigerant charge Data are subject to change without notice. 
    Please refer to unit nameplate data.
    Table 4 – General data WKD/WKH, DKD/DKH (Continued)
    General Data 
    						
    							RT-PRC014H-E4
    17
    WKD / WKH
    DKD / DKHWKD / WKH
    DKD / DKHWKD / WKH
    DKD / DKHWKD / WKH
    DKD / DKHWKD / WKH
    DKD / DKHWKD / WKH
    DKD / DKH
    125 155 200 265 290 340
    R410A R410A R410A R410A R410A R410A
    Physical data - Operating (3)
    Length (mm) 2726 2726 3107 3107 3987 3987
    Width (mm) 1811 1811 2167 2154 2154 2154
    Height (mm) 1313 1313 1704 1704 1440 1440
    Operating weight  WKD/WKH  (kg) 637 654 819 889 1183 1191
     DKD/DKH (kg) 707 729 898 968 1268 1276
    Shipping weight  WKD/WKH  (kg) 685 707 890 954 1248 1256
     DKD/DKH (kg) 755 782 969 1033 1333 1341
    Unit construction
    Sheet metal / ThicknessType / 
    mmGalvaSteel / 1.2 GalvaSteel / 1.2 GalvaSteel / 1.2 GalvaSteel / 1.2 GalvaSteel / 1.2 GalvaSteel / 1.2
    PaintType / 
    RALPolyester / 9002  Polyester / 9002  Polyester / 9002  Polyester / 9002  Polyester / 9002  Polyester / 9002 
    Insulation / ThicknessType / 
    mmM0 / 25 M0 / 25 M0 / 25 M0 / 25 M0 / 25 M0 / 25
    System Data
    Refrigerant circuit #222222
    Capacity steps (Cooling) % 50 / 50 50 / 50 50 / 50 50 / 50 50 / 50 50 / 50
    Capacity steps (Heating) % 100 100 100 50 / 50 50 / 50 50 / 50
    Refrigerant Charge (3)
    Circuit A (WKD / WKH) (kg) 5.6 6.1 9.1 9.2 11.5 11.6
    Circuit B (WKD / WKH) (kg) 5.6 6.1 9.1 9.2 11.5 11.6
    (1)  At Eurovent rating conditions : Indoor return Air (27°C DB / 19°C WB) - Ambiant 35°C 
    according to EN14511:2013
    (2) Per motor under 400V
    (3) For standard unit, with oversized drive, without electric heater options 
    (4) At the nominal air ow with standard drive(5) At the nominal air ow with oversized drive when available
    (6) At 10m from the unit in a free  eld
    Electrical & refrigerant charge Data are subject to change without notice. 
    Please refer to unit nameplate data.
    Table 4 – General data WKD/WKH, DKD/DKH (Continued)
    General Data 
    						
    							RT-PRC014H-E4 18
    Data given at 250Pa & 35°C ambient for nominal airflow rate
    Sound Power Référence = 10E--12 Watt
    Table 5 – Overall Outdoor Sound Power level (Env.)
    63 Hz 125 Hz 250 Hz 500 Hz 1000 Hz 2000 Hz 4000 Hz 8000 Hz
    TKD/H - YKD/H 155 64.2 dBA 67.8 dBA 71.0 dBA 77.2 dBA 79.6 dBA 78.8 dBA 72.7 dBA 68.7 dBA 84 dBA
    TKD/H - YKD/H 175 64.2 dBA 67.8 dBA 71.0 dBA 77.1 dBA 79.5 dBA 78.9 dBA 72.3 dBA 68.7 dBA 84 dBA
    TKD/H - YKD/H 200 73.2 dBA 72.3 dBA 77.0 dBA 80.7 dBA 81.6 dBA 78.2 dBA 71.3 dBA 55.4 dBA 86 dBA
    TKD/H - YKD/H 250 73.2 dBA 72.3 dBA 77.0 dBA 80.7 dBA 81.5 dBA 78.4 dBA 71.3 dBA 55.4 dBA 86 dBA
    TKD/H - YKD/H 265 73.2 dBA 72.3 dBA 77.0 dBA 80.7 dBA 81.6 dBA 78.5 dBA 71.2 dBA 55.4 dBA 86 dBA
    TKD/H - YKD/H 290 74.5 dBA 73.6 dBA 78.7 dBA 82.4 dBA 83.6 dBA 79.7 dBA 72.7 dBA 60.3 dBA 88 dBA
    TKD/H - YKD/H 340 74.5 dBA 73.6 dBA 78.8 dBA 83.4 dBA 84.0 dBA 81.4 dBA 75.3 dBA 60.3 dBA 89 dBA
    WKD/H - DKD/H 125 64.2 dBA 67.8 dBA 71.0 dBA 77.3 dBA 79.4 dBA 78.8 dBA 72.5 dBA 68.7 dBA 84 dBA
    WKD/H - DKD/H 155 64.2 dBA 67.8 dBA 71.0 dBA 76.9 dBA 79.6 dBA 78.7 dBA 71.5 dBA 68.7 dBA 84 dBA
    WKD/H - DKD/H 200 73.2 dBA 72.3 dBA 77.0 dBA 80.7 dBA 81.5 dBA 78.4 dBA 71.3 dBA 55.4 dBA 86 dBA
    WKD/H - DKD/H 265 73.2 dBA 72.3 dBA 77.0 dBA 80.7 dBA 81.6 dBA 78.5 dBA 71.2 dBA 55.4 dBA 86 dBA
    WKD/H - DKD/H 290 63.5 dBA 69.8 dBA 74.0 dBA 79.9 dBA 83.0 dBA 81.5 dBA 74.7 dBA 71.9 dBA 87 dBA
    WKD/H - DKD/H 340 63.5 dBA 69.8 dBA 74.0 dBA 81.6 dBA 83.5 dBA 82.7 dBA 76.5 dBA 71.9 dBA 88 dBA
    Table 6 – SUPPLY Indoor Sound Power level (In duct)
    63 Hz 125 Hz 250 Hz 500 Hz 1000 Hz 2000 Hz 4000 Hz 8000 Hz
    TKD/H - YKD/H 155 61.4 dBA 61.3 dBA 60.9 dBA 62.1 dBA 62.9 dBA 63.6 dBA 63.8 dBA 57.2 dBA 71 dBA
    TKD/H - YKD/H 175 63.1 dBA 66.5 dBA 65.5 dBA 69.2 dBA 68.6 dBA 67.7 dBA 66.5 dBA 57.9 dBA 76 dBA
    TKD/H - YKD/H 200 63.1 dBA 66.5 dBA 65.5 dBA 69.2 dBA 68.6 dBA 67.7 dBA 66.5 dBA 57.9 dBA 76 dBA
    TKD/H - YKD/H 250 67.5 dBA 70.9 dBA 69.9 dBA 74.6 dBA 73.9 dBA 74.1 dBA 72.9 dBA 64.3 dBA 81 dBA
    TKD/H - YKD/H 265 69.4 dBA 72.8 dBA 71.8 dBA 75.5 dBA 74.9 dBA 74.0 dBA 72.8 dBA 64.2 dBA 82 dBA
    TKD/H - YKD/H 290 50.0 dBA 67.2 dBA 71.4 dBA 76.1 dBA 77.8 dBA 72.7 dBA 69.9 dBA 63.9 dBA 82 dBA
    TKD/H - YKD/H 340 52.4 dBA 68.0 dBA 74.4 dBA 76.9 dBA 80.1 dBA 74.6 dBA 71.7 dBA 65.7 dBA 84 dBA
    WKD/H - DKD/H 125 66.4 dBA 66.3 dBA 65.9 dBA 67.1 dBA 67.9 dBA 68.6 dBA 68.8 dBA 62.2 dBA 76 dBA
    WKD/H - DKD/H 155 61.4 dBA 61.3 dBA 60.9 dBA 62.1 dBA 62.9 dBA 63.6 dBA 63.8 dBA 57.2 dBA 71 dBA
    WKD/H - DKD/H 200 67.1 dBA 70.5 dBA 69.5 dBA 73.2 dBA 72.6 dBA 71.7 dBA 70.5 dBA 61.9 dBA 80 dBA
    WKD/H - DKD/H 265 69.4 dBA 72.8 dBA 71.8 dBA 75.5 dBA 74.9 dBA 74.0 dBA 72.8 dBA 64.2 dBA 82 dBA
    WKD/H - DKD/H 290 50.0 dBA 67.2 dBA 71.4 dBA 76.1 dBA 77.8 dBA 72.7 dBA 69.9 dBA 63.9 dBA 82 dBA
    WKD/H - DKD/H 340 52.4 dBA 68.0 dBA 74.4 dBA 76.9 dBA 80.1 dBA 74.6 dBA 71.7 dBA 65.7 dBA 84 dBA
    Table 7 – RETURN Indoor Sound Power level (In duct)
    63 Hz 125 Hz 250 Hz 500 Hz 1000 Hz 2000 Hz 4000 Hz 8000 Hz
    TKD/H - YKD/H 155 63.4 dBA 60.8 dBA 56.9 dBA 63.6 dBA 66.4 dBA 61.1 dBA 56.3 dBA 48.2 dBA 71 dBA
    TKD/H - YKD/H 175 56.1 dBA 61.0 dBA 57.0 dBA 62.2 dBA 68.1 dBA 63.7 dBA 58.5 dBA 51.4 dBA 71 dBA
    TKD/H - YKD/H 200 56.1 dBA 61.0 dBA 57.0 dBA 62.2 dBA 68.1 dBA 63.7 dBA 58.5 dBA 51.4 dBA 71 dBA
    TKD/H - YKD/H 250 60.5 dBA 65.4 dBA 61.4 dBA 67.6 dBA 73.4 dBA 75.1 dBA 64.9 dBA 57.8 dBA 78 dBA
    TKD/H - YKD/H 265 62.4 dBA 67.3 dBA 63.3 dBA 68.5 dBA 74.4 dBA 70.0 dBA 64.8 dBA 57.7 dBA 78 dBA
    TKD/H - YKD/H 290 47.8 dBA 63.5 dBA 67.6 dBA 72.3 dBA 74.3 dBA 69.7 dBA 66.9 dBA 60.9 dBA 78 dBA
    TKD/H - YKD/H 340 50.1 dBA 64.6 dBA 70.6 dBA 73.2 dBA 76.3 dBA 71.6 dBA 68.7 dBA 62.7 dBA 80 dBA
    WKD/H - DKD/H 125 68.4 dBA 65.8 dBA 61.9 dBA 68.6 dBA 71.4 dBA 66.1 dBA 61.3 dBA 53.2 dBA 76 dBA
    WKD/H - DKD/H 155 63.4 dBA 60.8 dBA 56.9 dBA 63.6 dBA 66.4 dBA 61.1 dBA 56.3 dBA 48.2 dBA 71 dBA
    WKD/H - DKD/H 200 60.1 dBA 65.0 dBA 61.0 dBA 66.2 dBA 72.1 dBA 67.7 dBA 62.5 dBA 55.4 dBA 75 dBA
    WKD/H - DKD/H 265 62.4 dBA 67.3 dBA 63.3 dBA 68.5 dBA 74.4 dBA 70.0 dBA 64.8 dBA 57.7 dBA 78 dBA
    WKD/H - DKD/H 290 47.8 dBA 63.5 dBA 67.6 dBA 72.3 dBA 74.3 dBA 69.7 dBA 66.9 dBA 60.9 dBA 78 dBA
    WKD/H - DKD/H 340 50.1 dBA 64.6 dBA 70.6 dBA 73.2 dBA 76.3 dBA 71.6 dBA 68.7 dBA 62.7 dBA 80 dBA
    Sound Levels 
    						
    							RT-PRC014H-E4
    19
    Table 8 – Electrical characteristics
    Indoor Fan
    Belt DriveIndoor Fan
    Direct Drive
    Control Compressor 1 / 2Standard 
    driveOversized 
    driveStandard 
    driveOversized 
    driveExhaust 
    fan Outdoor FanElectric 
    Heat
    UnitMax 
    AmpsMax AmpsStart 
    AmpsMax Amps Max Amps Max Amps Qty Max Amps Max Amps
    TK* / YK* 155 0.5 18.5 / 11.2 142 / 82 4 6.4 5.4 8.5 3.0 2 1.2 36
    TK* / YK* 175 0.5 20.0 / 13.9 142 / 87 6.4 9 5.4 9.8 3.0 2 1.2 36
    TK* / YK* 200 0.5 18.5 / 18.5 142 / 142 6.4 9 9.4 12.4 3.0 2 2.5 54
    TK* / YK* 250 0.5 20.0 / 20.0 142 / 142 9 9 11.3 13.3 3.0 2 2.5 54
    TK*  265 0.5 23.0 / 23.0 147 / 147 9 11 11.3 13.5 3.0 2 2.5 54
    TK*  290 0.5 25.2 / 25.2 158 / 158 15 17.3 16.4 23.3 3.0 3 2.5 54
    TK*  340 0.5 29.0 / 29.0 197 / 197 15 17.3 16.6 22.9 3.0 3 2.5 54
    WK* / DK* 125 0.5 13.9 / 13.9 87 / 87 4 6.4 5.5 7.9 3.0 2 1.2 36
    WK* / DK* 155 0.5 15.2 / 15.2 98 / 98 4 6.4 5.4 8.5 3.0 2 1.2 36
    WK* / DK* 200 0.5 20.0 / 20.0 142 / 142 6.4 9 9.4 12.4 3.0 2 2.5 54
    WK* / DK* 265 0.5 23.0 / 23.0 147 / 147 9 11 11.3 13.5 3.0 2 2.5 54
    WK* / DK* 290 0.5 25.2 / 25.2 158 / 158 15 17.3 16.4 23.3 3.0 4 1.2 54
    WK* / DK* 340 0.5 29.0 / 29.0 197 / 197 15 17.3 16.6 22.9 3.0 4 1.2 54
    Data for nominal voltage 400V/3/50
    Data are subject to change without notice. Please refer to unit nameplate data.
    Maximum length
    Table 9 – Zone sensor wire size
    Wire size
    (mm2)Maximum wire length
    (m)
    THS/THP 03
    0.33 45
    0.5 76
    0.75 115
    1.3 185
    2 300
    Conventional thermostat
    0.33 10
    0.5 15
    0.75 23
    1.3 37
    260
    CO
    2 sensor wire size
    0.25 50
    0.5 100
    1 200
    Electrical Data 
    						
    							RT-PRC014H-E4 20
    Figure 8Dimensions, Weights and Clearances
    Overall unit dimensions, shipping weights and operating weights are given in 
    the General Data tables.
    Table 10 – Minimum recommended clearances
    Minimum clearance
    UNIT12345
    TK* / YK* 155 1900 1800 1220 1000 1300
    TK* / YK* 175 1900 1800 1220 1000 1300
    TK* / YK* 200 1900 1800 1220 1000 1300
    TK* / YK* 250 1900 1800 1220 1000 1300
    TK* 265 1900 1800 1220 1000 1300
    TK* 290 1900 1800 1220 1000 1300
    TK* 340 1900 1800 1220 1000 1300
    WK* / DK* 125 1900 1800 1220 1000 1300
    WK* / DK* 155 1900 1800 1220 1000 1300
    WK* / DK* 200 1900 1800 1220 1000 1300
    WK* / DK* 265 1900 1800 1220 1000 1300
    WK* / DK* 290 1900 1800 1220 1000 1300
    WK* / DK* 340 1900 1800 1220 1000 1300
    Weights of Factory-installed Accessories
    Table 11 – Factory-installed Accessories Net Weights (kg)
    UNITPitched 
    Roof Curb
    Pitched 
    Roof Curb
    Economizer
    Manual 
    Outside Air 
    Damper
    Motorized 
    Outside Air 
    Damper
    Electric 
    heater
    Hot water 
    coil
    Power 
    exhaust fan
    Direct drive 
    fan
    WKD/DKD 125 93 220 30 15 27 14 85 49 31
    WKD/DKD/TKD/YKD 155 93 220 30 15 27 14 85 49 31
    TKD/YKD 175 93 220 30 15 27 14 85 49 24
    WKD/DKD/TKD/YKD 200 107 260 37 15 34 18 110 49 48
    TKD/YKD 250 107 260 37 15 34 18 110 49 53
    WKD/DKD/TKD 265 107 260 37 15 34 18 110 49 53
    WKD/DKD/TKD 290 107 260 37 15 34 18 110 49 80
    WKD/DKD/TKD 340 107 260 37 15 34 18 110 49 80
    WKH/DKH 125 — — 30 15 27 14 — — —
    WKH/DKH/TKH/YKH 155 — — 30 15 27 14 — — —
    TKH/YKH 175 — — 30 15 27 14 — — —
    WKH/DKH/TKH/YKH 200 — — 37 15 34 18 — — —
    TKH/YKH 250 — — 37 15 34 18 — — —
    WKH/DKH/TKH 265 — — 37 15 34 18 — — —
    WKH/DKH/TKH 290 — — 37 15 34 18 — — —
    WKH/DKH/TKH 340 — — 37 15 34 18 — — —
    Notes :
    Net weight should be added to unit weight when ordering factory installed accessories.
    To estimate shipping weight add 2.3 kg to net weight.
    Filters
    Table 12 – Filter arrangement
    G4+F7 Filter
    G2 Filter G4 Filter G4 Filter F7 Filter
    UNIT Qty - Size Qty -  Size Qty -  Size Qty -  Size
    TKD / YKD 155 - 175 & WKD / DKD 125 - 155 2x (500x500x50) 2x (498x498x40) 1x (398x498x44) 2x (500x500x50)
    +4x (500x625x50) +4x (500x625x50) +1x (498x498x40) +4x (500x625x50)
    +2x (500x625x50)
    +2x (400x625x50)
    TKH / YKH 155 - 175 & WKH / DKH 125 - 155 2x (500x500x50) 2x (498x498x40) 4x (398x498x44) 2x (500x500x50)
    +4x (500x625x50) +4x (500x625x50) +2x (500x625x50) +4x (500x625x50)
    YKD 200 - 250 & TKD / WKD / DKD 200 - 340 4x (500x500x50) 4x (498x498x40) 4x (498x498x40) 4x (500x500x50)
    +4x (500x625x50) +4x (500x625x50) +4x (500x625x50) +4x (500x625x50)
    YKH 200 - 250 & TKH / WKH / DKH 200 - 340 8x (500x625x50) 8x (500x625x50) 6x (400x625x50) 8x (500x625x50)
    +2x (500x625x50)
    Dimensions and Weights 
    						
    All Trane manuals Comments (0)

    Related Manuals for Trane Voyager 2 Manual