Panasonic Cs C9gkq Cs C12gkq Cu C9gkq Cu C12gkq Repair Manual
Here you can view all the pages of manual Panasonic Cs C9gkq Cs C12gkq Cu C9gkq Cu C12gkq Repair Manual. The Panasonic manuals for Air Conditioner are available online for free. You can easily download all the documents as PDF.
Page 31
31 12.4.7. Dew Prevention control • To prevent dew formation at indoor unit discharge area. • This control will be activated if:- - Cooling mode or Quiet mode. - Remote Control setting temperature is less than 25°C. - Fan speed is at CLo or QLo. - Room temperature is constant (±1°C) for 30 minutes. - Compressor is continuously running. • Fan speed and angle of horizontal louver (vertical airflow angle) will be adjusted accordingly in this control. - Fan speed will be increased slowly if the unit is in...
Page 32
32 12.5. Indoor Fan Speed Control • Indoor Fan Speed can be set using remote control. 12.5.1. Fan Speed Rotation Chart 12.5.2. Automatic Fan Speed Control • When set to Auto Fan Speed, the fan speed is adjusted between maximum and minimum setting as shown in the table. - Fan speed rotates in the range of Hi and Me. - Deodorizing Control will be activated. Speed Fan Speed (rpm) CS-C9GKQ CS-C12GKQ S Hi 1300 1320 Hi 1210 1270 Me 1000 1060 H Lo 790 910 C Lo 730 800 Lo- 680 750 S Lo 630 700 Q H i 111 0 11 7...
Page 33
33 • Auto Fan Speed during cooling operation: 1. Indoor fan will rotate alternately between off and on as shown in below diagram. 2. At the beginning of each compressor start operation, indoor fan will increase fan speed gradually for deodorizing purpose. 3. For the first time the compressor operate, indoor fan will be switched to Hi fan speed from Lo- after 70 seconds from the start of compressor. This cause the room temperature to achieve the setting temperature quickly. 4. During compressor stop,...
Page 34
34 12.7. Vertical Airflow Direction Control 12.7.1. Auto Control • When the vertical airflow direction is set to Auto using the remote control, the louver swings up and down as shown in the diagram. • When stop operation using the remote control, the discharge vent is reset, and stop at the closing position. • During Cooling operation or Soft Dry operation, indoor fan motor may stop to rotate at certain periods. At that condition, the louver will stop swinging and rest at the upper limit. 12.7.2. Manual...
Page 35
35 12.10. Quiet Operation (For Cooling Operation or cooling region of Soft Dry Operation) •To provide quiet cooling operation condition compare to normal operation. • Once the Quiet Mode is set at the remote control, the Quiet Mode LED illuminated. The sound level will reduce around 2 dB(A) for Lo fan speed or 3 dB(A) for Hi/Me fan speed against the present operation sound level. • Dew formation become severe at Quiet Lo cool, therefore Quiet Lo cool is operated only 1hr 30 min (1hr QLo, 30 min QLo + 50...
Page 36
36 12.11. Timer Control 12.11.1. ON Timer • When the ON Timer is set by using the remote control, the unit will start to operate slightly before the set time, so that the room will reach nearly to the set temperature by the set time. • For Cooling and Soft Dry operation, the operation will start 15 minutes before the set time. • For Automatic operation, the indoor fan will operate at SLo speed for 20 seconds, 15 minutes before the set time to detect the intake air temperature to determine the operation...
Page 37
37 12.14. Patrol Operation 1. Purpose To monitor air dirtiness level by using gas sensor and activates e-ion operation whenever air is dirty. 2. Control Condition a. Patrol operation start condition • When the unit operation is started with “OFF/ON” button. • When the unit stops, “Patrol” button is pressed, Patrol individual operation will start. • During cooling only operation, “Patrol” button is pressed. b. Patrol operation stop condition When any of the following condition is fulfilled: • When...
Page 38
38 3. Control Content a. Gas Sensor Control • First 2 minutes from Patrol function activates is stabilization time, during stabilization time, no air dirtiness level is monitored. The Air Dirtiness level is set to level 2. • After that, gas sensor starts to record the resistance value at fixed interval. Higher resistance value indicates cleaner air. • The air dirtiness level is monitored by comparing the current resistance value with maximum resistance value from time to time to get the Air Dirtiness...
Page 39
39 c. Indoor Fan Control • During any operation mode combines with Patrol operation, fan speed follows respective operation mode. • During Patrol individual operation if e-ion starts, only Auto Fan Speed and no Powerful operation is allowed. Even if “Fan Speed” button is pressed, no signal is sent to air conditioner, and no change on LCD display. • During Patrol individual operation if e-ion stops, Indoor Fan stop operation. d. Airflow direction (Horizontal, Vertical) Control • During any operation mode...
Page 40
40 12.15. e-ion Operation 1. Purpose This operation provides clean air by producing negative ions to attract dust captured at the positively charged e-ion filters. 2. Control Condition a. e-ion operation start condition • During unit running at any operation mode, if “e-ion” button is pressed, combination operation (operation mode + e-ion operation) starts. • During unit is OFF, if “e-ion” button is pressed, e-ion individual operation starts. b. e-ion operation stop condition • When “OFF/ON” button is...