Page 41
10.2.1. SELECT THE BEST LOCATION (Refer to “Select the best location” section) 10.2.2. HOW TO FIX INSTALLATION PLATE The mounting wall is strong and solid enough to prevent it from the vibration. The centre of installation plate should be at more than 450 mm at right and left of the wall. The distance from installation plate edge to ceiling should more than 67 mm. From installation plate left edge to unit’s left side is 47 mm. From installation plate right edge to unit’s right is 73 mm. : : :For left...
Page 42
3. For the embedded piping (This can be used for left rear piping & left bottom piping also.) 42 CS-W7BKP CU-W7BKP5 / CS-W9BKP CU-W9BKP5 / CS-W12BKP CU-W12BKP5
Page 43
10.2.5. CONNECT THE CABLE TO THE INDOOR UNIT 1. The inside and outside connecting cable can be connected without removing the front grille. 2. Connecting cable between indoor unit and outdoor unit shall be approved polychloroprene sheathed 3 (C7BK, C9BK, C12BK, V7BK, V9BK, V12BK) or 5 (A7BK, A9BK, A12BK, W7BK, W9BK, W12BK) × 1.5 mm 2flexible cord, type designation 245 IEC57 or heavier cord. • Ensure the color of wires of outdoor unit and the terminal Nos. are the same to the indoor’s respectively. •...
Page 44
HOW TO TAKE OUT FRONT GRILLE Please follow the steps below to take out front grille if necessary such as when servicing. 1. Set the vertical airflow direction louver to the horizontal position. 2. Slide down the two caps on the front grille as shown in the illustration below, and then remove the two mounting screws. 3. Pull the lower section of the front grille towards you to remove the front grille. When reinstalling the front grille, first set the vertical airflow direction louver to the horizontal...
Page 45
CUTTING AND FLARING THE PIPING 1. Please cut using pipe cutter and then remove the burrs. 2. Remove the burrs by using reamer. If burrs is not removed, gas leakage may be caused. Turn the piping end down to avoid the metal powder entering the pipe. 3. Please make flare after inserting the flare nut onto the copper pipes. 10.3.4. (a) EVACUATION OF THE EQUIPMENT (FOR EUROPE & OCEANIA DESTINATION) WHEN INSTALLING AN AIR CONDITIONER, BE SURE TO EVACUATE THE AIR INSIDE THE INDOOR UNIT AND PIPES in the...
Page 46
(1)* *Connect the manifo ld gauge to the service port of 3-way valve. Measure the pressure. 10.3.6. CONNECT THE CABLE TO THE OUTDOOR UNIT 1. Remove the control board cover from the unit by loosening the screw. 2. Connecting cable between indoor unit and outdoor unit shall be approved polychloroprene sheathed 3 (C7BK, C9BK, C12BK, V7BK, V9BK, V12BK) or 5 (A7BK, A9BK, A12BK, W7BK, W9BK, W12BK) × 1.5 mm 2flexible cord, type designation 245 IEC57 or heavier cord. 3. Secure the cable onto the control board...
Page 47
10.3.7. PIPE INSULATION 1. Please carry out insulation at pipe connection portion as mentioned in Indoor/Outdoor Unit Installation Diagram. Please wrap the insulated piping end to prevent water from going inside the piping. 2. If drain hose or connecting piping is in the room (where dew may form), please increase the insulation by using POLY-E FOAM with thickness 6 mm or above. DISPOSAL OFOUTDOOR UNIT DRAINWATER • If a drain elbow is used, the unit should be placed on a stand which is taller than 3...
Page 48
NOTE:These equipment shall be connected to a suitable mains network with a main impedance less than the following: CS-A9BKP / CU-A9BKP5: 0.44Ω CS-C12BKP / CU-C12BKP5: 0.47Ω CS-A12BKP / CU-A12BKP5: 0.47Ω CS-V12BKP / CU-V12BKP5: 0.45Ω CS-W12BKP / CU-W12BKP5: 0.45Ω CHECK ITEMS Is there any gas leakage at flare nut connections? Has the heat insulation been carried out at flare nut connection? Is the connecting cable being fixed to terminal board firmly? Is the connecting cable being clamped firmly? Is the...
Page 49
11 2-way, 3-way Valve 2-way Valve (Liquid Side)3-way Valve (Gas Side) WorksShaft PositionShaft PositionService Port ShippingCloseCloseClose (With valve cap)(With valve cap)(With cap) EvacuationCloseCloseOpen (Installation and(Counter-Clockwise)(Clockwise)(Push-pin) Re-installation) OperationOpenOpenClose (With valve cap)(With valve cap)(With cap) Pumping downCloseOpenOpen (Transferring)(Clockwise)(Counter-Clockwise)(Connected manifo ld gauge) EvacuationOpenOpenOpen (Servicing)With vacuumpump Gas...
Page 50
11.1.1. Evacuation of Installation WHEN INSTALLING AN AIR CONDITIONER, BE SURE TO EVACUATE THE AIR INSIDE THE INDOOR UNIT AND PIPES in the following procedure. 1. Connect a charging hose with a push pin to the Low side of a charging set and the service port of a 3-way valve. • Be sure to connect the endof the charging hose with the push pin to the service port. 2. Connect the centre hose of the charging set to a vacuum pump. 3. Turn on the power switchof the vacuum pump and make sure that the needle...