Home > Toshiba > Automobile Parts > Toshiba Dvr 35 Instruction Manual

Toshiba Dvr 35 Instruction Manual

    Download as PDF Print this page Share this page

    Have a look at the manual Toshiba Dvr 35 Instruction Manual online for free. It’s possible to download the document as PDF or print. UserManuals.tech offer 566 Toshiba manuals and user’s guides for free. Share the user manual or guide on Facebook, Twitter or Google+.

    							TD - Series- 5 -
    TD SeriesDigital Solid State Soft Starter 48 - 1250A
    2.5    Mounting and Cleaning
    When drilling or punching holes in the enclosure, cover the electrical a\
    ssembly
    to prevent metal filings from becoming lodged in areas which can cause
    clearance reduction or actually short out electronics. After work is com\
    plete,
    thoroughly clean the area and reinspect the unit for foreign material. M\
    ake
    sure there is sufficient clearance (six inches) all around the unit fo\
    r cooling,
    wiring and maintenance purposes. To maximize effective air flow and cooling,
    the unit must be installed with its heat sink ribs oriented vertically a\
    nd running
    parallel to the mounting surface.
    Remove all sources of power before cleaning the unit.
    In dirty or contaminated atmospheres the unit should be cleaned on a reg\
    ular
    basis to ensure proper cooling. Do not use any chemicals to clean the un\
    it.
    To remove surface dust use 80 to 100 psi, clean, dry compressed air only. A
    three inch, high quality, dry paint brush is helpful to loosen up the dust prior
    to using compressed air on the unit.
    2.6    Power Terminal Wire Range and Tightening Torque
    Note:  All wiring must be sized according to NEC standards.
        WARNING
    Model Number Wire range Torque lbs/in
    TD005#18 - #4 20
    TD006 #14 - #2 50
    TD007
    TD008
    TD009
    TD010
    TD011
    TD012
    TD013
    TD014
    TD015 TD016
    TD017 #6 - 250 kcmil
    325
    375
    (3) #2 - 600 kcmil 375
    (2) #2 - 600 kcmil 375
    (2) #2 - 600 kcmil
    (4) #2 - 600 kcmil 375 
    						
    							TD - Series- 6 -
    TD  Series    Digital Solid State Soft Starter 48 - 1250A
    2.7   Dimensions
      TD CHASSIS (PANEL MOUNT) DIMENSIONS
      Ove ra ll Dimensions Mounting Dime nsions
    Mode l Numbe r (inche s) (inches)
    AB CDEF
    TD005A - TD007A16. 5 10 10 15. 9 9 0. 28
    TD008A20 20. 1 12 18. 5 17. 5 0. 44
    TD009A - TD010A27 20. 1 11.2 25. 5 17. 5 0. 44
    TD011A - TD013A29. 5 20. 1 11.5 25. 5 17. 5 0. 44
    TD014A - TD015A45 33 12.8 43.3 31.3 0.44
    TD016A - TD017A33 33 15.2 31.2 31.2 0.44
      
    						
    							TD - Series- 7 -
    TD SeriesDigital Solid State Soft Starter 48 - 1250A
    Chapter 3 - Motor Overload Protection
    3.1    Solid State Overload Protection
    The TD Series  Starter provides true U.L. listed I2T Thermal Overload Protection
    as a built-in function of the main digital processor. For maximum protection it
    simulates the tripping action of a bimetallic overload relay, with the accuracy and
    repeatability of a digital control system, yet is adjustable over a wide\
     range and
    can be easily programmed for different trip curves.
    3.1.1 Thermal Memory
    The  TD Series  microprocessor uses a sophisticated “Thermal Register” to keep
    track of motor heating and cooling over time regardless of the starter’\
    s power
    status. The  TD Series does not “forget” that the motor has been running even if
    power to the starter is turned off and back on. Continuous overload prot\
    ection is
    provided based on the true thermal condition of the motor.
    3.1.2 Thermal Capacity
    The Thermal Register is displayed as a percentage. This percentage is th\
    e motor’s
    remaining thermal capacity. The percentage value begins at 100, showing that
    the motor is cool. As the motor heats up or moves toward an overload con\
    dition,
    the percentage begins to drop. The Thermal Capacity is derived from the
    programmed motor nameplate Full Load Amps (FLA) in Function F001, the \
    Service
    Factor rating in Function F002, and the Overload Trip Class in Functions\
     F003
    and F004. Setting these functions to the proper values will provide maxi\
    mum
    protection yet eliminates nuisance tripping.
    3.1.2.a Motor Full Load (FLA) Setting
    Use Function F001 to enter motor FLA as indicated on the motor nameplate\
    . (Do
    not calculate for service factor, this is programmed separately in F002).
    Note: If  F001 is left at the factory default, the unit will not operate.  If the
    user attempts to start the TD without entering the motor nameplate
    FLA into this Function, the TD will Fault, and the display will read
    “nFLA” (for no Full Load Amps).
    3.1.3 Disabling the Overload Protection
    The Overload Protection feature can be disabled if absolutely necessary. When
    using external devices such as Motor Protection Relays or when the  TD Series
    is wired downstream from an existing starter, this feature can be disabled to
    prevent conflicts with external overload protection devices. When  the  TD Series
    is controlling multiple motors, Overload Protection must be disabled. In\
    dividual
    thermal overload relays must be installed on the motor leads going to ea\
    ch
    motor. To disable the Overload Protection function, use F005. (See Section 5.)\
    Do NOT disable Overload Protection unless another Thermal Overload
    Protection device exists in the circuit for all three phases. Running a
    motor without Overload Protection presents serious risk of motor damage
    or fire.
    3.1.3.a Manual Reset
    The factory default setting is Manual Reset. This means that when the Ov\
    erload
    Trip is activated, the starter cannot be restarted without pressing the  Reset key.
    The Overload Trip will not reset until the motor cools down. The Manual \
    Reset
    function is also “trip free”. Holding in the  Reset key will not prevent the Overload
    Trip from activating and protecting the motor.
    Note: When the Overload Trip activates, the Overload LED will glow
    solid. When the motor cools down, the LED will begin to flash,
    indicating that the Overload Trip can be reset.
        WARNING 
    						
    							TD - Series- 8 -
    TD  Series    Digital Solid State Soft Starter 48 - 1250A
    3.1.3.b Automatic Reset
    If Automatic Reset is necessary,  change from Manual Reset to Automatic Reset
    by using Function F005. (See Section 5 for details). In this mode, a 3\
    -wire control
    circuit will be capable of restart when the TD Series has reset itself a\
    fter the cool
    down period.
    Two-wire control systems may restart without warning  when Auto Reset
    is selected. Extreme caution should be exercised. To prevent automatic
    restarting with two-wire control systems, use external interlocking to
    provide sufficient warning and safety to operators. A Warning Label (su\
    ch
    as the one provided in the packet with this manual) must be placed to b\
    e
    visible on the starter enclosure and/or the equipment as required by loc\
    al
    code.
    3.2    NEMA Class Trip Curves The TD Series  Soft Starter provides six NEMA Class trip curve options: 5, 10,
    15, 20, 25, and 30. Program the appropriate curve according to the chara\
    cteristics
    of your motor and load.
    NEMA Class trip curves are based on a common tripping point of 600% of r\
    ated
    current. Curves vary by the amount of time before the unit trips. As an \
    example,
    a Class 20 curve will trip in 20 seconds at 600%. The factory default se\
    tting of
    Class 10 will trip in 10 seconds at 600%.
    3.2.1 Dual Overload Trip Curves
    The  TD Series  Soft Starter provides two separate Overload Trip Protection Curves,
    one for starting and one for running conditions. Programming a higher NE\
    MA
    Class overload during start (ramp-up) will eliminate nuisance tripping\
     in higher
    inertia or high friction loads.
    The starter’s At-Speed detection circuit determines when the motor ha\
    s reached
    full speed based on closed loop feedback signals. When the At-Speed cond\
    ition
    is reached, the overload trip curve will shift from the Start to the Run\
     level, as
    programmed in Functions F003 and F004. See Section 5 for programming det\
    ails. MOTOR CONNECTED TO THIS EQUIPMENT MAY
    START AUTOMATICALLY WITHOUT WARNING
        WARNING 
    						
    							TD - Series- 9 -
    TD SeriesDigital Solid State Soft Starter 48 - 1250A
    Note:  Factory default setting is Class 10  for both Start and Run Overl\
    oad Protection
    Class 30Class 25
    Class 20
    Class 15
    Class 10
    Class 5
    MFLA
    Tim
    e in 
    Seco
    nds
    TD Series
    Overload Trip Curves 
    						
    							TD - Series- 10 -
    TD  Series    Digital Solid State Soft Starter 48 - 1250A
    4.1   Power Connections
    Connect appropriate power lines to the unit input terminals marked L1, L\
    2, L3.
    Avoid routing power wires near the control board. Connect the motor lead\
    s to the
    unit terminals marked T1, T2, T3. Refer to NEC standards for wire length\
     and
    sizing. Never interchange input and output connections to the unit. This\
     could
    cause excessive voltage in the control logic circuit and may damage the \
    unit.
    Never connect power factor correction capacitors on the load side of the\
    unit. The SCRs will be seriously damaged if capacitors are located on
    the load side.
    The unit cannot be tested without a motor or other test load connected t\
    o the
    load side of the unit. It may be necessary to use a load bank to test th\
    e unit
    without a motor. Note that line voltage will appear across the output terminals if
    there is no motor or load connected to the unit. In areas where lightnin\
    g is a
    significant problem, stationary air gap lightning arrestors should be co\
    nsidered
    and utilized on the input power source.
    TD Series Unit
    Power Connections
    4.1.1  Grounding
    Connect the ground cable to the ground terminal as labeled on the unit. \
    Refer to
    the National Electrical Code for the proper ground wire sizing and be su\
    re that
    the ground connector is connected to earth ground.
    4.2   Control Connections
    4.2.1  Control Power Connections
    Separate 120VAC supply is required (order 240 VAC if required). The control
    voltage should be connected to pins 1 and 6 of TB1. This control voltage\
     must be
    customer supplied, unless an optional control power transformer has been\
     supplied
    with the unit.  The terminal block TB1 is located on the main power boar\
    d.
    However, on units rated 150 Amps and above, TB1 us brought out to a duplicate
    terminal block on the back panel assembly.TB1
    Chapter 4 - Connections
    120V
    Control Power 120V
    Control Power
    Return
    Unit comes standard with
    120VAC control. Order 240VAC
    control as an option if required.
        WARNING 
    						
    							TD - Series- 11 -
    TD SeriesDigital Solid State Soft Starter 48 - 1250A
    For standard 3-wire control connect 120VAC to pins 1 and 6 of TB1. Connect
    N.C. (normally closed) stop button between pins 3 and 4 of TB1. Connec\
    t N.O.
    (normally open) start button between pins 4 and 5 of terminal block TB\
    1.
    4.2.3  Two-Wire Connection
    An alternate connection for unattended operation replaces start/stop pus\
    h buttons
    by connecting a maintained contact closure between pins 3 and 5 on TB1. \
    When
    the maintained contact is used for start/stop it is necessary to set the\
     overload
    relay to the manual reset position. This will prevent the motor from res\
    tarting if
    the thermal overload trips and then cools off.
    When two-wire connection method is used, the user’s control circuit
    must be interlocked to prevent automatic restart when   protective
    devices reset. Refer to section 3.1.3.b.
    4.2.4  Relay Contacts
    All the relay contacts are FORM C common (N.O., N.C.), except the optical
    triac output. TOSHIBA recommends fusing all contacts with external fuses\
    . TB2
    is the terminal block for all auxiliary contacts. Each contact is explai\
    ned in the
    following sections. See Chapter 9 for main control board layout.
    4.2.5  Programmable Relays
    Three programmable relays are on TB2 which is located on the main contro\
    l
    board. The relays are rated for 240 VAC, 5 A and 1200 VA.
    Factory settings for these relays are:
    AUX 1 - Run / Stop (F050 = 1 )
    AUX 2 - At Speed / Stop (F051 = 2)
    AUX 3 - Any Trip (F052 = 14)
    Two-Wire Connection
    TB1
    Three-Wire Connection
    TB1
    4.2.2 Three-Wire Connection
        WARNING 
    						
    							TD - Series- 12 -
    TD  Series    Digital Solid State Soft Starter 48 - 1250A
    4.2.6  Fault Signal
    An optical AC switch triac driver is used for fault indication. This signal energizes
    with the fault LED. The optical output is rated for 240 VAC, 50 mA (maximum).
    4.2.7 Resetting Faults
    To reset faults, press the RESET key on the keypad.
    4.2.8  Enabling the Jog Function
    Closing TB4 Pins 1 and 2 will enable the Jog feature. The Jog feature can be
    used for tasks such as  lining up machines for blade or bit changes or inching
    belts along to check tracking. See chapter 9 for main control board layout.
    4.2.9  Enabling the Dual Ramp Feature
    Closing TB4 Pins 1 and 3 will enable ramp 2. The dual ramp feature is useful in
    instances where a load changes such as a loaded or unloaded conveyor belt.
    The characteristics for starting an unloaded conveyor can be programmed for
    ramp 1. The characteristics for starting a loaded conveyor can be programmed
    for ramp 2.
    4.3 Interlock Connection
    TB1 provides a connection point  for an external user N.C. (normally closed)
    interlock device between pins 2 and 3. (Examples of the use of this interlock
    connection would be for conditions such as low oil, high temperature, or excess
    vibration from user supplied devices).
    A factory installed jumper is provided which allows the TD unit to operate if
    external interlocks are not used. If this jumper is removed and an interlock is not
    used, the TD unit will not function.
    1      2      3
    TB4
    CommonDual
    Ramp
    1      2      3
    TB4
    CommonJog
    123456
    TB1
    Interlock
    12345678910
    C NO NC C NO NC C NO NC
    TB2
    240Vac
    50mA 240Vac / 5A / 1200VA
    AUX 3
    Fn F051 Fn F052Optical Triac
    DriverAUX 1
    Fn F050AUX 2
    11 12
    Programmable
    RelayProgrammable Programmable
    Relay RelayFault
    Signal 
    						
    							TD - Series- 13 -
    TD SeriesDigital Solid State Soft Starter 48 - 1250A
    5.1    Introduction
    It is best to operate the motor at its full load starting condition to achieve the
    proper time, torque and ramp settings. Initial factory settings are set to
    accommodate general motor applications and provide basic motor protection.
    Advanced features must be enabled via programming. The only parameter that
    MUST be set by the user is motor FLA (F001).
    5.2    Digital Interface
    The TD Soft Starter includes an intuitive, digital keypad with eight  LEDs, seven
    command keys, and an LED display with four alphanumeric digits.
    Chapter 5 - Programming
    MOTOR FLA (F001) 
    must be programmed 
    for unit to operate.
    Reset Clears the trip indicator and releases the trip relay.
    Fn Enters or exits the program mode.
    Up ArrowNavigates through the Status Display Mode, scrolls up through the list 
    of functions, increases the value of an active (flashing) digit, and scrolls 
    through the history of fault conditions.
    Right ArrowEach keypress shifts the active (flashing) digit to the right one position, 
    use to change function number or value.
    Down ArrowNavigates through the Status Display Mode, scrolls down through the 
    list of functions, decreases the value of an active (flashing) digit, and 
    scrolls through the history of fault conditions.
    Left ArrowEach keypress shifts the flashing digit to the left one position, use to 
    change function number or value.
    Read Enter Selects and stores the value of a function.
    Power On Control power is present. 
    At Speed Motor is at full speed and power.
    (The SCRs have phased fully on.)
    Shorted SCRShorted SCR has been detected in the unit. Refer to section 8.2 for 
    instructions on checking SCRs. 
    Phase Loss One or more of the phase currents is low or has been lost while the 
    motor was starting or running.
    Over Temp Motor starter has tripped due to heat sink over temperature.
    Over LoadStarters motor overload has tripped. The overload must be reset 
    before the fault can be cleared
    Display88884 digit 7 segment display
    Keys
    Green 
    LEDs
    Two or more power poles are shorted and current is passing to the 
    motor while in the off mode. For positive motor protection, an auxiliary 
    relay should be be programmed for Shunt Trip and should be 
    interlocked with a shunt trip breaker or in-line contactor. (In the event o
    f 
    a shunt trip, do not re-power the unit without repairing the power poles.)
    Over CurrentOver Current LED illuminates for two sets of fault conditions: over 
    current and short circuit.
    If unit experiences output current (of any phase) in excess of the value 
    programmed in F034 (over current trip %) for the time period specified 
    in F035 (over current trip delay), this LED will illuminate and either 
    oCA, oCC, or oCd will be displayed. 
    If unit experiences a short circuit fault condition, the Over Current LED 
    illuminates and either SCA, SCC, or SCd will be displayed. This trip is 
    fixed at 10 times the full load motor current and is not adjustable.  Shunt Trip
    Yellow 
    LEDs 
    						
    							TD - Series- 14 -
    TD  Series    Digital Solid State Soft Starter 48 - 1250A
    5.3    Display Modes
    There are three modes of display: the Status Display mode, the Program mode,
    and the Fault mode.
    5.3.1 Status Display Mode
    The Status Display Mode displays three phase motor current information and the
    thermal capacity remaining.
    Status mode:
    •[0000.] The initial display on power up is four digits and the decimal. This
    indicates the motor current for Phase A of the motor.
    •[0000] Scroll up to display four digits only (no decimal). This indicates
    the motor current for either Phase B or C. While viewing Phase A, press
    the UP arrow once to view Phase B or twice to view Phase C current.
    •[H000] Scroll up to display the “H”. This indicates that this value is the
    remaining thermal capacity  of the motor (as a percentage i.e. H070 =
    70% remaining thermal capacity)
    Reading Phase Current and Thermal Capacity (See Example)
    [0120.]Indicates that Phase A is
    drawing 120 amps.
    Press the UP arrow.
    [0121]Indicates that Phase B is
    drawing 121 amps.
    Press the UP arrow.
    NOTE: Decimal points are not
    present in the readouts
    for Phase B and Phase C.
    [0120]Indicates that Phase C is
    drawing 120 amps.
    Press the UP arrow.
    [H051]Indicates that the motor has
    51% of its thermal capacity
    remaining.
    5.3.2 Program Mode
    Use the Program Mode to view or change Function (Fn) settings.
    To enter the Program Mode, press the [Fn] key once. The first time you enter
    Program Mode after power has been cycled to the starter, the initial function
    [F001] should display with the selected digit flashing. If the TD Soft Starter has
    been programmed and power to the unit has not been cycled, the readout will
    display the last function viewed or changed.
    To change to a different function, use the arrow keys.
    Program Mode:
    •[F001] The “F” indicates the programmable function.
    •[0000] This is the present setting of the applicable function. This display
    may include decimals between digits depending on the function setting’s
    range and incremental step.
            Display
    Reading Phase Current
    and
    Thermal Capacity
    0 120.
    0 121
    0 120
    H05 1
    Phase A
    Phase B
    Phase C
    Remaining Thermal
    CapacityPress 
    						
    All Toshiba manuals Comments (0)