Home > Panasonic > Air Conditioner > Panasonic Cs Ksxxnb4x Cz 18bt1u Technical Service Manual

Panasonic Cs Ksxxnb4x Cz 18bt1u Technical Service Manual

    Download as PDF Print this page Share this page

    Have a look at the manual Panasonic Cs Ksxxnb4x Cz 18bt1u Technical Service Manual online for free. It’s possible to download the document as PDF or print. UserManuals.tech offer 10737 Panasonic manuals and user’s guides for free. Share the user manual or guide on Facebook, Twitter or Google+.

    							7-3.  Disassembly Procedure
    7-3-1.  Remove the air intake grill.
    (1)  Slide the 2 latches each to the corresponding arrow direction. (Fig. 1 and Fig. 2)
      Open downward the air intake grill located on the latch side.
    (2)  Undo the air intake grill drop preventive hook. (Fig. 3)
      Undo the 2 hinges for the grill and remove the air intake grill.
    7-3-2.  Disconnect the connectors in the control box.
    (1)  Remove the 2 screws and remove the control box cover. (Fig. 4)
    (2)  Disconnect the connectors CN04 (FLAP 5P), CN12 (RC 4P) and CN13 (IND 7P). (Fig. 5)
    Latch
    LatchHookHinge
    Air intake grill
    Screw Control box coverCN13CN04
    CN12
    Fig.1
    Fig.4 Fig.5Fig.2 Fig.3
    Hinge
    Control PCboard
    To avoid electrical shock hazard, be sure to disconnect power before
    attempting to disassemble the unit.
    When a footstool, etc. is used for disassembling the indoor unit, 
    be careful not to fall down. If you fall down, you might be injured seriously.
    WARNING
    41 
    						
    							NOTE
    7-3-3. Remove the ceiling panel.
    (1)  Open the clamp (4 locations) and remove the 2 lead wires from the clamps. (Fig. 6)
    (2)  Remove the 4 screws fixing the corner cover (at 3 locations) and indicator cover (at 1 location). (Fig. 6)
    (3)  Press the center 1 of the cover and remove the cover with the section 2 pulled down. (Fig. 7)
    (4)  Remove the strap (3 locations) from the hook on the ceiling panel. (Fig. 8)
    There is no strap on the indicator cover.
    (5)  Remove the bolt (4 locations) with a washer and remove the ceiling panel. (Fig. 9)
    Screw
    Bolt
    Bolt Screw
    Indicator
    coverCorner cover
    Corner cover Corner cover Clamp
     ClampPull down 
    section 2.  Lead wire
    Cover
    Center 1Fig.6 Fig.7
    Fig.8 Fig.9
    Remove the strap 
    from the hook. Strap
    42 
    						
    							123
    7-3-4.  Remove the indoor air temperature sensor.
    (1)  Disconnect the connector CN08 (ROOM 2P) in the control box and remove the indoor air temperature 
    sensor. (Fig. 10)
    7-3-5. Remove the power box and control box.
    (1)  Remove a screw and remove the terminal cover. (Fig. 11)
    (2)  Remove the 2 screws and remove the power box cover. (Fig. 11)
    (3)  Disconnect the power lines (No. 1 and No. 2) / signal line (No. 3) and ground cable from the terminals in 
    the power box. (Fig. 12)
    Indoor air temperature sensor
    CN08
    Terminal
    Fig.10
    Fig.11
    Fig.12
    Ground cable Terminal cover
    Screw Screw
    Power box cover
    Power lines / Signal line
    43 
    						
    							12 3
    (4)  Disconnect the connector CN07 (DP 2P) in the power box. (Fig. 13)
      Remove a screw and disconnect the ground cable. (Fig. 13)
    (5)  Disconnect the connector CN03 (DCM 6P) in the power box. (Fig. 14)
    (6)  Remove the 4 screws and remove the power box. (Fig. 14)
    (7)  Disconnect the connectors CN06 (FS 3P) and CN09 (COIL-1 2P) in the control box. (Fig. 15)
    (8)  Remove the 2 screws and remove the control box. (Fig. 15)
    Fig.13
    Fig.14
    Fig.15
    Screw
    Screw
    Screw
    Screw
    Screw
    CN06 CN03ScrewScrew Ground cable
    CN07
    CN09
    44 
    						
    							For the removal of the following components, perform any work after removing the indoor 
    unit (main body) from the ceiling.
        Main body lower section      Heat exchanger sensor      Drain pump
        Float switch      Turbo fan      Fan motor
        Heat exchanger 
    1.  Perform the work after draining the water to prevent the water leakage from the drain pan.
     
    • Put a bucket, etc., under the drain cap and remove the drain cap to drain the water. 
        (Fig. 16)
    2.  Refer to the installation instructions for recovery of refrigerant or removal of the power
      cable or tubing.
    7-3-6.  Remove the main body lower section.
    (1)  Remove the 4 screws. (Fig. 16)
    (2)  Remove the 2 screws. (Fig. 17)
    (3)  Disconnect the connector CN03 (DCM 6P) in the power box. (Fig. 18)
    (4)  Lift the main body lower section and remove it from the main body upper section.
    Screw
    Fig.16
    Fig.18 Fig.17
    Drain cap
    Main body lower section Main body lower section
    Screw Screw
    Main body lower section
    Main body 
    upper section
    Screw
    CN03 Screw
    NOTE
    45 
    						
    							7-3-7. Remove the heat exchanger sensor.
    (1)  Remove the heat exchanger sensor from the sensor holder. (Fig. 19) 
    7-3-8. Remove the drain pump and float switch.
    (1)  Remove the 2 screws (Fig. 20)
    (2)  Loosen the clamp and disconnect the drain hose from the drain pump. (Fig. 20)
    (3)  Remove the drain pump from the main body upper section. (Fig. 20)
    (4)  Remove a nut and remove the float switch. (Fig. 21)
    Heat exchanger sensor
    Fig.20 Fig.21Fig.19
    Holder
    Drain pumpScrew
    ClampFloat switch
    Nut
    Drain hose
    46 
    						
    							7-3-9. Remove the turbo fan and fan motor.
    (1)  Remove a nut and remove the turbo fan. (Fig. 22)
    (2)  Remove the 2 screws and 3 nuts, and remove the fan motor. (Fig. 23) 
    7-3-10. Remove the heat exchanger.
    (1)  Remove the 3 screws. (Fig. 24)
    (2)  Remove the 3 screws. (Fig. 25)
    (3)  Remove the heat exchanger from the main body upper section with the heat exchanger lifted.Fig.22 Fig.23
    Fig.24 Fig.25
    Turbo fan
    NutScrew Nut
    Fan motor
    Screw
    Screw Heat exchanger
    Screw Main body 
    upper section
    47 
    						
    							8.  FUNCTIONS
    8-1.  Operation Functions
    Emergency operation SENSOR DRY
      During DRY operation, the system adjusts the room 
    temperature and fan speed according to the conditions in the 
    room, in order to maintain a comfortable room environment.
    SENSOR DRY operation
        DRY operation is as shown in the figure below.
    PAM-    control
       In order to further improve inverter performance, control is 
    switched between PWM control at low operation speeds, and 
    PAM control at high operation speeds, making the most 
    effective use of power.   The compressor operation frequency varies.
      The indoor fan operates with 1/f fluctuation.
      The compressor operates at a low operating frequency.
      The indoor fan operates with 1/f fluctuation.
       Monitoring operation takes place when the room temperature 
    is below 59°F
    (15°C), or more than 5°F(3°C) below the set 
    temperature.
       When the monitoring range is entered, the compressor stops, 
    and the indoor fan operates with 1/f fluctuation.
    DRY A
    DRY B
    Monitor
    Conditions are monitored at all 
    times when the room temperature 
    is below 59°F(15°C). Load
    COOL zone
    A zone
    B zone
    Emergency operation is available when the remote 
    controller malfunctions, has been lost, or otherwise 
    cannot be used.
       The set temperature is 4°F(2°C) below the detected room 
    temperature in the case of cooling operation.
    (GREEN) (Lamp Off)COOL STOP To operate the system, press the OPERATION button, 
    which is also used as the receiver, below the unit display. 
    Each time this button is pressed, the OPERATION lamp 
    changes color to indicate the type of operation. Select the 
    desired type of operation.
    The Sensor Dry operation during the Low Ambient Cooling 
    Mode (outside air temperature:59°F(15°C) or lower) is as 
    follows. 
    The compressor operates a cycle of 3 minutes ON and 6 
    minutes OFF repeatedly.
    NOTE
    DRY A
    DRY B and (CLxx models only)
    48 
    						
    							HIGH POWERNIGHT SETBACK
    Lamp colors
    Timer backup
    This function acts to raise the power but keeps the AC system in 
    the same operating mode.
    This function is set with the HIGH POWER button on the remote 
    controller.
    (It can be set regardless of the temperature and fan speed 
    settings.)
     HIGH POWER operation from remote controller
      The unit operates at maximum output for 30 minutes, 
    regardless of the desired temperature.
      The fan speed is 1 step above "High."
    OPERATION lamp  When HIGH POWER operation ends, the unit operates at low 
    Hz for 5 minutes, regardless of the thermostat OFF conditions.
      When in DRY mode, operation is in the cooling zone.
       Operation stops if there are no operator controls for 25 hours or 
    longer after unit operation switched from OFF to ON by use of 
    ON timer operation.
    Frequency
    MAX
    0
    Start EndTime
    30 min. 5 min.
    Setting
    temperature
    Press the NIGHT
    SETBACK button
       When NIGHT SETBACK operation is set, the temperature and 
    fan speed settings will be adjusted automatically to allow 
    comfortable sleep.
       When NIGHT SETBACK operation is set, "     mark" appears on 
    the remote controller. The main unit display lamp also becomes 
    dimmer.
      COOL and DRY modes
    When the night setback mode is selected, the air conditioner 
    automatically raises the temperature setting 2°F(1°C) when 30 
    minutes have passed after the selection was made, and then 
    another 2°F(1°C) after another 30 minutes have passed, 
    regardless of the indoor temperature when night setback was 
    selected. This enables you to save energy without sacrificing 
    comfort. This function is convenient when gentle cooling is 
    needed.
    OPERATION lamp Green
    TIMER lamp Green
    HIGH POWER lamp Green DRY operation  Orange
    COOL operation  Green
    FAN operation  Green
    NOTE
    30 min. 30 min.
    Time
    2°F(1°C)
    2°F(1°C)
    49 
    						
    							a.  Area: Automatic capacity control
    b.  When the temperature drops below Point A, the operation 
    frequency is reduced by a certain proportion.
    c.  Area: Frequency increase is prohibited.
    d.  When the temperature reaches Point C or above, freezing 
    prevention is ended and control is the same as in the a area.
    *  When the temperature drops to below 36°F(2°C) 
    (continuously for 2 minutes or longer), the compressor stops.
    Once the freeze condition is detected, the air conditioner will 
    work less than the maximum frequency until it is turned off.
    The Freeze Prevention Control during the Low Ambient Cooling 
    Mode (outside air temperature:59°F(15°C) or lower) is as follows.The compressor stops when the temperature of indoor heat 
    exchanger becomes less than 36°F(2°C).
    The compressor restarts when the temperature of indoor heat 
    exchanger becomes 46°F(8°C) or higher.
    NOTE
    Compressor discharge temperature controlFreeze prevention
    During COOL or DRY operation, freezing is detected and 
    operation is stopped when the temperature of the indoor heat 
    exchanger matches the conditions below.
    1.  Freeze-prevention operation is engaged when the 
    temperature of the indoor heat exchanger is below 43°F(6°C).
    2.  Restart after freeze-prevention operation occurs when the 
    temperature of the indoor heat exchanger reaches 46°F(8°C) 
    or above.
    A
    *
    BC
    abcd
    Indoor heat exchanger
    temperature °F(°C)
    36
    (2)43
    (6)46
    (8)
    This function controls the operation frequency to prevent the 
    compressor discharge temperature from rising more than a 
    specified temperature.
    a.  Area: Automatic capacity control.
    b.  When the temperature rises above Point A, the operation 
    frequency is reduced at a specified rate.
    c.  Area: Further frequency increase is prohibited.
    d.  When the temperature falls below Point B, prevention of a rise 
    in frequency is released and the air conditioner operates as in 
    a area.
    *  The compressor will stop if the temperature of the compressor 
    discharge exceeds 248°F(120°C) due to shortage of gas or 
    other reason.
    Approx.
    214
    (101)A
    B
    abc d
    Compressor discharge temperature °F(°C)
    Approx.
    201
    (94)
    8-2.  Protective Functions
    This function prevents the circuit breaker or fuse from operating
     to open the circuit. This function works when electrical current 
    has increased due to an increase in the cooling load, 
    or to a decrease in the power supply voltage. In these cases, 
    operation frequency is reduced or operation is interrupted auto-
    matically to control the electrical current for operation.
    When the cause of the increase in electrical current is rectified, 
    the system will resume operation in the original mode.
    CT (Peak current cut-off control)
    (CLxx models only)
    Cooling   Dry 
    Peak current cut-off trips 22.5
    Hz down 14.0
    (A) 
    Cooling   Dry 
    Peak current cut-off trips 17.5
    Hz down 11.0
    (A) 
    50 
    						
    All Panasonic manuals Comments (0)

    Related Manuals for Panasonic Cs Ksxxnb4x Cz 18bt1u Technical Service Manual