Panasonic Cs C9gkv Cs C12gkv Cu C9gkv Cu C12gkv Repair Manual
Have a look at the manual Panasonic Cs C9gkv Cs C12gkv Cu C9gkv Cu C12gkv Repair Manual online for free. It’s possible to download the document as PDF or print. UserManuals.tech offer 10737 Panasonic manuals and user’s guides for free. Share the user manual or guide on Facebook, Twitter or Google+.
11 5 Dimensions 5.1. Indoor Unit & Remote Control 5.1.1. CS-C9GK CS-C12GK
12 5.2. Outdoor Unit 5.2.1. CU-C9GK 5.2.2. CU-C12GK
15 8 Wiring Connection Diagram 8.1. CS-C9GK CU-C9GK / CS-C12GK CU-C12GK Resistance of Indoor Fan Motor Windings Note: Resistance at 25qC of ambient temperature. Resistance of Outdoor Fan Motor Windings Note: Resistance at 25qC of ambient temperature.Resistance of Compressor Windings Note: Resistance at 20qC of ambient temperature. Note: Resistance at 20qC of ambient temperature. MODEL CU-C9GK CU-C12GK CONNECTION CWA921181J BLUE-YELLOW 390.0 : YELLOW-RED 394.0 : MODEL CU-C9GK CU-C12GK CONNECTION CWA951395J CWA951329J BLUE-YELLOW 265 :258.3: YELLOW-RED 168 :245.9:MODEL CU-C9GK CONNECTION 2R13C236BSC C - R 3.298 : C - S 5.500 : MODEL CU-C12GK CONNECTION 2P19S236A1L C - R 2.237 : C - S 2.710 :
17 10 Printed Circuit Board 10.1. Indoor Unit TOP VIEW
20 11 Installation Instruction 11.1. Select The Best Location There should not be any heat source or steam near the unit. There should not be any obstacles blocking the air circulation. A place where air circulation in the room is good. A place where drainage can be easily done. A place where noise prevention is taken into consideration. Do not install the unit near the door way. Ensure the spaces indicated by arrows from the wall, ceiling, fence or other obstacles. Recommended installation height for indoor unit shall be at least 2.5 m. If an awning is built over the unit to prevent direct sunlight or rain, be careful that heat radiation from the condenser is not obstructed. There should not be any animal or plant which could be affected by hot air discharged. Keep the spaces indicated by arrows from wall, ceiling, fence or other obstacles. Do not place any obstacles which may cause a short circuit of the discharged air. If piping length is over the rated length, additional refrigerant should be added as shown in the table. This illustration is for explanation purposes only. The indoor unit will actually face a different way. Indoor Unit Outdoor Unit Piping size Rated Length (m)Max Elevation (m)Max. Piping Length (m)Additional Refrigerant (g/m) Model Gas Liquid C9GK 3/8” 1/4” 7.5 5 10 10 C12GK 1/2” 1/4” 7.5 5 15 10Indoor/Outdoor Unit Installation Diagram