Panasonic Cs Ksxxnb4x Cz 18bt1u Technical Service Manual
Here you can view all the pages of manual Panasonic Cs Ksxxnb4x Cz 18bt1u Technical Service Manual. The Panasonic manuals for Air Conditioner are available online for free. You can easily download all the documents as PDF.
Page 41
7-3. Disassembly Procedure 7-3-1. Remove the air intake grill. (1) Slide the 2 latches each to the corresponding arrow direction. (Fig. 1 and Fig. 2) Open downward the air intake grill located on the latch side. (2) Undo the air intake grill drop preventive hook. (Fig. 3) Undo the 2 hinges for the grill and remove the air intake grill. 7-3-2. Disconnect the connectors in the control box. (1) Remove the 2 screws and remove the control box cover. (Fig. 4) (2) Disconnect the connectors CN04 (FLAP...
Page 42
NOTE 7-3-3. Remove the ceiling panel. (1) Open the clamp (4 locations) and remove the 2 lead wires from the clamps. (Fig. 6) (2) Remove the 4 screws fixing the corner cover (at 3 locations) and indicator cover (at 1 location). (Fig. 6) (3) Press the center 1 of the cover and remove the cover with the section 2 pulled down. (Fig. 7) (4) Remove the strap (3 locations) from the hook on the ceiling panel. (Fig. 8) There is no strap on the indicator cover. (5) Remove the bolt (4 locations) with a washer...
Page 43
123 7-3-4. Remove the indoor air temperature sensor. (1) Disconnect the connector CN08 (ROOM 2P) in the control box and remove the indoor air temperature sensor. (Fig. 10) 7-3-5. Remove the power box and control box. (1) Remove a screw and remove the terminal cover. (Fig. 11) (2) Remove the 2 screws and remove the power box cover. (Fig. 11) (3) Disconnect the power lines (No. 1 and No. 2) / signal line (No. 3) and ground cable from the terminals in the power box. (Fig. 12) Indoor air temperature...
Page 44
12 3 (4) Disconnect the connector CN07 (DP 2P) in the power box. (Fig. 13) Remove a screw and disconnect the ground cable. (Fig. 13) (5) Disconnect the connector CN03 (DCM 6P) in the power box. (Fig. 14) (6) Remove the 4 screws and remove the power box. (Fig. 14) (7) Disconnect the connectors CN06 (FS 3P) and CN09 (COIL-1 2P) in the control box. (Fig. 15) (8) Remove the 2 screws and remove the control box. (Fig. 15) Fig.13 Fig.14 Fig.15 Screw Screw Screw Screw Screw CN06 CN03ScrewScrew Ground...
Page 45
For the removal of the following components, perform any work after removing the indoor unit (main body) from the ceiling. Main body lower section Heat exchanger sensor Drain pump Float switch Turbo fan Fan motor Heat exchanger 1. Perform the work after draining the water to prevent the water leakage from the drain pan. • Put a bucket, etc., under the drain cap and remove the drain cap to drain the water. (Fig. 16) 2. Refer to the installation instructions for...
Page 46
7-3-7. Remove the heat exchanger sensor. (1) Remove the heat exchanger sensor from the sensor holder. (Fig. 19) 7-3-8. Remove the drain pump and float switch. (1) Remove the 2 screws (Fig. 20) (2) Loosen the clamp and disconnect the drain hose from the drain pump. (Fig. 20) (3) Remove the drain pump from the main body upper section. (Fig. 20) (4) Remove a nut and remove the float switch. (Fig. 21) Heat exchanger sensor Fig.20 Fig.21Fig.19 Holder Drain pumpScrew ClampFloat switch Nut Drain hose 46
Page 47
7-3-9. Remove the turbo fan and fan motor. (1) Remove a nut and remove the turbo fan. (Fig. 22) (2) Remove the 2 screws and 3 nuts, and remove the fan motor. (Fig. 23) 7-3-10. Remove the heat exchanger. (1) Remove the 3 screws. (Fig. 24) (2) Remove the 3 screws. (Fig. 25) (3) Remove the heat exchanger from the main body upper section with the heat exchanger lifted.Fig.22 Fig.23 Fig.24 Fig.25 Turbo fan NutScrew Nut Fan motor Screw Screw Heat exchanger Screw Main body upper section 47
Page 48
8. FUNCTIONS 8-1. Operation Functions Emergency operation SENSOR DRY During DRY operation, the system adjusts the room temperature and fan speed according to the conditions in the room, in order to maintain a comfortable room environment. SENSOR DRY operation DRY operation is as shown in the figure below. PAM- control In order to further improve inverter performance, control is switched between PWM control at low operation speeds, and PAM control at high operation speeds, making the...
Page 49
HIGH POWERNIGHT SETBACK Lamp colors Timer backup This function acts to raise the power but keeps the AC system in the same operating mode. This function is set with the HIGH POWER button on the remote controller. (It can be set regardless of the temperature and fan speed settings.) HIGH POWER operation from remote controller The unit operates at maximum output for 30 minutes, regardless of the desired temperature. The fan speed is 1 step above "High." OPERATION lamp When HIGH POWER...
Page 50
a. Area: Automatic capacity control b. When the temperature drops below Point A, the operation frequency is reduced by a certain proportion. c. Area: Frequency increase is prohibited. d. When the temperature reaches Point C or above, freezing prevention is ended and control is the same as in the a area. * When the temperature drops to below 36°F(2°C) (continuously for 2 minutes or longer), the compressor stops. Once the freeze condition is detected, the air conditioner will work less than the...