TD - Series- 5 - TD SeriesDigital Solid State Soft Starter 48 - 1250A 2.5 Mounting and Cleaning When drilling or punching holes in the enclosure, cover the electrical a\ ssembly to prevent metal filings from becoming lodged in areas which can cause clearance reduction or actually short out electronics. After work is com\ plete, thoroughly clean the area and reinspect the unit for foreign material. M\ ake sure there is sufficient clearance (six inches) all around the unit fo\ r cooling, wiring and...
Page 12
TD - Series- 6 - TD Series Digital Solid State Soft Starter 48 - 1250A 2.7 Dimensions TD CHASSIS (PANEL MOUNT) DIMENSIONS Ove ra ll Dimensions Mounting Dime nsions Mode l Numbe r (inche s) (inches) AB CDEF TD005A - TD007A16. 5 10 10 15. 9 9 0. 28 TD008A20 20. 1 12 18. 5 17. 5 0. 44 TD009A - TD010A27 20. 1 11.2 25. 5 17. 5 0. 44 TD011A - TD013A29. 5 20. 1 11.5 25. 5 17. 5 0. 44 TD014A - TD015A45 33 12.8 43.3 31.3 0.44 TD016A - TD017A33 33 15.2 31.2 31.2 0.44
Page 13
TD - Series- 7 - TD SeriesDigital Solid State Soft Starter 48 - 1250A Chapter 3 - Motor Overload Protection 3.1 Solid State Overload Protection The TD Series Starter provides true U.L. listed I2T Thermal Overload Protection as a built-in function of the main digital processor. For maximum protection it simulates the tripping action of a bimetallic overload relay, with the accuracy and repeatability of a digital control system, yet is adjustable over a wide\ range and can be easily programmed for...
Page 14
TD - Series- 8 - TD Series Digital Solid State Soft Starter 48 - 1250A 3.1.3.b Automatic Reset If Automatic Reset is necessary, change from Manual Reset to Automatic Reset by using Function F005. (See Section 5 for details). In this mode, a 3\ -wire control circuit will be capable of restart when the TD Series has reset itself a\ fter the cool down period. Two-wire control systems may restart without warning when Auto Reset is selected. Extreme caution should be exercised. To prevent automatic...
Page 15
TD - Series- 9 - TD SeriesDigital Solid State Soft Starter 48 - 1250A Note: Factory default setting is Class 10 for both Start and Run Overl\ oad Protection Class 30Class 25 Class 20 Class 15 Class 10 Class 5 MFLA Tim e in Seco nds TD Series Overload Trip Curves
Page 16
TD - Series- 10 - TD Series Digital Solid State Soft Starter 48 - 1250A 4.1 Power Connections Connect appropriate power lines to the unit input terminals marked L1, L\ 2, L3. Avoid routing power wires near the control board. Connect the motor lead\ s to the unit terminals marked T1, T2, T3. Refer to NEC standards for wire length\ and sizing. Never interchange input and output connections to the unit. This\ could cause excessive voltage in the control logic circuit and may damage the \ unit. Never...
Page 17
TD - Series- 11 - TD SeriesDigital Solid State Soft Starter 48 - 1250A For standard 3-wire control connect 120VAC to pins 1 and 6 of TB1. Connect N.C. (normally closed) stop button between pins 3 and 4 of TB1. Connec\ t N.O. (normally open) start button between pins 4 and 5 of terminal block TB\ 1. 4.2.3 Two-Wire Connection An alternate connection for unattended operation replaces start/stop pus\ h buttons by connecting a maintained contact closure between pins 3 and 5 on TB1. \ When the maintained...
Page 18
TD - Series- 12 - TD Series Digital Solid State Soft Starter 48 - 1250A 4.2.6 Fault Signal An optical AC switch triac driver is used for fault indication. This signal energizes with the fault LED. The optical output is rated for 240 VAC, 50 mA (maximum). 4.2.7 Resetting Faults To reset faults, press the RESET key on the keypad. 4.2.8 Enabling the Jog Function Closing TB4 Pins 1 and 2 will enable the Jog feature. The Jog feature can be used for tasks such as lining up machines for blade or bit...
Page 19
TD - Series- 13 - TD SeriesDigital Solid State Soft Starter 48 - 1250A 5.1 Introduction It is best to operate the motor at its full load starting condition to achieve the proper time, torque and ramp settings. Initial factory settings are set to accommodate general motor applications and provide basic motor protection. Advanced features must be enabled via programming. The only parameter that MUST be set by the user is motor FLA (F001). 5.2 Digital Interface The TD Soft Starter includes an...
Page 20
TD - Series- 14 - TD Series Digital Solid State Soft Starter 48 - 1250A 5.3 Display Modes There are three modes of display: the Status Display mode, the Program mode, and the Fault mode. 5.3.1 Status Display Mode The Status Display Mode displays three phase motor current information and the thermal capacity remaining. Status mode: •[0000.] The initial display on power up is four digits and the decimal. This indicates the motor current for Phase A of the motor. •[0000] Scroll up to display four...