Page 61
Fig. 4 − To remove the electronic controller. − Release CN-FM connectors. (Fig. 4) − Release CN-Sonic connector. (Fig. 4) − Release CN-FB connector. (Fig. 4) − Release CN-ION connector. (Fig. 4) − Release CN-TH connector. (Fig. 4) − Release CN-STM connector. (Fig. 4) − Release CN-REC/DISP connector. (Fig. 4) • Remove Control Board Cover Fig. 6 − Remove the screw on the left of the unit. (Fig. 6) − Pull the hook to the left and lift up the evaporator. (Fig. 6) − Pull down the Discharge Grille...
Page 62
− Release the generator complete wire (green and red). (Fig. 8) − Remove 2 screws on the right and 1 screw at the left side of the control board. (Fig. 7) − Press down the hook on the left side of control board. (Fig. 7) − Then pull out the Control Board Complete from the unit. (Fig. 7) Fig. 9 − Remove the cross flowfan bushing from the chassis. (Fig. 9) − Loosen the fan boss screw at the cross flow fan. (Fig. 9) Fig. 10 − Push up the evaporator andremove crossflow fan by pulling both cross flow...
Page 63
• When the batteries are inserted for the first time or the batteries are replaced, you may notice the indications at remote control’s display screen blink continuously and not functionable. If this condition happens, try to reset the remote control by pushing the reset terminal with a pointing device. • You may also do the reset to erase the setting at remote control and restore back the default setting. − Long “beep”: Turn OFF remote control signal receiving sound. • After “Auto OFF/ON Button” is...
Page 64
In order to diagnose malfunctions, make sure that there are no electrical problems before inspecting the refrigeration cycle. Such problems include insufficient insulation, problem with the power source, malfunction of a compressor and a fan. The normal outlet air temperature and pressure of the refrigeration cycle depends on various conditions, the standard values for them are shown in the table to the right. 13 Troubleshooting Guide 13.1. Refrigeration Cycle System 64 CS-A9DKH CU-A9DKH / CS-A12D KH...
Page 65
13.2. Relationship Between The Condition Of The Air Conditioner And Pressure And Electric Current Cooling ModeHeating Mode Condition of the air conditonerLow PressureHigh PressureElectric current during operationLow PressureHigh PressureElectric current during operation Insufficient refrigerant (gas leakage) Clogged capillary tube or Strainer Short circuit in the indoor unit Heat radiation deficiency of the outdoor unit Inefficient compression • Carry out the measurements of pressure, electric current,...
Page 66
14 Technical Data 14.1. Thermostat Characteristics 14.1.1. CS-A9DKH CS-A12DKH 66 CS-A9DKH CU-A9DKH / CS-A12D KH CU-A12D KH /
Page 67
14.2. Operation Characteristics 14.2.1. CS-A9DKH CU-A9DKH 67 CS-A9DKH CU-A9DKH / CS-A12D KH CU-A12D KH /
Page 69
15 Exploded View (Indoor Unit) 15.1. CS-A9DKH CS-A12DKH Note: The above exploded view is for the purpose of parts disassembly and replacement. The non-numbered parts are not kept as standard service parts. 69 CS-A9DKH CU-A9DKH / CS-A12D KH CU-A12D KH /
Page 70
16 Replacement Parts List (Indoor Unit) REF. NO.PART NAME & DESCRIPTIONQTY.CS-A9DKHCS-A12DKHREMARKS1CHASSY COMPLETE1CWD50C1377←2FAN MOTOR1CWA921181←03CROSS FLOW FAN COMPLETE1CWH02C1031←4BEARING ASS’Y1CWH64K007←5SCREW - CROSS FLOW FAN1CWH4580304←6EVAPORATOR1CWB30C1687CWB30C16017FLARE NUT1CWT25078(1/4”)←8FLARE NUT1CWT25005 (3/8”)CWT25007 (1/2”)9INTAKE AIR SENSOR HOLDER1CWH32143←10DISCHARGE GRILLE COMPLETE1CWE20C2316←11VERTICAL VANE9CWE241150←12CONNECTING BAR1CWE261066←13CONNECTING BAR1CWE261070←14AIR...