Page 31
(Heating Operation condition) • When the piping air temperature reaches 38°C, the louver is changed from upper to lower limit. When the piping air temperature falls to 35°C, the louver is changed from lower to upper limit. Cooling and Soft Dry Operation (Cooling and Soft Dry Operation condition)Heating Operation Heating Operation 8.8.2. Manual Control • When the vertical airflow direction is set to Manual using the remote control, the automatic airflow is released and the airflow direction louver move...
Page 32
• Vertical Airflow Direction:- − In “Manual” setting, the vane will automatically shift down 5° lower than previous setting. − In “Auto” setting, the vane will automatically shift between upper and lower limit depending on the intake air temperature as Heating Mode, Airflow Direction Auto-Control. However the upperand lower limit will be shifted 5° downward. • Powerful operation stops when:- − Powerful operation has operate for 15 minutes. − Powerful button is pressed again. − Quiet button is...
Page 33
8.11. Quiet Operation • The Quiet operation is to provide quiet cooling/heating operation condition compare to normal operation. (Cooling and Soft Dry Operation condition) • Once the Quiet Mode is set at the remote control, Quiet Mode LED illuminates. The sound level will reduce either around 2 dB(A) for Lo fan speed or 3 dB(A) for Hi/Me fan speed against the present sound level operation. • Dew formation become severe at Quiet Lo cool, therefore Quiet Locool is operated only 1hr 30min (1hr QLo, 30...
Page 34
(Heating Operation condition) • When the Quiet Mode is set at the remote control, Quiet Mode LED illuminates. The sound level will reduce either around 2 dB (Lo) or 3 dB (Hi, Me), against the present sound level operation. • Quiet setting of fan speed rpm refer to Indoor Fan Speed Control. • Manual Fan Speed:- − Rpm control during Lo, Me & Hi Cool • Auto Fan Speed:- − Rpm control depends on the piping air temperature sensor of Indoor heat exchanger • Quiet operation stops when:- − Quiet button is...
Page 35
8.12. Ionizer Operation • The Ionizer operation is to provide fresh air effect to user by producing minus ion in discharge air. 8.12.1. Operation Control 1. Ionizer individual operation a. When air-conditioner unit is at “OFF” condition (standby) and ION operation button at the remote control is pressed, the Ionizer and indoor fan operations will turn on. Only ION LED will illuminates. Power LED maintain off. (1→2) b. Ionizer individual operation can be turned off by pressing the ION button again....
Page 36
8.12.2. Error Detection Control • The error detection control is to inform user that erroroccurs at ionizer system and repairing job will be needed. • There are two types of error detection control: a. When Ionizer is ON − If ionizer feedback = Lo for 24 times within 11hr 30min, ION LED blinks continuously. b. When ionizer is OFF − If ionizer feedback = Hi,ION LED blinks continuously. • During ionizer at breakdown condition, if ionizer feedback voltage = Lo (become normal), ION LED will stop...