11 5 Dimensions 5.1. Indoor Unit & Remote Control 5.1.1. CS-C9GK CS-C12GK
12 5.2. Outdoor Unit 5.2.1. CU-C9GK 5.2.2. CU-C12GK
15 8 Wiring Connection Diagram 8.1. CS-C9GK CU-C9GK / CS-C12GK CU-C12GK Resistance of Indoor Fan Motor Windings Note: Resistance at 25°C of ambient temperature. Resistance of Outdoor Fan Motor Windings Note: Resistance at 25°C of ambient temperature.Resistance of Compressor Windings Note: Resistance at 20°C of ambient temperature. Note: Resistance at 20°C of ambient temperature. MODEL CU-C9GK CU-C12GK CONNECTION CWA921181 CWA921324 BLUE-YELLOW 390.0 Ω371.0 Ω YELLOW-RED 394.0 Ω385.6 Ω MODEL CU-C9GK CU-C12GK CONNECTION CWA951395J CWA951329J BLUE-YELLOW 265 Ω258.3 Ω YELLOW-RED 168 Ω245.9 ΩMODEL CU-C9GK CONNECTION 2R13C236BSC C - R 3.298 Ω C - S 5.500 Ω MODEL CU-C12GK CONNECTION 2P19S236A1L C - R 2.237 Ω C - S 2.710 Ω
17 10 Printed Circuit Board 10.1. Indoor Unit TOP VIEW
20 11 Installation Instruction 11.1. Select The Best Location • There should not be any heat source or steam near the unit. • There should not be any obstacles blocking the air circulation. • A place where air circulation in the room is good. • A place where drainage can be easily done. • A place where noise prevention is taken into consideration. • Do not install the unit near the door way. • Ensure the spaces indicated by arrows from the wall, ceiling, fence or other obstacles. • Recommended installation height for indoor unit shall be at least 2.5 m. • If an awning is built over the unit to prevent direct sunlight or rain, be careful that heat radiation from the condenser is not obstructed. • There should not be any animal or plant which could be affected by hot air discharged. • Keep the spaces indicated by arrows from wall, ceiling, fence or other obstacles. • Do not place any obstacles which may cause a short circuit of the discharged air. • If piping length is over the rated length, additional refrigerant should be added as shown in the table. • This illustration is for explanation purposes only. The indoor unit will actually face a different way. Indoor Unit Outdoor Unit Piping size Rated Length (m)Max Elevation (m)Max. Piping Length (m)Additional Refrigerant (g/m) Model Gas Liquid C7GK/ C9GK3/8” 1/4” 7.5 5 10 10 A9GK 3/8” 1/4” 7.5 5 10 20 RS-C7GK/ C9GK3/8” 1/4” 7.5 5 10 10 C12GK 1/2” 1/4” 7.5 5 15 10 A12GK 1/2” 1/4” 7.5 5 15 20 RS- C12GK1/2” 1/4” 7.5 5 15 10Indoor/Outdoor Unit Installation Diagram