TD - Series- 15 - TD SeriesDigital Solid State Soft Starter 48 - 1250A Viewing a Function’s Set Value (See Example) NOTE: If password protection has been enabled, operator will need to obtain password access before function settings can be changed. [0000.]Indicates that Phase A is drawing no current. Press the Fn key. [F001]Indicates that this is (function 001) Motor FLA. To view the F001’s value, press Read Enter. [0306]Indicates that the programmed motor FLA is 306 Amps. Press the Fn key to return...
Page 22
TD - Series- 16 - TD Series Digital Solid State Soft Starter 48 - 1250A Setting Motor FLA and Overload Class During Start (See Example) 5.3.3 Fault Mode The Fault Display Mode provides information to the operator when a fault occurs or when the operator wishes to review fault history. Refer to Section 7 for details. Fault codes are three-digits in length and are displayed in alpha characters. The first and second characters (reading left to right) are the initials for the applicable English-language...
Page 23
TD - Series- 17 - TD SeriesDigital Solid State Soft Starter 48 - 1250A 5.4 The TD Function List 5.4.1 Motor FLA, Service Factor and Overload Protection Functions 5.4.2 Starting Mode Functions 5.4.3 Jog Mode Functions Note 1: Current percentages are based on Motor Full Load Amps (FLA) as entered in F001. Fn Group FunctionAdjustment RangeSetting IncrementsFactory SettingSection F001Motor Nameplate FLA Motor FLA must be programmed for proper unit operation.50-100% of starter Max. Amp rating Upper limit...
Page 24
TD - Series- 18 - TD Series Digital Solid State Soft Starter 48 - 1250A 5.4.4 Kick Start Mode Functions 5.4.5 Decel Mode Functions 5.4.6 Protection Features Fn Group FunctionAdjustment RangeSetting IncrementsFactory SettingSection F025 Deceleration Ramp0=Disabled / Coast to Stop 1=Enabled (except in event of OL Trip) 2=Enabled (continued Decel on OL Trip)1 0 (Disabled) 5.5.5 F026 Begin Decel Level (BDL) 0 - 100 % 1% 60% 5.5.5 F027 Decel Shut Off Voltage 0 to (BDL minus 1)% 1% 30% 5.5.5 F028 Decel...
Page 25
TD - Series- 19 - TD SeriesDigital Solid State Soft Starter 48 - 1250A 5.4.7 Relays Note 2: Auxiliary relays can be programmed for any of the following operations. # 1 - Run / Stop (Signal) # 7 - Shunt Trip # 13 - Under Current Trip # 2 - At Speed / Stop (Signal) # 8 - OL Trip # 14 - Any Trip (# 5 - #13) # 3 - At Speed / End of Decel (SCRs Off) # 9 - OT Trip # 15 - Coastdown Time # 4 - Start / End of Decel # 10 - Short Circuit Trip # 16 - Starts Per Hour # 5 - Short SCR...
Page 26
TD - Series- 20 - TD Series Digital Solid State Soft Starter 48 - 1250A 5.4.10 Fault History and Run Time 5.5 Function Descriptions The unit is set at the factory with typical starting characteristics that perform well in most applications. Note: Customer must program motor FLA (F001) for unit to operate. 5.5.1 Motor and Overload Function Descriptions F001 = Motor FLA Factory Setting = 0 Range = 50 - 100% of Unit Max. Current. Set the value of this function to the motor nameplate Full Load...
Page 27
TD - Series- 21 - TD SeriesDigital Solid State Soft Starter 48 - 1250A F002 = Service Factor Factory Setting = 1.0 S.F. Range = 1.00 - 1.30 Set value according to the Service Factor (SF) data provided on the motor’s nameplate. This value affects several protection features so \ it must be accurate. Setting the SF too high may result in motor damage in overload conditions. Setting SF too low may cause nuisance trips. F003 = Overload Class During Start Factory Setting = 10 (Class 10) Range = 5 - 30 NEMA...
Page 28
TD - Series- 22 - TD Series Digital Solid State Soft Starter 48 - 1250A 5.5.2 Starting Mode The TD is capable of several different starting modes, but is set from the factory for the most common applications. A second ramp profile is available for use should you need it but unless wired to do so, the TD defaults to Ramp 1. This section describes functions for Ramp 1, with references to function numbers that do the same thing for Ramp 2 if required. Refer to Appendix 2 for a detailed description of...