Toshiba Dvr 35 Instruction Manual
Have a look at the manual Toshiba Dvr 35 Instruction Manual online for free. It’s possible to download the document as PDF or print. UserManuals.tech offer 566 Toshiba manuals and user’s guides for free. Share the user manual or guide on Facebook, Twitter or Google+.

TD - Series- 5 - TD SeriesDigital Solid State Soft Starter 48 - 1250A 2.5 Mounting and Cleaning When drilling or punching holes in the enclosure, cover the electrical a\ ssembly to prevent metal filings from becoming lodged in areas which can cause clearance reduction or actually short out electronics. After work is com\ plete, thoroughly clean the area and reinspect the unit for foreign material. M\ ake sure there is sufficient clearance (six inches) all around the unit fo\ r cooling, wiring and maintenance purposes. To maximize effective air flow and cooling, the unit must be installed with its heat sink ribs oriented vertically a\ nd running parallel to the mounting surface. Remove all sources of power before cleaning the unit. In dirty or contaminated atmospheres the unit should be cleaned on a reg\ ular basis to ensure proper cooling. Do not use any chemicals to clean the un\ it. To remove surface dust use 80 to 100 psi, clean, dry compressed air only. A three inch, high quality, dry paint brush is helpful to loosen up the dust prior to using compressed air on the unit. 2.6 Power Terminal Wire Range and Tightening Torque Note: All wiring must be sized according to NEC standards. WARNING Model Number Wire range Torque lbs/in TD005#18 - #4 20 TD006 #14 - #2 50 TD007 TD008 TD009 TD010 TD011 TD012 TD013 TD014 TD015 TD016 TD017 #6 - 250 kcmil 325 375 (3) #2 - 600 kcmil 375 (2) #2 - 600 kcmil 375 (2) #2 - 600 kcmil (4) #2 - 600 kcmil 375

TD - Series- 6 - TD Series Digital Solid State Soft Starter 48 - 1250A 2.7 Dimensions TD CHASSIS (PANEL MOUNT) DIMENSIONS Ove ra ll Dimensions Mounting Dime nsions Mode l Numbe r (inche s) (inches) AB CDEF TD005A - TD007A16. 5 10 10 15. 9 9 0. 28 TD008A20 20. 1 12 18. 5 17. 5 0. 44 TD009A - TD010A27 20. 1 11.2 25. 5 17. 5 0. 44 TD011A - TD013A29. 5 20. 1 11.5 25. 5 17. 5 0. 44 TD014A - TD015A45 33 12.8 43.3 31.3 0.44 TD016A - TD017A33 33 15.2 31.2 31.2 0.44

TD - Series- 7 - TD SeriesDigital Solid State Soft Starter 48 - 1250A Chapter 3 - Motor Overload Protection 3.1 Solid State Overload Protection The TD Series Starter provides true U.L. listed I2T Thermal Overload Protection as a built-in function of the main digital processor. For maximum protection it simulates the tripping action of a bimetallic overload relay, with the accuracy and repeatability of a digital control system, yet is adjustable over a wide\ range and can be easily programmed for different trip curves. 3.1.1 Thermal Memory The TD Series microprocessor uses a sophisticated “Thermal Register” to keep track of motor heating and cooling over time regardless of the starter’\ s power status. The TD Series does not “forget” that the motor has been running even if power to the starter is turned off and back on. Continuous overload prot\ ection is provided based on the true thermal condition of the motor. 3.1.2 Thermal Capacity The Thermal Register is displayed as a percentage. This percentage is th\ e motor’s remaining thermal capacity. The percentage value begins at 100, showing that the motor is cool. As the motor heats up or moves toward an overload con\ dition, the percentage begins to drop. The Thermal Capacity is derived from the programmed motor nameplate Full Load Amps (FLA) in Function F001, the \ Service Factor rating in Function F002, and the Overload Trip Class in Functions\ F003 and F004. Setting these functions to the proper values will provide maxi\ mum protection yet eliminates nuisance tripping. 3.1.2.a Motor Full Load (FLA) Setting Use Function F001 to enter motor FLA as indicated on the motor nameplate\ . (Do not calculate for service factor, this is programmed separately in F002). Note: If F001 is left at the factory default, the unit will not operate. If the user attempts to start the TD without entering the motor nameplate FLA into this Function, the TD will Fault, and the display will read “nFLA” (for no Full Load Amps). 3.1.3 Disabling the Overload Protection The Overload Protection feature can be disabled if absolutely necessary. When using external devices such as Motor Protection Relays or when the TD Series is wired downstream from an existing starter, this feature can be disabled to prevent conflicts with external overload protection devices. When the TD Series is controlling multiple motors, Overload Protection must be disabled. In\ dividual thermal overload relays must be installed on the motor leads going to ea\ ch motor. To disable the Overload Protection function, use F005. (See Section 5.)\ Do NOT disable Overload Protection unless another Thermal Overload Protection device exists in the circuit for all three phases. Running a motor without Overload Protection presents serious risk of motor damage or fire. 3.1.3.a Manual Reset The factory default setting is Manual Reset. This means that when the Ov\ erload Trip is activated, the starter cannot be restarted without pressing the Reset key. The Overload Trip will not reset until the motor cools down. The Manual \ Reset function is also “trip free”. Holding in the Reset key will not prevent the Overload Trip from activating and protecting the motor. Note: When the Overload Trip activates, the Overload LED will glow solid. When the motor cools down, the LED will begin to flash, indicating that the Overload Trip can be reset. WARNING

TD - Series- 8 - TD Series Digital Solid State Soft Starter 48 - 1250A 3.1.3.b Automatic Reset If Automatic Reset is necessary, change from Manual Reset to Automatic Reset by using Function F005. (See Section 5 for details). In this mode, a 3\ -wire control circuit will be capable of restart when the TD Series has reset itself a\ fter the cool down period. Two-wire control systems may restart without warning when Auto Reset is selected. Extreme caution should be exercised. To prevent automatic restarting with two-wire control systems, use external interlocking to provide sufficient warning and safety to operators. A Warning Label (su\ ch as the one provided in the packet with this manual) must be placed to b\ e visible on the starter enclosure and/or the equipment as required by loc\ al code. 3.2 NEMA Class Trip Curves The TD Series Soft Starter provides six NEMA Class trip curve options: 5, 10, 15, 20, 25, and 30. Program the appropriate curve according to the chara\ cteristics of your motor and load. NEMA Class trip curves are based on a common tripping point of 600% of r\ ated current. Curves vary by the amount of time before the unit trips. As an \ example, a Class 20 curve will trip in 20 seconds at 600%. The factory default se\ tting of Class 10 will trip in 10 seconds at 600%. 3.2.1 Dual Overload Trip Curves The TD Series Soft Starter provides two separate Overload Trip Protection Curves, one for starting and one for running conditions. Programming a higher NE\ MA Class overload during start (ramp-up) will eliminate nuisance tripping\ in higher inertia or high friction loads. The starter’s At-Speed detection circuit determines when the motor ha\ s reached full speed based on closed loop feedback signals. When the At-Speed cond\ ition is reached, the overload trip curve will shift from the Start to the Run\ level, as programmed in Functions F003 and F004. See Section 5 for programming det\ ails. MOTOR CONNECTED TO THIS EQUIPMENT MAY START AUTOMATICALLY WITHOUT WARNING WARNING

TD - Series- 9 - TD SeriesDigital Solid State Soft Starter 48 - 1250A Note: Factory default setting is Class 10 for both Start and Run Overl\ oad Protection Class 30Class 25 Class 20 Class 15 Class 10 Class 5 MFLA Tim e in Seco nds TD Series Overload Trip Curves

TD - Series- 10 - TD Series Digital Solid State Soft Starter 48 - 1250A 4.1 Power Connections Connect appropriate power lines to the unit input terminals marked L1, L\ 2, L3. Avoid routing power wires near the control board. Connect the motor lead\ s to the unit terminals marked T1, T2, T3. Refer to NEC standards for wire length\ and sizing. Never interchange input and output connections to the unit. This\ could cause excessive voltage in the control logic circuit and may damage the \ unit. Never connect power factor correction capacitors on the load side of the\ unit. The SCRs will be seriously damaged if capacitors are located on the load side. The unit cannot be tested without a motor or other test load connected t\ o the load side of the unit. It may be necessary to use a load bank to test th\ e unit without a motor. Note that line voltage will appear across the output terminals if there is no motor or load connected to the unit. In areas where lightnin\ g is a significant problem, stationary air gap lightning arrestors should be co\ nsidered and utilized on the input power source. TD Series Unit Power Connections 4.1.1 Grounding Connect the ground cable to the ground terminal as labeled on the unit. \ Refer to the National Electrical Code for the proper ground wire sizing and be su\ re that the ground connector is connected to earth ground. 4.2 Control Connections 4.2.1 Control Power Connections Separate 120VAC supply is required (order 240 VAC if required). The control voltage should be connected to pins 1 and 6 of TB1. This control voltage\ must be customer supplied, unless an optional control power transformer has been\ supplied with the unit. The terminal block TB1 is located on the main power boar\ d. However, on units rated 150 Amps and above, TB1 us brought out to a duplicate terminal block on the back panel assembly.TB1 Chapter 4 - Connections 120V Control Power 120V Control Power Return Unit comes standard with 120VAC control. Order 240VAC control as an option if required. WARNING

TD - Series- 11 - TD SeriesDigital Solid State Soft Starter 48 - 1250A For standard 3-wire control connect 120VAC to pins 1 and 6 of TB1. Connect N.C. (normally closed) stop button between pins 3 and 4 of TB1. Connec\ t N.O. (normally open) start button between pins 4 and 5 of terminal block TB\ 1. 4.2.3 Two-Wire Connection An alternate connection for unattended operation replaces start/stop pus\ h buttons by connecting a maintained contact closure between pins 3 and 5 on TB1. \ When the maintained contact is used for start/stop it is necessary to set the\ overload relay to the manual reset position. This will prevent the motor from res\ tarting if the thermal overload trips and then cools off. When two-wire connection method is used, the user’s control circuit must be interlocked to prevent automatic restart when protective devices reset. Refer to section 3.1.3.b. 4.2.4 Relay Contacts All the relay contacts are FORM C common (N.O., N.C.), except the optical triac output. TOSHIBA recommends fusing all contacts with external fuses\ . TB2 is the terminal block for all auxiliary contacts. Each contact is explai\ ned in the following sections. See Chapter 9 for main control board layout. 4.2.5 Programmable Relays Three programmable relays are on TB2 which is located on the main contro\ l board. The relays are rated for 240 VAC, 5 A and 1200 VA. Factory settings for these relays are: AUX 1 - Run / Stop (F050 = 1 ) AUX 2 - At Speed / Stop (F051 = 2) AUX 3 - Any Trip (F052 = 14) Two-Wire Connection TB1 Three-Wire Connection TB1 4.2.2 Three-Wire Connection WARNING

TD - Series- 12 - TD Series Digital Solid State Soft Starter 48 - 1250A 4.2.6 Fault Signal An optical AC switch triac driver is used for fault indication. This signal energizes with the fault LED. The optical output is rated for 240 VAC, 50 mA (maximum). 4.2.7 Resetting Faults To reset faults, press the RESET key on the keypad. 4.2.8 Enabling the Jog Function Closing TB4 Pins 1 and 2 will enable the Jog feature. The Jog feature can be used for tasks such as lining up machines for blade or bit changes or inching belts along to check tracking. See chapter 9 for main control board layout. 4.2.9 Enabling the Dual Ramp Feature Closing TB4 Pins 1 and 3 will enable ramp 2. The dual ramp feature is useful in instances where a load changes such as a loaded or unloaded conveyor belt. The characteristics for starting an unloaded conveyor can be programmed for ramp 1. The characteristics for starting a loaded conveyor can be programmed for ramp 2. 4.3 Interlock Connection TB1 provides a connection point for an external user N.C. (normally closed) interlock device between pins 2 and 3. (Examples of the use of this interlock connection would be for conditions such as low oil, high temperature, or excess vibration from user supplied devices). A factory installed jumper is provided which allows the TD unit to operate if external interlocks are not used. If this jumper is removed and an interlock is not used, the TD unit will not function. 1 2 3 TB4 CommonDual Ramp 1 2 3 TB4 CommonJog 123456 TB1 Interlock 12345678910 C NO NC C NO NC C NO NC TB2 240Vac 50mA 240Vac / 5A / 1200VA AUX 3 Fn F051 Fn F052Optical Triac DriverAUX 1 Fn F050AUX 2 11 12 Programmable RelayProgrammable Programmable Relay RelayFault Signal

TD - Series- 13 - TD SeriesDigital Solid State Soft Starter 48 - 1250A 5.1 Introduction It is best to operate the motor at its full load starting condition to achieve the proper time, torque and ramp settings. Initial factory settings are set to accommodate general motor applications and provide basic motor protection. Advanced features must be enabled via programming. The only parameter that MUST be set by the user is motor FLA (F001). 5.2 Digital Interface The TD Soft Starter includes an intuitive, digital keypad with eight LEDs, seven command keys, and an LED display with four alphanumeric digits. Chapter 5 - Programming MOTOR FLA (F001) must be programmed for unit to operate. Reset Clears the trip indicator and releases the trip relay. Fn Enters or exits the program mode. Up ArrowNavigates through the Status Display Mode, scrolls up through the list of functions, increases the value of an active (flashing) digit, and scrolls through the history of fault conditions. Right ArrowEach keypress shifts the active (flashing) digit to the right one position, use to change function number or value. Down ArrowNavigates through the Status Display Mode, scrolls down through the list of functions, decreases the value of an active (flashing) digit, and scrolls through the history of fault conditions. Left ArrowEach keypress shifts the flashing digit to the left one position, use to change function number or value. Read Enter Selects and stores the value of a function. Power On Control power is present. At Speed Motor is at full speed and power. (The SCRs have phased fully on.) Shorted SCRShorted SCR has been detected in the unit. Refer to section 8.2 for instructions on checking SCRs. Phase Loss One or more of the phase currents is low or has been lost while the motor was starting or running. Over Temp Motor starter has tripped due to heat sink over temperature. Over LoadStarters motor overload has tripped. The overload must be reset before the fault can be cleared Display88884 digit 7 segment display Keys Green LEDs Two or more power poles are shorted and current is passing to the motor while in the off mode. For positive motor protection, an auxiliary relay should be be programmed for Shunt Trip and should be interlocked with a shunt trip breaker or in-line contactor. (In the event o f a shunt trip, do not re-power the unit without repairing the power poles.) Over CurrentOver Current LED illuminates for two sets of fault conditions: over current and short circuit. If unit experiences output current (of any phase) in excess of the value programmed in F034 (over current trip %) for the time period specified in F035 (over current trip delay), this LED will illuminate and either oCA, oCC, or oCd will be displayed. If unit experiences a short circuit fault condition, the Over Current LED illuminates and either SCA, SCC, or SCd will be displayed. This trip is fixed at 10 times the full load motor current and is not adjustable. Shunt Trip Yellow LEDs

TD - Series- 14 - TD Series Digital Solid State Soft Starter 48 - 1250A 5.3 Display Modes There are three modes of display: the Status Display mode, the Program mode, and the Fault mode. 5.3.1 Status Display Mode The Status Display Mode displays three phase motor current information and the thermal capacity remaining. Status mode: •[0000.] The initial display on power up is four digits and the decimal. This indicates the motor current for Phase A of the motor. •[0000] Scroll up to display four digits only (no decimal). This indicates the motor current for either Phase B or C. While viewing Phase A, press the UP arrow once to view Phase B or twice to view Phase C current. •[H000] Scroll up to display the “H”. This indicates that this value is the remaining thermal capacity of the motor (as a percentage i.e. H070 = 70% remaining thermal capacity) Reading Phase Current and Thermal Capacity (See Example) [0120.]Indicates that Phase A is drawing 120 amps. Press the UP arrow. [0121]Indicates that Phase B is drawing 121 amps. Press the UP arrow. NOTE: Decimal points are not present in the readouts for Phase B and Phase C. [0120]Indicates that Phase C is drawing 120 amps. Press the UP arrow. [H051]Indicates that the motor has 51% of its thermal capacity remaining. 5.3.2 Program Mode Use the Program Mode to view or change Function (Fn) settings. To enter the Program Mode, press the [Fn] key once. The first time you enter Program Mode after power has been cycled to the starter, the initial function [F001] should display with the selected digit flashing. If the TD Soft Starter has been programmed and power to the unit has not been cycled, the readout will display the last function viewed or changed. To change to a different function, use the arrow keys. Program Mode: •[F001] The “F” indicates the programmable function. •[0000] This is the present setting of the applicable function. This display may include decimals between digits depending on the function setting’s range and incremental step. Display Reading Phase Current and Thermal Capacity 0 120. 0 121 0 120 H05 1 Phase A Phase B Phase C Remaining Thermal CapacityPress