Toshiba Dvr 35 Instruction Manual
Have a look at the manual Toshiba Dvr 35 Instruction Manual online for free. It’s possible to download the document as PDF or print. UserManuals.tech offer 566 Toshiba manuals and user’s guides for free. Share the user manual or guide on Facebook, Twitter or Google+.
TD - Series- 15 - TD SeriesDigital Solid State Soft Starter 48 - 1250A Viewing a Function’s Set Value (See Example) NOTE: If password protection has been enabled, operator will need to obtain password access before function settings can be changed. [0000.]Indicates that Phase A is drawing no current. Press the Fn key. [F001]Indicates that this is (function 001) Motor FLA. To view the F001’s value, press Read Enter. [0306]Indicates that the programmed motor FLA is 306 Amps. Press the Fn key to return to the function. [F001]Press the Fn key again to return to the Status Display Mode. Enabling Password Protection / Parameter Lock The TD Series Soft Starter is shipped with the Customer password disabled (F060 = 0). If it is necessary to prevent parameters from being changed inadvertently, set the password in function F060. See Appendix 4 for details. The display of a customer password is encrypted. If you do not have a record of the password and need to gain access, contact TOSHIBA Tech Support. Be ready to provide the TD Series serial number and the four digits in the encrypted display. If the display reads “Err” when the READ/ENTER key is pressed, the parameter lock is enabled. Changing a Function’s Set Value Use the UP arrow key to increment the value of the flashing digit. Use the DOWN arrow key to decrement the value of the flashing digit. Use the LEFT or RIGHT arrow to select the next digit to be altered. Values can only be changed within the Adjustment Range of the function parameter. Storing the Altered Value of a Function Once the desired value is displayed, press the READ/ENTER key. This stores the value in memory. The readout momentarily displays [ END] and then returns to another function code. NOTE: If the Fn key is pressed BEFORE the READ/ENTER key is pressed, the TD Series Starter will not store the selected value in memory. 0000. F00 1 0306 F00 1 0000. Viewing a Function’s Set Value
TD - Series- 16 - TD Series Digital Solid State Soft Starter 48 - 1250A Setting Motor FLA and Overload Class During Start (See Example) 5.3.3 Fault Mode The Fault Display Mode provides information to the operator when a fault occurs or when the operator wishes to review fault history. Refer to Section 7 for details. Fault codes are three-digits in length and are displayed in alpha characters. The first and second characters (reading left to right) are the initials for the applicable English-language fault name. The third or right-most character can be either A, C, or D to denote when the fault occurred. A denotes Acceleration. C denotes Constant speed. D denotes Decel. Reading Fault Code (See Example) [ PLC.]Indicates a Phase Loss fault was detected while at Constant Speed. The decimal point (to the right of the C) denotes that this is the most recent fault condition. Once a fault condition has been corrected, pressing the Reset key will return the readout to the Status Display mode. Fault History can be accessed during a fault condition. While the current fault number is being displayed, use the Up and Down Arrow keys to scroll through the Fault History. Access Fault History via Functions F075 through F083. PLC. Reading Fault Code Setting OL Class During StartSetting mFLA During Start
TD - Series- 17 - TD SeriesDigital Solid State Soft Starter 48 - 1250A 5.4 The TD Function List 5.4.1 Motor FLA, Service Factor and Overload Protection Functions 5.4.2 Starting Mode Functions 5.4.3 Jog Mode Functions Note 1: Current percentages are based on Motor Full Load Amps (FLA) as entered in F001. Fn Group FunctionAdjustment RangeSetting IncrementsFactory SettingSection F001Motor Nameplate FLA Motor FLA must be programmed for proper unit operation.50-100% of starter Max. Amp rating Upper limit of range automatically adjusts downward as Service Factor is increased1 amp0 (Starter disabled until set to FLA)5.5.1 F002 Motor Nameplate Service Factor 1.00 - 1.30 0.05 1.0 SF 5.5.1 F003 Overload Class During Start5 - 30 NEMA / UL Class Overload Time / Trip Curve5 Class 10 5.5.1 F004 Overload Class During Run5 - 30 NEMA / UL Class Overload Time / Trip Curve5 Class 10 5.5.1 F005 Overload Reset0=Manual 1=Auto 2=Disabled Overload1 0 (Manual) 5.5.1 5.5.1 F006- F009Reserved Reserved Reserved Reserved Motor and Overload Fn Group FunctionAdjustment RangeSetting IncrementsFactory SettingSection F010Ramp Select VR = Voltage Ramp, CR = Current Ramp Range is 1 - 4 Setting to #1: Ramp 1 = VR, Ramp 2 = VR Setting to #2: Ramp 1 = CR, Ramp 2 = CR Setting to #3: Ramp 1 = VR, Ramp 2 = CR Setting to #4: Ramp 1 = CR, Ramp 2 = VR 1 1 (VR1-VR2) 5.5.2 F011 Initial Voltage of Ramp 1 0-100% 1% 60% 5.5.2 F012 Initial Current of Ramp 1 0-600% (note1) 1% 200% 5.5.2 F013 Accel Ramp Time of Ramp 1 1-120 seconds 1 second 10 seconds 5.5.2 F014 Max Current Limit of Ramp 1 200 - 600% (note1) 1% 350% 5.5.2 F015 Initial Voltage of Ramp 2 0-100% 1% 60% 5.5.2 F016 Initial Current of Ramp 2 0-600% (note1) 1% 200% 5.5.2 F017 Accel Ramp Time of Ramp 2 1-120 seconds 1 second 10 seconds 5.5.2 F018 Max Current Limit of Ramp 2 200 - 600% (note1) 1% 350% 5.5.2 Starting Mode Fn Group FunctionAdjustment RangeSetting IncrementsFactory SettingSection F019 Voltage Jog 5 - 100% 1% 50% 5.5.3 F020 Time of Voltage Jog 1 - 20 Seconds 1 second 10 seconds 5.5.3 F021 Current Jog 100 - 500% 1% 150% 5.5.3 Jog Mode
TD - Series- 18 - TD Series Digital Solid State Soft Starter 48 - 1250A 5.4.4 Kick Start Mode Functions 5.4.5 Decel Mode Functions 5.4.6 Protection Features Fn Group FunctionAdjustment RangeSetting IncrementsFactory SettingSection F025 Deceleration Ramp0=Disabled / Coast to Stop 1=Enabled (except in event of OL Trip) 2=Enabled (continued Decel on OL Trip)1 0 (Disabled) 5.5.5 F026 Begin Decel Level (BDL) 0 - 100 % 1% 60% 5.5.5 F027 Decel Shut Off Voltage 0 to (BDL minus 1)% 1% 30% 5.5.5 F028 Decel Ramp Time 1 - 60 Seconds 1 second 10 seconds 5.5.5 F029 Reserved Reserved Reserved Reserved 5.5.5 Decel Mode Fn Group FunctionAdjustment RangeSetting IncrementsFactory SettingSection F030 Current Imbalance Trip0=Disabled 1=Enabled1 0 (Disabled) 5.5.6 F031 Current Imbalance Trip % 5 - 30% 1% 10% 5.5.6 F032 Current Imbalance Trip Delay 1 - 20 seconds 1 second 2 seconds 5.5.6 F033 Over Current / Shear Pin Trip0=Disabled 1=Enabled1 0 (Disabled) 5.5.6 F034 Over Current / Shear Pin Trip % 50 - 300% (note1) 1% 125% 5.5.6 F035 Over Current Trip Delay 1 - 20 seconds 1 second 1 second 5.5.6 F036 Under Current Trip0=Disabled 1=Enabled1 0 (Disabled) 5.5.6 F037 Under Current Trip % 10 - 90% (note1) 1% 40% 5.5.6 F038 Under Current Trip Delay 1 - 60 seconds 1 second 2 seconds 5.5.6 F039 Coast Down Lockout Timer0=Disabled 1=Enabled1 0 (Disabled) 5.5.6 F040 Coast Down Lockout Time 1 - 60 minutes 1 minute 5 minutes 5.5.6 F041 Starts per Hour Lockout0=Disabled 1=Enabled1 0 (Disabled) 5.5.6 F042 Maximum Starts per Hour 1 - 10 1 2 5.5.6 F043 Time Between Starts Lockout0=Disabled 1=Enabled1 0 (Disabled) 5.5.6 F044 Minimum Time Between Starts 1 - 60 minutes 1 minute 15 minutes 5.5.6 F045 Coast Down Timer Value 1 - 3600 Seconds View Only 0 5.5.6 F046 Starts per Hour Timer Value 1 - 3600 Seconds View Only 0 5.5.6 F047 Starts per Hour Count Value 1 - 10 Starts View Only 0 5.5.6 F048 Time Value Between Starts 1 - 3600 Seconds View Only 0 5.5.6 F049 Thermal Capacity to Start 0 - 100 % Thermal Capacity View Only 0 5.5.6 Protection Features Fn Group FunctionAdjustment RangeSetting IncrementsFactory SettingSection F022 Kick Start0=Disabled 1=Enabled1 0 (Disabled) 5.5.4 F023 Kick Voltage 10 - 100% 1% 65% 5.5.4 F024 Kick Time 0.1 - 2 Seconds 0.1 second 0.8 seconds 5.5.4 Kick Start Mode
TD - Series- 19 - TD SeriesDigital Solid State Soft Starter 48 - 1250A 5.4.7 Relays Note 2: Auxiliary relays can be programmed for any of the following operations. # 1 - Run / Stop (Signal) # 7 - Shunt Trip # 13 - Under Current Trip # 2 - At Speed / Stop (Signal) # 8 - OL Trip # 14 - Any Trip (# 5 - #13) # 3 - At Speed / End of Decel (SCRs Off) # 9 - OT Trip # 15 - Coastdown Time # 4 - Start / End of Decel # 10 - Short Circuit Trip # 16 - Starts Per Hour # 5 - Short SCR Trip # 11 - Current Imbalance Trip # 17 - Time Between Starts # 6 - Phase Loss Trip # 12 - Over Current Trip # 18 - Any Lockout (#15 -17) 5.4.8 Communications 5.4.9 System Settings Fn Group FunctionAdjustment RangeSetting IncrementsFactory SettingSection F050 Aux Relay 1 setting Operation # 1 - 18 (note2) 1 1 5.5.7 F051 Aux Relay 2 setting Operation # 1 - 18 1 2 5.5.7 F052 Aux Relay 3 setting Operation # 1 - 18 1 14 5.5.7 5.5.7 F053- F054Reserved Reserved Reserved Reserved Relays Fn Group FunctionAdjustment RangeSetting IncrementsFactory SettingSection F055 Communications0=Disabled 1=Enabled105.5.8 F056 Baud Rate 9.6 - 38.4 KB 9.6 KB 9.6 KB 5.5.8 F057 Modbus Address 1 - 247 1 1 5.5.8 Reserved Reserved Reserved Reserved 5.5.8 F058- F059 Communications Fn Group FunctionAdjustment RangeSetting IncrementsFactory SettingSection F060Parameter Lock/ User PasswordRange is 0 - 999 0 = Disabled Any Other Number = Password Protected1 0 (Disabled) 5.5.9 F061 Reset Factory Default SettingsRange is 0 - 2 0=Disabled 1=Clear Thermal Register and Lockout Timers 2 = Reset to Factory Default Settings105.5.9 F062- F064Reserved Reserved Reserved Reserved 5.5.9 F065 Year 2000 - 2047 1 Year Date of Mfg. 5.5.9 F066 Month 1 - 12 1 Month Date of Mfg. 5.5.9 F067 Day 1 - 31 1 Day Date of Mfg. 5.5.9 F068 Hour 0 - 23 1 Hour Date of Mfg. 5.5.9 F069 Minute 0 - 59 1 Minute Date of Mfg. 5.5.9 F070 Second 0 - 59 1 Second Date of Mfg. 5.5.9 F071 Revision # - View Only Factory Setting 5.5.9 F072- F074Reserved Reserved Reserved Reserved 5.5.9 System Settings
TD - Series- 20 - TD Series Digital Solid State Soft Starter 48 - 1250A 5.4.10 Fault History and Run Time 5.5 Function Descriptions The unit is set at the factory with typical starting characteristics that perform well in most applications. Note: Customer must program motor FLA (F001) for unit to operate. 5.5.1 Motor and Overload Function Descriptions F001 = Motor FLA Factory Setting = 0 Range = 50 - 100% of Unit Max. Current. Set the value of this function to the motor nameplate Full Load Amps (FLA). Adjustments for service factor are not necessary when programming this function. (See note below). If the motor nameplate FLA is not available, use typical values as shown in NEC, NEMA standard MG-1 or other reputable third party source (motor manufacturer, etc.). Note: To prevent adjusting the settings beyond the starter Max Amp rating, the range of adjustment for the Motor Nameplate FLA will vary to reflect the Service Factor as programmed into F002. At the default setting of 1.0SF, the full range of adjustment from 50 - 100% of the Max Amp rating is available. For example F002 = 1.15 to reflect a 1.15SF, the maximum FLA programmable into F001 will be limited to 85% of the starter Max. Amp rating (100% - 15%). Fn Group FunctionAdjustment RangeSetting IncrementsFactory SettingSection F075 Fault History #1, Latest Fault0, 1 - 27 (Fault #: see Fault code list; 0: No fault history)View Only 0 5.5.10 F076 Time Stamp, Fault #100.00-23.59 (hh.mm) [hh = 00-23; mm = 00-59]View Only 00.00 EST 5.5.10 F077 Date Stamp, Fault #101.01 - 12.31 (MM.DD) [MM = 01-12; DD = 01-31]View Only 01.01 5.5.10 F078Fault History #2, Previous Fault0, 1 - 27 (Fault #: see Fault code list; 0: No fault history)View Only 0 5.5.10 F079 Time Stamp, Fault #200.00-23.59 (hh.mm) [hh = 00-23; mm = 00-59]View Only 00.00 EST 5.5.10 F080 Date Stamp, Fault #201.01 - 12.31 (MM.DD) [MM = 01-12; DD = 01-31]View Only 01.01 5.5.10 F081 Fault History #3, Oldest Fault0, 1 - 27 (Fault #: see Fault code list; 0: No fault history)View Only 0 5.5.10 F082 Time Stamp, Fault #300.00-23.59 (hh.mm) [hh = 00-23; mm = 00-59]View Only 00.00 EST 5.5.10 F083 Date Stamp, Fault #301.01 - 12.31 (MM.DD) [MM = 01-12; DD = 01-31]View Only 01.01 5.5.10 F084 Run Time, Hours 000.0 - 999.9 (hours) View Only 0 5.5.10 F085 Run Time, K Hours 0000 - 9999 (thousand hours) View Only 0 5.5.10 F086 Run Counts 0000 - 9999 (times) View Only 0 5.5.10 F087 Run Counts, 10K times 0000 - 9999 (10 thousand times) View Only 0 5.5.10 Fault History and Run Time
TD - Series- 21 - TD SeriesDigital Solid State Soft Starter 48 - 1250A F002 = Service Factor Factory Setting = 1.0 S.F. Range = 1.00 - 1.30 Set value according to the Service Factor (SF) data provided on the motor’s nameplate. This value affects several protection features so \ it must be accurate. Setting the SF too high may result in motor damage in overload conditions. Setting SF too low may cause nuisance trips. F003 = Overload Class During Start Factory Setting = 10 (Class 10) Range = 5 - 30 NEMA / UL Class Set value to the motor protection overload class required for the application. It is recommended that you try the factory setting first. (\ If possible, keep values for F003 and F004 the same.) Increase F003 above F004 only if nuisance tripping occurs during start. See Section 3.2 for details on trip curves. F004 = Overload Class During Run Factory Setting = 10 (Class 10) Range = 5 - 30 NEMA / UL Class Set value according to the instructions provided by your motor / equipment manufacturer. This trip curve will not be enabled until the motor has reached full speed. F005 = Overload Reset Factory Setting = 0 (Manual) Range = 0 - 2 Set value to determine starter behavior after an overload condition has cleared. When set to 0 = Manual, the operator must press the Reset key before restarting the motor. Once the motor windings have cooled sufficiently AND the Reset key is pressed, the unit will accept a restart command. When set to 1 = Automatic mode, and once sufficient time has elapsed allowing motor windings to cool, the motor will be restarted upon a start command. Setting F005 = 1 (Automatic) may present significant operational risk. When set to 2 = Disabled Overload , a separate external thermal overload protection device must be in the circuit. F006 - F009 = Reserved WARNING
TD - Series- 22 - TD Series Digital Solid State Soft Starter 48 - 1250A 5.5.2 Starting Mode The TD is capable of several different starting modes, but is set from the factory for the most common applications. A second ramp profile is available for use should you need it but unless wired to do so, the TD defaults to Ramp 1. This section describes functions for Ramp 1, with references to function numbers that do the same thing for Ramp 2 if required. Refer to Appendix 2 for a detailed description of the differences in Ramp Profiles and their uses. F010 = Ramp Profile Selection Factory Setting = 1 Range = 1 - 4 This Function selects the type of Ramp Profile desired. Ramp profiles can be either Voltage Ramp or Current Ramp. See Appendix 2 for details. Each Ramp Profile consists of 3 settings: Initial Torque, Ramp Time and Maximum Current Limit Because there are two ramps available, there are 4 settings to cover the combinations of profiles possible. If you are not using the 2nd ramp, the TD will ignore all settings in reference to Ramp 2. Select Voltage Ramp by setting F010 = 1 (factory default) When Voltage Ramp is selected, Set Initial Torque with F011 (see below) Set Ramp with F013 (see below) Set Maximum Current Limit with F014 (see below) Or; Select Current Ramp by setting F010 = 2 When Current Ramp is selected, Set Initial Torque with F012 (see below) Set Ramp Time with F013 (see below) Set Maximum Current Limit with F014 (see below) Ramp 1 Ramp 2 1 Voltage Ramp Voltage Ramp 2 Current Ramp Current Ramp 3 Voltage Ramp Current Ramp 4 Current Ramp Voltage RampRamp Type Setting F010 Ramp Profile Selection F011 = Initial Voltage of Ramp 1 Factory Setting = 60% Range = 0 - 100% Sets the initial voltage of ramp 1 when F010 = 1 or 3. The initial torque level should be set to provide just enough torque to make the motor shaft begin to rotate while preventing torque shock damage to mechanical components. F012 = Initial Current of Ramp 1 Factory Setting = 200% Range = 0 - 600% Sets the initial current of ramp 1 (when F010 = 2 or 4). Current percentages are based on the Motor FLA as set in F001. The initial torque level should be set to provide just enough torque to make the motor shaft begin to rotate while preventing torque shock damage to mechanical components.