Panasonic Cs A9dkh Cu A9dkh Cs A12dkh Cu A12dkh Repair Manual
Here you can view all the pages of manual Panasonic Cs A9dkh Cu A9dkh Cs A12dkh Cu A12dkh Repair Manual. The Panasonic manuals for Air Conditioner are available online for free. You can easily download all the documents as PDF.
Page 21
• The operation mode judging temperature and standard setting temperature canbe increased by 2°C permanently, by open the circuit of JX1 at indoor electronic controller. 8.5. Operation Control 8.5.1. Restart Control (Time Delay Safety Control) • When the thermo-off temperature (temperature which compressor stops to operate) is reached during:- − Cooling/Heating operation - the compressor stops for 3 minutes (minimum) before resume operation. − Soft Dry operation - the compressor stops for 6 minutes...
Page 22
(For 8.5.3. to 8.5.7. information applies only to Cooling and Soft Dry Operation) 8.5.3. 7 Minutes Time Save Control • The compressor will startautomatically if it has stopped for 7 minutes and the intake air temperature falls between the compressor ON temperature (A) and compressor OFF temperature (B) during the period. • This phenomenon is to reduce thebuilt up humidity inside a room. 8.5.4. 60 Seconds Forced Operation • Once the air conditioner is turned on, the compressor will not stop within 60...
Page 23
(For 8.5.8. to 8.5.14. information applies only to Heating Operation) 8.5.7. Anti-Dew Formation Control • Purpose is to prevent dew formation on indoor unit air discharge area. • When room temperature is constant (±1°C) the following conditions occur for 30 minutes continuously, anti-dew formation will activate: − Remote Control setting temperature is less than 25°C. − Compressor is on. − Cooling operation mode. − Indoor Fan motor operate at Low fan speed (CLo, Lo- or QLo). • This control is...
Page 24
8.5.9. Compressor Overload Protection Control Outdoor Fan Control • If the temperature of the indoor heat exchanger rises to 51°C, outdoor fan stops. The outdoor fan restarts when the indoor heat exchanger temperature falls to 49°C. Compressor high pressure protection • If the indoor heat exchanger becomes 65°C ormore, the compressor willstop and restart automatically. (Time Delay Safety Control- 4 minutes waiting). • This is to reduce the pressure, as to reduce the indoor heat exchanger temp....
Page 25
8.5.12. Hot Start Control • Hot Start Control is to prevent cool air discharge into the room when heating operation start. • When Heating operation starts, Indoor fan will not start until the indoor heat exchanger reaches 30°C as diagram shown. • Hot start is completed when indoor heat exchanger rises to 39°C or operation over 4 minutes. 8.5.13. Anti Cold Draft Control • This operation is to prevent the Cold Draft during Heating mode operation. • The operation will start when compressor OFF (Thermo...
Page 26
8.5.14. Deicing Control Deice starts to prevent frosting at outdoor heat exchanger. • Normal Deicing Deice operations detection commences after 30 minutes of Heating operation starts or 60 minutes after previous deice operation. If the TRS (Thermal Reed Switch) senses the outdoorpiping temperature drops to -3°C (TRS CLOSE) or less for 50 sec. continuously during compressor isin operation, deice will start. (There is no detection during Outdoor Fan stops.) • Overload Deicing During heating operation, if...
Page 27
Normal Deicing Time Diagram Overload Deicing Time Diagram 27 CS-A9DKH CU-A9DKH / CS-A12D KH CU-A12D KH /
Page 28
8.6. Indoor Fan Speed Control • Indoor Fan Speed can be set using remote control. 8.6.1. Fan Speed Rotation Chart Fan Speed (rpm)CS-A9DKHCS-A12DKH SHi12701310 Hi11601280 Me9601120 HLo840960 CLo780880 Lo-750850 SLo700750 SS Lo300300 QSHi11701210 QHi10601180 QMe8601020 QHLo770890 QLo680780 8.6.2. Automatic Fan Speed Control • When set to Auto Fan Speed, the fan speed is adjusted between maximum and minimum setting as shown in the table. − Fan speed rotates in the range of Hi, Me and Lo-. − Deodorizing...
Page 29
• Auto Fan Speed during cooling operation: 1. Indoor fan will rotate alternately between off and on as shown in below diagram. 2. At the beginning of each compressor start operation,indoor fan will increase fan speed gradually for deodorizing purpose. 3. For the first time the compressor operate, indoor fan will be switched to Hi fan speed from Lo- after 70 seconds from the start of compressor. This cause the roomtemperature to achieve the setting temperature quickly. 4. During compressor stop,...
Page 30
(Cooling and Soft Dry Operation condition) • When the vertical airflow direction is set to Auto using the remote control, the louver swings up and down as shown in the diagram. • When stop operation using the remote control, the discharge vent is reset, and stop at the closing position. • During Cooling operation or Soft Dry operation, indoor fan motor may stop to rotate at certain periods. At that condition, the louver will stop swinging and rest at the upper limit. • During Anti-dew condensation...