21 10 Installation Instruction 10.1. Select The Best Location • There should not be any heat source or steam near the unit. • There should not be any obstacles blocking the air circula- tion. • A place where air circulation in the room is good. • A place where drainage can be easily done. • A place where noise prevention is taken into consideration. • Do not install the unit near the door way. • Ensure the spaces indicated by arrows from the wall, ceiling, fence or other obstacles. • Recommended...
Page 22
22 10.2. Indoor Unit 10.2.1. How To Fix Installation Plate The mounting wall is strong and solid enough to prevent it from the vibration. The centre of installation plate should be at more than 450 mm at right and left of the wall. The distance from installation plate edge to ceiling should more than 67 mm. From installation plate left edge to units left side is 74 mm. From installation plate right edge to units right is 94 mm. 1. Mount the installation plate on the wall with 5 screws or more. (If...
Page 23
23 For the embedded piping Pull out the piping and drain hose How to keep the coverInsert the connecting cable Install the Indoor unit Secure the Indoor Unit (This can be used for left rear piping & left bottom piping also.)
Page 24
24 • How to pull the piping and drain hose out, in case of the embedded piping. • In case of left piping how to insert the connecting cable and drain hose. 10.2.4. Connect The Cable To The Indoor Unit 1. The inside and outside connecting cable can be con- nected without removing the front grille. 2. Connecting cable between indoor unit and outdoor unit shall be approved polychloroprene sheathed 3 (C7EK, C9EK, C12EK, RS-C7EK, RS-C9EK, RS-C12EK) or 5 (A9EK, A12EK) × 1.5mm 2 flexible cord, type designation...
Page 25
25 torque as stated in the table. Connecting The Piping To Outdoor Unit Decide piping length and then cut by using pipe cutter. Remove burrs from cut edge. Make flare after inserting the flare nut (locate at valve) onto the copper pipe. Align center of piping tovalves and then tighten with torque wrench to the specified torque as stated in the table. CUTTING AND FLARING THE PIPING 1. Please cut using pipe cutter and then remove the burrs. 2. Remove the burrs by using reamer. If burrs is not removed, gas...
Page 26
26 4(A). Checking gas leakage for the left piping 10.3.4. Connect The Cable To The Outdoor Unit 1. Remove the control board cover from the unit by loosen- ing the screw. 2. Connecting cable between indoor unit and outdoor unit shall be approved polychloroprene sheathed 3 (C7EK, C9EK, C12EK, RS-C7EK, RS-C9EK, RS-C12EK) or 5 (A9EK, A12EK) × 1.5 mm 2 flexible cord, type designation 245 IEC 57 or heavier cord. 3. Secure the cable onto the control board with the holder (clamper). 4. Attach the control board...
Page 27
27 11 Operation and Control 11.1. Heating Operation • Heating operation can be set using remote control. • This operation is applied to warm the room temperature reaches the setting temperature set on the remote control. • The remote control setting temperature, which takes the reading of intake air temperature sensor, can be adjusted from 16°C to 30°C. • During heating operation, the compressor will stop running and restart as shown in below figure. 11.1.1. Heating Operation Time Diagram
Page 28
28 11.2. Cooling Operation • Cooling operation can be set using remote control. • This operation is applied to cool down the room temperature reaches the setting temperature set on the remote control. • The remote control setting temperature, which takes the reading of intake air temperature sensor, can be adjusted from 16°C to 30°C. • During cooling operation, the compressor will stop running and restart as shown in below figure. 11.2.1. Cooling Operation Time Diagram
Page 29
29 11.3. Soft Dry Operation • Soft Dry operation can be set using remote control. • Soft Dry operation is applied to dehumidify and to perform a gentle cooling to the room. • This operation starts when the intake air temperature sensor reaches the setting temperature on the remote control. • When operation begins, Soft Dry will be switched “ON” for a maximum 10 minutes, then Soft Dry operation will be turned “OFF” for a minimum 6 minutes. After that, the Soft Dry operation will be “ON” and “OFF” based on...
Page 30
30 11.4. Automatic Operation • Automatic operation can be set using remote control. • This operation starts to operate with indoor fan at SLo speed for 25 seconds to judge the intake air temperature. • After judged the temperature, the operation mode is determined by referring to the below standard. • Then, the unit start to operate at determined operation mode, until it is switched off using remote control, with the setting temper- ature as shown in below table. • Operation mode will be determine again...