TD - Series- 15 -
TD SeriesDigital Solid State Soft Starter 48 - 1250A
Viewing a Function’s Set Value (See Example)
    NOTE: If password protection has been enabled, operator will need to obtain
password access before function settings can be changed.
[0000.]Indicates that Phase A is
drawing no current.
Press the Fn key.
[F001]Indicates that this is (function
001) Motor FLA.
To view the F001’s value, press
Read Enter.
[0306]Indicates that the
programmed motor FLA
is 306 Amps.
Press the Fn key to return...

Page 22

TD - Series- 16 -
TD  Series    Digital Solid State Soft Starter 48 - 1250A
Setting Motor FLA and Overload Class During Start (See Example)
5.3.3 Fault Mode
The Fault Display Mode provides information to the operator when a fault occurs
or when the operator wishes to review fault history. Refer to Section 7 for details.
Fault codes are three-digits in length and are displayed in alpha characters.  The
first and second characters (reading left to right) are the initials for the applicable
English-language...

Page 23

TD - Series- 17 -
TD SeriesDigital Solid State Soft Starter 48 - 1250A
5.4    The TD Function List
5.4.1 Motor FLA, Service Factor and Overload Protection Functions
5.4.2 Starting Mode Functions
5.4.3 Jog Mode Functions
Note 1: Current percentages are based on Motor Full Load Amps (FLA) as entered in F001.
Fn Group FunctionAdjustment
 RangeSetting
IncrementsFactory
SettingSection
F001Motor Nameplate FLA
Motor FLA must be programmed 
for proper unit operation.50-100% of starter Max. Amp rating
Upper limit...

Page 24

TD - Series- 18 -
TD  Series    Digital Solid State Soft Starter 48 - 1250A
5.4.4 Kick Start Mode Functions
5.4.5 Decel Mode Functions
 5.4.6 Protection Features
Fn Group FunctionAdjustment
 RangeSetting
IncrementsFactory
SettingSection
F025 Deceleration Ramp0=Disabled / Coast to Stop
1=Enabled (except in event of OL Trip)
2=Enabled (continued Decel on OL Trip)1 0 (Disabled) 5.5.5
F026 Begin Decel Level (BDL) 0 - 100 % 1% 60% 5.5.5
F027 Decel Shut Off Voltage 0 to (BDL minus 1)% 1% 30% 5.5.5
F028 Decel...

Page 25

TD - Series- 19 -
TD SeriesDigital Solid State Soft Starter 48 - 1250A
5.4.7 Relays
Note 2: Auxiliary relays can be programmed for any of the following operations.
#  1 - Run / Stop (Signal)       #   7 - Shunt Trip # 13 - Under Current Trip
#  2 - At Speed / Stop (Signal)       #   8 - OL Trip # 14 - Any Trip (# 5 - #13)
#  3 - At Speed / End of Decel (SCRs Off)      #   9 - OT Trip # 15 - Coastdown Time
#  4 - Start / End of Decel       # 10 - Short Circuit Trip # 16 - Starts Per Hour
#  5 - Short SCR...

Page 26

TD - Series- 20 -
TD  Series    Digital Solid State Soft Starter 48 - 1250A
5.4.10 Fault History and Run Time
5.5    Function Descriptions
The unit is set at the factory with typical starting characteristics that perform well
in most applications.
    Note: Customer must program motor FLA (F001) for unit to operate.
5.5.1 Motor and Overload Function Descriptions
F001 = Motor FLA
Factory Setting = 0
Range = 50 - 100% of Unit Max. Current.
Set the value of this function to the motor nameplate Full Load...

Page 27

TD - Series- 21 -
TD SeriesDigital Solid State Soft Starter 48 - 1250A
F002 = Service  Factor
Factory Setting = 1.0 S.F.
Range = 1.00 - 1.30
Set value according to the Service Factor (SF) data provided on the
motor’s nameplate. This value affects several protection features so \
it
must be accurate. Setting the SF too high may result in motor damage
in overload conditions. Setting SF too low may cause nuisance trips.
F003 = Overload  Class During Start
Factory Setting = 10 (Class 10)
Range = 5 - 30 NEMA...

Page 28

TD - Series- 22 -
TD  Series    Digital Solid State Soft Starter 48 - 1250A
5.5.2 Starting Mode
The TD is capable of several different starting modes, but is set from the factory
for the most common  applications. A second ramp profile is available for use
should you need it but unless wired to do so, the TD defaults to Ramp 1. This
section describes functions for Ramp 1, with references to function numbers that
do the same thing for Ramp 2 if required. Refer to Appendix 2 for a detailed
description of...