Home > NEC > Telephone > NEC Electra 616 General Installation Manual

NEC Electra 616 General Installation Manual

    Download as PDF Print this page Share this page

    Have a look at the manual NEC Electra 616 General Installation Manual online for free. It’s possible to download the document as PDF or print. UserManuals.tech offer 1168 NEC manuals and user’s guides for free. Share the user manual or guide on Facebook, Twitter or Google+.

    							_..._,.^ ..___ ___ _.....__..... -- .-.._ . -. ..__. -.. 
    ..- -L,.-L- 
    TO KSU 
    r 
    CABLE 
    MODULAR 
    TERMINAL 
    ________--__ J 
    Fig. 250-2 View of Modular Terminal for Connection of ET-$-l Telephone 
    Page 200-10 
    ?  
    						
    							” & 2502 EB-6-l installation 
    The 
    EB-6 -1 is a modular electronic busy lamp 
    field. Each unit is provided with a 9V DC 03A power 
    supply for LED illumination. The power supply is to be 
    plugged into a standard 117V AC outlet. Each BLF requires 
    1 -pair cabling to the main distribution frame (MDF). 
    The maximum cable length is 700 ft. using standard 24 
    AWG cable and 1,150 ft. using standard 22 AWG cable. 
    Refer to Section 140, “Cabling Requirements”, of this 
    manual. For BLF connection, see Figures 250-3, 2504 
    and 250-S and Table 240-3. 
    RUNNING CABLE 
    BLR (BK) 
    TO KSU 
    BLT (Y L) 
    DR DT 
    EB-6-1 BLF 
    Fig. 2503 Simplified Schematic - EB-6-1 BLF Connection 
    Page 200-il  
    						
    							____..__ _._- - . . . . . ..- ._.--. _- .-_ ..I ._._ _-__-l-._-~-.C_~“~-~~ ‘xL..?Au.-.. . . . . __.~, 
    TO KSU 
    BLFCABLE 
    I 
    I MODULAR 
    I TERMINAL 
    I 
    L _____------- -I 
    Fig. 2504 View of Modular Terminal for Connection of EB-6-1 BLF 
    / 
    EB-6-1 BLF 
    TO POWER 
    SUPPLY 
    Fig. 250-5 Power Supply Connection 
    Page 200-12  
    						
    							250.3 DP-6-1 Installation 
    The 
    DP-6-1 is a Door/Monitor phone unit. Each 
    door phone requires 1 pair cabling to the Main Distribution 
    Frame (MDF). The maximum cable length is 700 ft. using 
    standard 24 AWG cable and 1,150 ft. using standard 22 
    AWG cable. Refer to Section 140, “Cabling Requirements” 
    of this manual. 
    To prepare the door phone for wall mounting losen the set 
    screw and remove the door phone unit from the mounting 
    plate. Use the two screws provided or other appropriate 
    fastners to fiiy connect to wall surface. For door phone 
    cable connection, see Figure 2506 and Table 240-3. Refer 
    to Section 340, ‘Programming Sheets” for Door Phone 
    assignment. 
    SCREW SLOT 
    POSITIONS 
    TO 
    Fig. 250-6 
    Rear View of DP-6-l Door Phone 
    Page 2m-13 ‘-_  
    						
    							260 
    260.1 
    installing Options 
    Music On Hold 
    Provision has been made to allow connection of a 
    locally provided external music source to provide Music- 
    On-Hold for held CO/PBX calls. Connection of the Music 
    Source is made at the Jl Block of the Main Distribution 
    Frame (MDF). The output signal level should be approxi- 
    mately 1 milliwatt with 8 ohms impedance. See Figure 
    260.3 and Table 240.3 for connection information to 
    MDF . 
    260.2 External Paging Speaker 
    When a PBS-S KTU is installed in the ES -6 - 1 KSU, 
    external paging with meet-me answer can be provided. The 
    PBS-S KTU contains a 1 -watt Amplifier and Control 
    Circuit for one-zone paging (when a l-watt amplifier is 
    insufficient, see Section 260.5.) The External Speaker 
    should be locally-supplied in correspondence to the output 
    impedance of 600 ohms. The Volume Control (VRl), 
    located on the PBS-S, provides a way to increase or de- 
    crease the output signal of the amplifier to the speakers. 
    To adjust output signal, turn VR1 clockwise to increase 
    signal, and counterclockwise to lower signal. An LED is 
    provided on PBS-S KTU to indicate when paging is being 
    used. When an External Page is answered (meet-me-answer), 
    the PBS-S is released to allow access for another page. 
    See Figure 2 60-3 and Table 240-3 for connection informa- 
    tion to MDF. 
    260.3 External Background Music when PBS-S KTU 
    is 
    Used 
    When a PBS-S KTU is installed, an external locally- 
    provided music source can be used to supply background 
    music over the External Paging System. The recommended 
    output of the music source is l-watt with 600 ohms im- 
    pedance. When external paging is accessed music is cut off 
    from the paging speaker. Connection is made on the Jl 
    block of the MDF. See Figure 260-3 and Table 240-3 for 
    connection information to MDF. 
    260.4 External Tone Ringer 
    Provision has been made to allow connection of 
    locally provided External Tone Ringer to supply common 
    audible on all incoming CO/PBX calls. For this purpose a 
    relay contact is prepared on the CLK-S KTlJ. which 
    provides an interrupted closure (1 SEC. on/ 1 SEC. off) 
    during the CO/PBX Ring Cycle. The signal of the tone 
    ringer can be controlled by a locally provided control 
    switch. See Figure 260-3 and Table 240-3 for connection 
    information to MDF. 
    2605 External Paging Amplifier 
    The PBS-S 
    KTU contains a l-watt Amplifier and 
    control circuit for external paging. For applications where 
    1 -watt is insufficient, an external amplifier may be used. 
    Provision has been made to allow connection of a locally- 
    provided amplifier to the MDF for this purpose. The PBS-S 
    KTU is required when an external amplifier is used. See 
    Figure 2604 and Table 240-3 for connection information 
    to the MDF. 
    260.6 
    External Background Music when External 
    Amplifier is Used 
    To provide for background music with an external 
    amplifier installed, set the SW4 switch 
    io the “ON” posi- 
    tion and the SW3 switch to the “OFF” position on the 
    PBS-S KTU. When background music is not required set 
    the SW3 switch to the “ON” position and the SW4 switch 
    to the “OFF” position. Music will be cut off from the 
    . 
    paging speakers when external paging is accessed. The 
    output level and impedance of the music source should 
    match the input level and impedance of the external 
    amplifier. See Figure 2604 and Table 240-3 for connec- 
    tion information to the MDF. 
    ON c-.-.. OFF 
    ON - - OFF 
    SW3 SW4 
    Fig. 260-I PBS-S Switches for BGM 
    260-7 Power Failure Telephones 
    ET-6-l Ke:J Telephone Sets cannot be used to 
    originate or answer calls during a commercial power 
    failure. Locally-provided single line telephone sets can be 
    installed for this purpose. The KSU provides automatic 
    power failure for CO/PBX lines 
    1 and 2. No optional KTU 
    is required. Connection of the Single Line Telephones is 
    made at the Jl block of the MDF. Single Line Telephones 
    with appropriate dials (rotary or DTMF) should be installed 
    if the capability of dialing out during a power outage is 
    desired. See Figtire 260-3 and Table 240-3 for connection 
    information to MDF. 
    Page 200-14  
    						
    							26043 Security Control Equipment 
    Provision has been made to allow connection of a 
    locally-provided security control system. For this purpose 
    the PBS-S KTU contains 2 individual control circuits that, 
    when activiated, provide an audible alarm through all idle 
    keyset speakers and a visual alarm on each keyset display. 
    Each security circuit can be activiated by means of an 
    external make (closed) or break (open) contact. The SW1 
    switch on the PBS-S KTU is used to set the desired break 
    or make detection for security circuit one and the SW2 
    switch performs the same function for security circuit two. 
    For connection information to the MDF see Figure 260-3 
    and 260.4 and Table 240-3. 
    1M - - 18 2M - - 20 
    piT=q p7i-l 
    SW1 SW2 
    Fig. 260-2 PBS-S Security Control Switches 260.9 External Amplifier Control 
    A set of dry contacts is provided on the PBS-S 
    KTU, which can be used to control an auxiliary relay for 
    External Paging. Although this option is not required when 
    an external amplifier is used, it may be desired in some 
    applications. When an external page is activiated the EAS 
    and EAM contacts are closed for the duration of the page. 
    In the idle condition the closure is made between the EAS 
    and EAB contacts. See Figure 2604 and Table 240-3 for 
    connection information to the MDF. 
    Page 200 - 15  
    						
    							_. _. __. 
    -.- . . 
    CLK-S Y L-BR 
    1SE 
    BR-Y L 1SEG 
    YLSL MOH 
    SL-YL MOHG 
    VI-BL SKR 
    BL-VI SKRG 
    VI-OR BGM 
    OR-VI BGMG 
    VI-SL 2PFT 
    44 
    -oo-oo- 
    -o&a- 
    --Qc2Lo- 
    -o&o- 
    -o&o- 
    -4&o- 
    -oEoo- 
    -ocPoo- 
    -oEoo- 
    -o&* 
    -o&c 
    -o&* 
    25 
    -ac--Oo- 
    : 
    SECURITY 1 
    ACTIVATION 
    CONTACT 
    ---p&&i 
    EXTERNAL 
    PAGING 
    SPEAKERS (600.52) 
    Jl BLOCK 
    OF MDF 
    (668-50 OR 66M-50) 
    Fig. 260-3 Connection of Optional Features 
    POWER FAILURE 
    CONNECTION 
    FOR CO/PBX 1 
    POWER FAILURE 
    CONNECTION 
    FOR COIPBX 2 
    ..- Page 200-16  
    						
    							I YL-BR 2SE 
    00% 
    BR-YL 2SEG 
    00% 
    YL-SL EA 
    00% 
    SL-YL EAG 
    O& 
    PBS-S AGING AMPLIFIER 
    - VI-BL EAB 
    oa 
    RELAY CONTACT SHOWN 
    BL-VI EAS 
    00% (NON-OPERATED) IS OPERATED 
    FOR THE DURATION OF AN 
    t VI -OR EAM 
    Oc% EXTERNAL PAGE 
    OR-VI 
    00% 
    h J2 BLOCK 
    OF MDF 
    (668-50 OR 66M-50) 
    Fig. 2604 Connection of Optional Features 
    t 
    Page 200-17 _-  
    						
    							SECTiON 300 
    CONTENTS 
    310 Explanation of Programming 
    . . . . . . . . . . . . . . . . . . . . . . . . 300-l 
    320 Programming Operations . . . . . . . . . . . . . . . . . . . . . . . . . . . 300-3 
    320.1 Going Off-Line from Keyset 1 
    320.2 Selecting a Memory Block 
    320.3 Selecting Addresses Using the Dial Pad 
    320.4 Entering Data 
    320.5 Use of Function Buttons in Programming 
    320.8 Going On-Line 
    320.7 Resetting System to Change Contents of NPM 
    , 
    320.8 To Return System to Resident System Program 
    330 Job Specifications . . . . . . . . . . . . . . . . . . . _ . . . . . . . . . . I . 300-6 
    330.1 Instructions for Completing Job Specification 
    . 
    340 Programming Sheets . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 300-12 
    340.1 Programming Details 
    3402 Memory Block 1 
    340.3 Memory Block 2 
    340.4 Memory Block 3 
    340.5 Memory Block 4 
    .  
    						
    							SECTION 300 PROGRAMMING 
    310 Explanation of Programming 
    1. The Electra-616 Electronic Key Telephone System 
    comes nrovided with a Resident System Program in PROM 
    I 
    2. Keyset 1 must be installed to allow System Prograrnm- 
    ing. NO other station can program system data. The 
    programming procedure includes the foilowing steps: 
    (Programmable Read Only Memory). When the system is 
    powered this Resident System Program is duplicated in 
    RAM (Random Access Memory) and becomes the Network 
    Plan Memory (NPM). The NPM is the program the system 
    actually utilizes. This NPM will norrna.lly be supplemented 
    by progr arnrning performed at each installation to provide 
    the system program desired for the individual site. The 
    additional programming is entered into RAM which is vola- 
    tile, but which has been provided a battery to retain 
    program during power outage. 
    1. 
    2. 
    3. 
    4. Completion of job specification 
    battery provided on the CPU-S KTU is switched 
    lost with the firsr loss of Power to rhe KSCJ. 
    5. 
    6. 
    7. 
    8. 
    9. 
    10. Completion of programming work sheets. 
    Taking keyset 1 “Off-line” 
    Selecting a memory block (using DSS buttons), 
    thus selecting the general area of the memory to 
    be modified. 
    Selecting addresses via the dial pad. 
    Entering data via CO/PBX button ! -6, MIC but- 
    ton and DND button. 
    Displaying data, clearing data, changing address 
    (plus or minus 1 address increment) and writing 
    datausing the Add-On, Last NBR, Hold and Speed 
    Dial buttons. 
    Repeat steps 4 th_ru 7 until all desired data has been 
    written into memory. 
    Return keyset 1 to “on-line” mode. 
    Put the program into the working Network Plan 
    Memory. This function will occur automatically 
    when the entire system is idle. An alternate 
    method is to depress the reset button on the 
    CPU-S KTU; this will interrupt service. Testing 
    of the new program can then be performed. 
    Page 300-l _-’  
    						
    All NEC manuals Comments (0)

    Related Manuals for NEC Electra 616 General Installation Manual