NEC Electra 616 General Installation Manual
Have a look at the manual NEC Electra 616 General Installation Manual online for free. It’s possible to download the document as PDF or print. UserManuals.tech offer 1168 NEC manuals and user’s guides for free. Share the user manual or guide on Facebook, Twitter or Google+.
_..._,.^ ..___ ___ _.....__..... -- .-.._ . -. ..__. -.. ..- -L,.-L- TO KSU r CABLE MODULAR TERMINAL ________--__ J Fig. 250-2 View of Modular Terminal for Connection of ET-$-l Telephone Page 200-10 ?
” & 2502 EB-6-l installation The EB-6 -1 is a modular electronic busy lamp field. Each unit is provided with a 9V DC 03A power supply for LED illumination. The power supply is to be plugged into a standard 117V AC outlet. Each BLF requires 1 -pair cabling to the main distribution frame (MDF). The maximum cable length is 700 ft. using standard 24 AWG cable and 1,150 ft. using standard 22 AWG cable. Refer to Section 140, “Cabling Requirements”, of this manual. For BLF connection, see Figures 250-3, 2504 and 250-S and Table 240-3. RUNNING CABLE BLR (BK) TO KSU BLT (Y L) DR DT EB-6-1 BLF Fig. 2503 Simplified Schematic - EB-6-1 BLF Connection Page 200-il
____..__ _._- - . . . . . ..- ._.--. _- .-_ ..I ._._ _-__-l-._-~-.C_~“~-~~ ‘xL..?Au.-.. . . . . __.~, TO KSU BLFCABLE I I MODULAR I TERMINAL I L _____------- -I Fig. 2504 View of Modular Terminal for Connection of EB-6-1 BLF / EB-6-1 BLF TO POWER SUPPLY Fig. 250-5 Power Supply Connection Page 200-12
250.3 DP-6-1 Installation The DP-6-1 is a Door/Monitor phone unit. Each door phone requires 1 pair cabling to the Main Distribution Frame (MDF). The maximum cable length is 700 ft. using standard 24 AWG cable and 1,150 ft. using standard 22 AWG cable. Refer to Section 140, “Cabling Requirements” of this manual. To prepare the door phone for wall mounting losen the set screw and remove the door phone unit from the mounting plate. Use the two screws provided or other appropriate fastners to fiiy connect to wall surface. For door phone cable connection, see Figure 2506 and Table 240-3. Refer to Section 340, ‘Programming Sheets” for Door Phone assignment. SCREW SLOT POSITIONS TO Fig. 250-6 Rear View of DP-6-l Door Phone Page 2m-13 ‘-_
260 260.1 installing Options Music On Hold Provision has been made to allow connection of a locally provided external music source to provide Music- On-Hold for held CO/PBX calls. Connection of the Music Source is made at the Jl Block of the Main Distribution Frame (MDF). The output signal level should be approxi- mately 1 milliwatt with 8 ohms impedance. See Figure 260.3 and Table 240.3 for connection information to MDF . 260.2 External Paging Speaker When a PBS-S KTU is installed in the ES -6 - 1 KSU, external paging with meet-me answer can be provided. The PBS-S KTU contains a 1 -watt Amplifier and Control Circuit for one-zone paging (when a l-watt amplifier is insufficient, see Section 260.5.) The External Speaker should be locally-supplied in correspondence to the output impedance of 600 ohms. The Volume Control (VRl), located on the PBS-S, provides a way to increase or de- crease the output signal of the amplifier to the speakers. To adjust output signal, turn VR1 clockwise to increase signal, and counterclockwise to lower signal. An LED is provided on PBS-S KTU to indicate when paging is being used. When an External Page is answered (meet-me-answer), the PBS-S is released to allow access for another page. See Figure 2 60-3 and Table 240-3 for connection informa- tion to MDF. 260.3 External Background Music when PBS-S KTU is Used When a PBS-S KTU is installed, an external locally- provided music source can be used to supply background music over the External Paging System. The recommended output of the music source is l-watt with 600 ohms im- pedance. When external paging is accessed music is cut off from the paging speaker. Connection is made on the Jl block of the MDF. See Figure 260-3 and Table 240-3 for connection information to MDF. 260.4 External Tone Ringer Provision has been made to allow connection of locally provided External Tone Ringer to supply common audible on all incoming CO/PBX calls. For this purpose a relay contact is prepared on the CLK-S KTlJ. which provides an interrupted closure (1 SEC. on/ 1 SEC. off) during the CO/PBX Ring Cycle. The signal of the tone ringer can be controlled by a locally provided control switch. See Figure 260-3 and Table 240-3 for connection information to MDF. 2605 External Paging Amplifier The PBS-S KTU contains a l-watt Amplifier and control circuit for external paging. For applications where 1 -watt is insufficient, an external amplifier may be used. Provision has been made to allow connection of a locally- provided amplifier to the MDF for this purpose. The PBS-S KTU is required when an external amplifier is used. See Figure 2604 and Table 240-3 for connection information to the MDF. 260.6 External Background Music when External Amplifier is Used To provide for background music with an external amplifier installed, set the SW4 switch io the “ON” posi- tion and the SW3 switch to the “OFF” position on the PBS-S KTU. When background music is not required set the SW3 switch to the “ON” position and the SW4 switch to the “OFF” position. Music will be cut off from the . paging speakers when external paging is accessed. The output level and impedance of the music source should match the input level and impedance of the external amplifier. See Figure 2604 and Table 240-3 for connec- tion information to the MDF. ON c-.-.. OFF ON - - OFF SW3 SW4 Fig. 260-I PBS-S Switches for BGM 260-7 Power Failure Telephones ET-6-l Ke:J Telephone Sets cannot be used to originate or answer calls during a commercial power failure. Locally-provided single line telephone sets can be installed for this purpose. The KSU provides automatic power failure for CO/PBX lines 1 and 2. No optional KTU is required. Connection of the Single Line Telephones is made at the Jl block of the MDF. Single Line Telephones with appropriate dials (rotary or DTMF) should be installed if the capability of dialing out during a power outage is desired. See Figtire 260-3 and Table 240-3 for connection information to MDF. Page 200-14
26043 Security Control Equipment Provision has been made to allow connection of a locally-provided security control system. For this purpose the PBS-S KTU contains 2 individual control circuits that, when activiated, provide an audible alarm through all idle keyset speakers and a visual alarm on each keyset display. Each security circuit can be activiated by means of an external make (closed) or break (open) contact. The SW1 switch on the PBS-S KTU is used to set the desired break or make detection for security circuit one and the SW2 switch performs the same function for security circuit two. For connection information to the MDF see Figure 260-3 and 260.4 and Table 240-3. 1M - - 18 2M - - 20 piT=q p7i-l SW1 SW2 Fig. 260-2 PBS-S Security Control Switches 260.9 External Amplifier Control A set of dry contacts is provided on the PBS-S KTU, which can be used to control an auxiliary relay for External Paging. Although this option is not required when an external amplifier is used, it may be desired in some applications. When an external page is activiated the EAS and EAM contacts are closed for the duration of the page. In the idle condition the closure is made between the EAS and EAB contacts. See Figure 2604 and Table 240-3 for connection information to the MDF. Page 200 - 15
_. _. __. -.- . . CLK-S Y L-BR 1SE BR-Y L 1SEG YLSL MOH SL-YL MOHG VI-BL SKR BL-VI SKRG VI-OR BGM OR-VI BGMG VI-SL 2PFT 44 -oo-oo- -o&a- --Qc2Lo- -o&o- -o&o- -4&o- -oEoo- -ocPoo- -oEoo- -o&* -o&c -o&* 25 -ac--Oo- : SECURITY 1 ACTIVATION CONTACT ---p&&i EXTERNAL PAGING SPEAKERS (600.52) Jl BLOCK OF MDF (668-50 OR 66M-50) Fig. 260-3 Connection of Optional Features POWER FAILURE CONNECTION FOR CO/PBX 1 POWER FAILURE CONNECTION FOR COIPBX 2 ..- Page 200-16
I YL-BR 2SE 00% BR-YL 2SEG 00% YL-SL EA 00% SL-YL EAG O& PBS-S AGING AMPLIFIER - VI-BL EAB oa RELAY CONTACT SHOWN BL-VI EAS 00% (NON-OPERATED) IS OPERATED FOR THE DURATION OF AN t VI -OR EAM Oc% EXTERNAL PAGE OR-VI 00% h J2 BLOCK OF MDF (668-50 OR 66M-50) Fig. 2604 Connection of Optional Features t Page 200-17 _-
SECTiON 300 CONTENTS 310 Explanation of Programming . . . . . . . . . . . . . . . . . . . . . . . . 300-l 320 Programming Operations . . . . . . . . . . . . . . . . . . . . . . . . . . . 300-3 320.1 Going Off-Line from Keyset 1 320.2 Selecting a Memory Block 320.3 Selecting Addresses Using the Dial Pad 320.4 Entering Data 320.5 Use of Function Buttons in Programming 320.8 Going On-Line 320.7 Resetting System to Change Contents of NPM , 320.8 To Return System to Resident System Program 330 Job Specifications . . . . . . . . . . . . . . . . . . . _ . . . . . . . . . . I . 300-6 330.1 Instructions for Completing Job Specification . 340 Programming Sheets . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 300-12 340.1 Programming Details 3402 Memory Block 1 340.3 Memory Block 2 340.4 Memory Block 3 340.5 Memory Block 4 .
SECTION 300 PROGRAMMING 310 Explanation of Programming 1. The Electra-616 Electronic Key Telephone System comes nrovided with a Resident System Program in PROM I 2. Keyset 1 must be installed to allow System Prograrnm- ing. NO other station can program system data. The programming procedure includes the foilowing steps: (Programmable Read Only Memory). When the system is powered this Resident System Program is duplicated in RAM (Random Access Memory) and becomes the Network Plan Memory (NPM). The NPM is the program the system actually utilizes. This NPM will norrna.lly be supplemented by progr arnrning performed at each installation to provide the system program desired for the individual site. The additional programming is entered into RAM which is vola- tile, but which has been provided a battery to retain program during power outage. 1. 2. 3. 4. Completion of job specification battery provided on the CPU-S KTU is switched lost with the firsr loss of Power to rhe KSCJ. 5. 6. 7. 8. 9. 10. Completion of programming work sheets. Taking keyset 1 “Off-line” Selecting a memory block (using DSS buttons), thus selecting the general area of the memory to be modified. Selecting addresses via the dial pad. Entering data via CO/PBX button ! -6, MIC but- ton and DND button. Displaying data, clearing data, changing address (plus or minus 1 address increment) and writing datausing the Add-On, Last NBR, Hold and Speed Dial buttons. Repeat steps 4 th_ru 7 until all desired data has been written into memory. Return keyset 1 to “on-line” mode. Put the program into the working Network Plan Memory. This function will occur automatically when the entire system is idle. An alternate method is to depress the reset button on the CPU-S KTU; this will interrupt service. Testing of the new program can then be performed. Page 300-l _-’