ModelCW -XC71YACW -XC91YA PhaseSingleSingle Voltage220 V220 V Frequency50 Hz50 Hz Cooling Capacity2.06 kW 7,000 Btu/h2.64 kW 9,000 Btu/h Running Current3.1 A4.1 A Input Power650 W880 W EER3.17 W/W3.00 W/W Starting Current11 A18 A Compressor Output550 W750 W Noise LevelIndoor (High / Low): 45 dB(A) / 35 dB(A) Outdoor (High / Low): 55 dB(A) / 50 dB(A)Indoor (High / Low): 45 dB(A) / 37 dB(A) Outdoor (High / Low): 56 dB(A) / 53 dB(A) Moisture Removal1.3 Ltr/h 2.7 Pint/h1.6 Ltr/h 3.4 Pint/h © 2001 Matsushita Industrial Corp. Sdn. Bhd. (11969-T). All rights reserved. Unauthorized copying and distribution is a violation of law. CW-XC71YA CW-XC91YA ModelCW -XC71YACW -XC91YA Air Circulation7.1 m3/min. 250 Ft 3/min. 7.1 m3/min. 250 Ft 3/min. DimensionsHeight: 346 mm (13-5/8 inches) Width: 450 mm (17-23/32 inches) Depth: 580 mm (22-27/32 inches)Height: 346 mm (13-5/8 inches) Width: 450 mm (17-23/32 inches) Depth: 580 mm (22-27/32 inches) Net Weight31 kg 68 Ib34 kg 75 Ib Refrigerant (R-22)510 g 18.0 oz465 g 16.4 oz Note: Specifications are subject to change without notice for further improvement. Room Air Conditioner Specification Order No. MAC0107036C3
1 Functions 2 2 Dimensions 4 3 Refrigeration Cycle Diagram 5 4 Block Diagram 5 5 Wiring Diagram 6 6 Air Conditioner Performance Evaluation 7 7 Troubleshooting Guide 8 8 Operation Details 9 9 Operating Instructions 12 10 How To Install 17 11 Care and Maintenance 21 12 Service Information 22 13 Exploded View 23 14 Replacement Part List 24 15 Electronic Circuit / Indicator Complete 25 16 Electronic Circuit / Main 25 17 Technical Data 26 18 Electronic Circuit Diagram 27 CONTENTS Page Page 1 Functions 1.1. Remote Control 2 CW-XC71YA / CW-XC91YA
2 Dimensions 2.1. CW-XC71YA CW-XC91YA 2.1.1. Top View, Front View and Side View. ItemUnit: Inch (mm) A - Width17-23/32” (450) B - Height13-5/8” (346) C - Depth22-27/32” (580) D21-1/4” (540) E5-21/32” (144) F6-1/32” (153) G1-31/32” (50) H3-27/32” (98) I1-3/16” (30) J3-27/32” (98) K1-9/16” (40) L9-7/32” (234) M3-27/32” (98) N2-31/32” (75) O1-11/16” (43) P3-17/32” (90) Q0-29/32” (23) R10-11/32” (263) 4 CW-XC71YA / CW-XC91YA
3.1. CW-XC71YA CW-XC91YA3.2. CW-XC71YA ItemPressure (MPa)Temperature (°C) A1.91 ~ 2.1170 ~ 85 B1.86 ~ 2.0635 ~ 45 C0.60 ~ 0.668~14 D0.57 ~ 0.6310 ~ 18 Note: Indoor temperature at 27°C (DB), 19°C(WB) andOutdoor at 35°C (DB), 24°C(WB). 3.3. CW-XC91YA ItemPressure (MPa)Temperature (°C) A2.00 ~ 2.2072 ~ 87 B1.95 ~ 2.1535 ~ 45 C0.54 ~ 0.607~13 D0.51 ~ 0.579~17 Note: Indoor temperature at 27°C (DB), 19°C(WB) andOutdoor at 35°C (DB), 24°C(WB). 3 Refrigeration Cycle Diagram 4 Block Diagram 4.1. CW-XC71YA CW-XC91YA 5 CW-XC71YA / CW-XC91YA
5.2. Resistance of Fan Motor windings and the rated Capacitor. ModelCW-XC71YACW-XC91YA ConnectionCWA921085CWA921085 Blue - Yellow76.6Ω76.6Ω Yellow - Brown19.2Ω19.2Ω Brown - Orange133.3Ω133.3Ω Red - Yellow119.1Ω119.1Ω 5.3. Resistance of Compressor windings and the rated Capacitor. ModelCW-XC71YACW-XC91YA Connection2RS122D5AA042PS156D5CA02 C-R4.023Ω3.501Ω C-S8.803Ω3.405Ω CapacitorCWA312074 (15µF, 400VAC)DS371306CPNA (30µF, 370VAC) Note: Resistance at 20°C of Ambient Temperature. 5 Wiring Diagram 5.1. CW-XC71YA CW-XC91YA 6 CW-XC71YA / CW-XC91YA
6 Air Conditioner Performance Evaluation Suction & Discharge Air Temperature DifferenceCurrentDeterminationRemedy • • • • 8°C and over (14.4°F) • • • • As specified. • • • • Nothing wrong. • • • • None. • • • • 8°C and over (14.4°F) • • • • Higher than specified. • • • • Nothing wrong, outdoor temperature is too high, heat radiation is not efficient. • • • • Improve heat radiation. • • • • Under 8°C (14.4°F) • • • • Higher than specified. • • • • Something is preventing heat radiation. • • • • Excessive amount of refrigerant. • • • • Improve heat radiation. • • • • Under 8°C (14.4°F) • • • • Lower than specified. • • • • Leakage of refrigerant or refrigerant system is blocked. • • • • Locate and repair leak. • • • • Flush refrigeration cycle. • • • • Under 8°C (14.4°F) • • • • Higher than specified by 50%. • • • • Compressor defect. • • • • Replace the compressor. Note: Room air humidity is relatively higher, the temperature differen ce will be smaller. 7 CW-XC71YA / CW-XC91YA
7 Troubleshooting Guide Warning: Disconnect unit from electrical powersupply before making any electrical checks. TroubleCheckResultCauseRemedy Fan Motor and Compressor won’t run. • • • • Supply Voltage • • • • Fuse Box or Circuit Breaker. • • • • Power cord orWiring Harness. • • • • Temp. Setting. • • • • Less than 10% by Rated. • • • • Open Contacts. • • • • Pulled loose or Shorted. • • • • Higher than ROOM TEMP. • • • • Customer Restarted unit immediately without waiting 3 minutes. • • • • Consult ELECTRICIAN, • • • • Repair Open Circuit. • • • • W AIT FOR 3 MINUTES. • • • • Repair or Replace it. • • • • Set it LOWER. Fan Motor won’t run. • • • • Objects around Fan. • • • • RESISTANCE betweenWires. • • • • Capacitor Fan Motor. • • • • Locked Fan. • • • • Shorted/ Open circuit. • • • • OHM Meter doesn’t Deflect. • • • • Fan Hitting Cowling or • • • • Foreign Materials. • • • • Frozen Bearings. • • • • Shorted or Burned out. • • • • Capacitor Defect. • • • • Adjust Fan position setting screw. • • • • Remove Foreign Materials. • • • • Replace Fan Motor. • • • • Replace Fan Motor. • • • • Replace Capacitor Fan Motor. Compressor won’t run (Fan Runs). • • • • Temp. setting. • • • • RESISTANCE between Terminal and the Compressor Body. • • • • RESISTANCE between Terminals. • • • • Capacitor Compressor. • • • • Inner Protector. • • • • Higher than room temperature. • • • • Shorted. • • • • Shorted. • • • • OHM Meter doesn’t deflect. • • • • Infinity between Terminals. • • • • W inding Coil touched to the Body. • • • • Rare Shorted or Burnt out. • • • • Capacitor defect. • • • • Inner Protector defect. • • • • Set it lower. • • • • Replace Compressor. • • • • Replace Compressor. • • • • Replace Capacitor Compressor. • • • • Replace Protector. Insufficient cooling. • • • • Temp. setting. • • • • Ventilation Door open. • • • • Air filter dirty. • • • • Location of installation. • • • • Evaporator / Condenser Coil obstructed. • • • • Unit capacity for the room too small. • • • • Temp difference and running current. • • • • Higher than room temperature. • • • • Open. • • • • Clogged or dirty. • • • • Sunlight hitting outdoor side. • • • • Obstacles. • • • • Clogged or dirty. • • • • Not satisfied. • • • • REFER TO PERFORMANCE EVALUATIO N. • • • • Reduces capacity. • • • • Restricted air circulation. • • • • Restricted Heat Exchanger. • • • • Restricted Heat Exchanger. • • • • Restricted air circulation. • • • • Leakage of refrigerant or refrigeration system is blocked. • • • • Set it lower. • • • • Close Vent door. • • • • Clean or Replace Air Filter. • • • • Consider building an AWNING. • • • • Remove obstacles or reinstall unit. • • • • Clean using steam cleaner. • • • • Replace the unit with bigger one. • • • • Locate repair leak. • • • • Flush refrigeration cycle. Noise. • • • • Source of Noise • • • • Vibration. • • • • Intermittent Noise. • • • • Faulty installation. • • • • Fan hitting objects. • • • • Refrigerant tubing touching each other. • • • • Fan splashing Drain Water. • • • • Reinstall unit or Reinforce the installation. • • • • Adjust Fan position or remove foreign materials. • • • • About 1/2” Clearance needed. • • • • Remove drain plug and mount a drain pan to remove the water. • • • • Set the Drain outlet downward, so that the Drain water can run off. Water dripping inside room. • • • • Unit installation. • • • • Drain Tray- STYROFOA M pieces blocking Drain Channel. • • • • Tilted to inside room. • • • • Clogged. • • • • Restricted run off. • • • • Clogged or blocked. • • • • Tilt unit to outside slightly. • • • • Remove the foreign materials. 8 CW-XC71YA / CW-XC91YA
8 Operation Details 8.1. Fan Mode Operation • • • • Fan operation only. Fan in operation according to Remote Control or Main Unit (Touch Control Panel) setting. 8.1.1. Manual Setting of Fan Speed • • • • Basic Fan Speed can be manually adjusted (Lo or Hi) by using the Fan Speed Selection Button/Pad at Remote Control or Main Unit (Touch Control Panel). 8.2. Cooling Mode Operation • • • • Cooling in operation according to Remote Control or Main Unit (Touch Control Panel) setting. 8.2.1. Time Delay Safety Control (3 minute) • • • • W hen the compressor is stopped by Power Switch and Operation Switch at the Remote Control or Main Unit (Touch Control Panel), it restart after 3 minutes when the Power Switch and Operation Switch at the Remote Control or Main Unit (Touch Control Panel) is turned ON. • • • • W hen the setting temperature is reached during cooling operation, the compressor stops and it will not start for 3 minutes. • • • • Protection of compressor to balance the pressure in the refrigeration cycle for 3 minutes. 8.2.2. 7 minutes Time Saved Control • • • • The compressor will start automatically if it has stopped for 7 minutes even if theroom temperature is between the compressor ON temperature and OFF temperature. 8.2.3. Starting Current Control • • • • W hen the compressor and fan motor are simultaneously started, the fanmotorwill operate 1.6 seconds later. 8.2.4. Freeze Prevention Control If the temperature of the indoor heat exchan ger falls continuously below 1°C for 3 minutes ormore, the compressor turns off to protect the heat exchan gerfrom freezing. The fan speed setting remains the same. Compressor restarts when the heat exchanger temperature rises to 12°C (Recovery). *3 minutes waiting of Time Delay Safety Control is valid for Cooling Operation. 8.2.5. Compressor Reverse Rotation Protection Control • • • • If the compressor is operating continuously for 5 minutes or longer and thetemperature differen ce between intake air and heat exchan ger is 2.5°C or less for 2 minutes, compressor will stop and restart automatically (TimeDelay Safety Control is valid). 9 CW-XC71YA / CW-XC91YA
8.2.6. Cooling Operation Time Diagram 8.3. Powerful Operation • • • • Purpose of this operation is to obtain the setting temperature quickly. • • • • W hen the Powerful is set during Cooling Operation, the set temperature will be automatically decreased 3°C against the present setting temperature (Lowest limit temperature: 16°C). • • • • This operation automatically will be running under Super High Fan Speed. • • • • Sound emitted by the unit will be increased during Powerful operation due to increased of air volume. • • • • Powerful will operate for 15 minutes only, after that it will shift back to previous operation mode. • • • • Powerful will stop if:- − − − − Powerful button/Pad is pressed again. − − − − Powerful operation has run for 15 minutes. − − − − Stopped by ON/OFF switch. − − − − Timer OFF activates. 8.4. Auto Restart Control • • • • If there is a power failure, operation will be automatically restarted after 3 to 4 minutes when the power is resumed. It will start with previous operation mode and airflow direction (TimeDelay Safety Control is valid) as the operation was not stopped by Remote Control or Main Unit (Touch Control Panel). • • • • Restart time is decided randomly with 5 parameters:- − − − − Intake air temperature. − − − − Setting temperature. − − − − Fan speed. − − − − Air Swing blade position . − − − − Indoor heat exchanger temperature. • • • • Auto Restart Control is not available when Timer is set. • • • • If Powerful is set during power failure, Powerful will not start automatically along with previous operation mode after power resume. • • • • This control can be omitted by open the circuit of JX1. 10 CW-XC71YA / CW-XC91YA