Page 61
Function Automatic address resetting fortwinsystem s • • • • This clears the current twin addresses which have been set automatically , and causes automatic twin address setting to be carried out once more. Procedure:Press the ADDRESS RESET switch SW3 (push button switch) on the outdoor unit circuit board continuously until LEDs 2 to 8 on the outdoor unit circuit board are all illuminated (takes approx. 3.5 seconds). Operation:The outdoor unit will reset the addresses for the indoor units which...
Page 62
• • • • The branch pipe should be horizon tal to or perpendicular to the indoor unit. ! !! ! Installing branch pipes 17.3. Refrigerant charging • • • • For twin systems The pipe length is the total of the branch pipe (L) and the junction pipes (Ia→ tIb→ t Ic in order from the thickest diameter). At the point where the pipe length exceed s 30 m, determine the amoun t of refrigerant for the remaining liquid-side pipe diameters and pipe lengths from the following table in order to charge...
Page 63
17.4. Wiring Whenboth indoor and outdoor unit draw power (Example: 3 Phase power supply model) When only theoutdoor unit draws power 63
Page 64
18 WIRING MISTAKE PREVENTION Improved quality of installation work through adoption of an “Connection error prevention” circuitwhichpreven ts wiring mistakes Conne ction errors with the control wires and the power supply wires will not only contribute to burning-out of the control circuit board, but can also cause large-scale working losses and affect reliability. If a circuit board with a “Connection error prevention” circuit is used, the relay will not operate if the wires have been connected...
Page 65
19.1. Test operation • • • • Always be sure to use a properly-insu lated tool to operate the switch on the circuit board. (Do not use your finger or a metallic object). • • • • Never turn on the power supply until all installa tion work has been completed. • • • • Turn on the circuit breaker before test operation extends past 6 hours. (The crankcase heater will become energized, which will warm the compressor and prevent liquid compression.) • • • • For three-phase...
Page 69
20 SETTING OF SAVE ENERGY AND THERMISTOR SWITCH 20.1. Energy save setting Open the cover remote control unit and confirm the presence of the [ RP1] marking. Energy save setting method should be different for with [ RP1] marking and without [RP1] marking. 69
Page 70
21 GROUP CONTROL 1 Setting group for 1 remote control unit • • • • W hen using a remote control thermostat, the thermostat setting is used for all indoor units in the group. • • • • During group control, up to a maximum of 16 indoor units can be connected. (Do not mix heat pump units and cooling only units.) • • • • Do not mix manua l settings and automatic settings. (Manual settings take priority.) • • • • The master unit and slave units can all be centrally...