Home
>
Lucent Technologies
>
Communications System
>
Lucent Technologies DEFINITY Extender Switch Module System Administrators Guide
Lucent Technologies DEFINITY Extender Switch Module System Administrators Guide
Have a look at the manual Lucent Technologies DEFINITY Extender Switch Module System Administrators Guide online for free. It’s possible to download the document as PDF or print. UserManuals.tech offer 413 Lucent Technologies manuals and user’s guides for free. Share the user manual or guide on Facebook, Twitter or Google+.
Installation Issue 3 July 1997 3-17 Figure 3-4. RS-232 Cable Pin Connections NOTE: The DEFINITY Extender modules use the CTS lead for flow control. When the internal buffer is 32 characters from full, the CTS lead is turned off. While CTS is off, up to an additional 32 characters can be transmitted without any loss of data. If hardware flow control is not enabled or if a cable without the CTS lead is used, characters will be lost when this buffer overflows. The DEFINITY Extender modules use the DCD lead to indicate whether or not the modules have made a connection. When this lead is on, the modules have made connection.
Issue 3 July 1997 4-1 Troubleshooting 4 Troubleshooting and LED Activity As with all equipment of a sophisticated nature, occasionally an error in connection or transmission may occur. The DEFINITY Extender system provides indication of any errors via light-emitting diodes (LEDs) on the Remote and Switch Modules and by error messages on the display telephone connected to the Remote Module.
Troubleshooting 4-2 Issue 3 July 1997 Troubleshooting When an error occurs in the operation of the Switch Module, you should check for malfunctions in an organized manner. Follow these steps when troubleshooting the Switch Module: 1. Check all interconnecting cables to ensure that they are properly seated. 2. Verify that the DIP switches are set correctly. 3. Check the circuits to ensure that they are free of noise and meet the specifications listed in Chapter 1, Introduction. 4. Verify that the power LEDs are illuminated. 5. If you cannot locate the source of the problem, contact Lucent Technologies by calling 1 800 242-2121 at any time. Please have ready the serial number found on your Switch Module and a description of the problem. If a remote user reports a problem with the Remote Module, verify that the user has followed the appropriate troubleshooting steps: 1. Verify that the programmed telephone number is correct. 2. Check all interconnecting cables to ensure that they are properly seated. 3. Verify that the DIP switches are set correctly. 4. Check the circuits to ensure that they are free of noise and meet the specifications listed in Chapter 1, Introduction. 5. Verify that the power LEDs are illuminated. If you must contact Lucent Technologies on behalf of the remote user, be sure to obtain the serial number found on the Remote Module.
Troubleshooting Issue 3 July 1997 4-3 LED Sequences The LEDs on the Standalone Switch Module and the Rack-Mount Switch Module help to indicate problems that occur. Standalone Switch Module The following flash sequences may be observed on the Standalone Switch Module: n1 Green: Online to Remote Module n2 Green: Dial mode; waiting for ring n3 Green: Leased line mode; waiting for connect sequence n4 Green: Dial mode connect sequence n3 Red: Waiting for PBX connection n3 Yellow: Test mode NOTE: During the power-up sequence, the DEFINITY Extender system performs a self-test, indicated by a sequence of eight red flashes.
Troubleshooting 4-4 Issue 3 July 1997 Multi-Mount Rack The Multi-Mount Rack’s LED blink sequence helps to identify a malfunctioning interface card. Problem cards are identified by a red/green blink in the LED blink sequence. Table 4-1 shows the LED blink sequences for the Rack-Mount Switch Module The sequences are listed in the order of priority. Table 4-1. Rack-Mount Module LED Blink Sequence LED Sequence Meaning RGRG Module has been flagged by Remote user. A Remote Module user can flag a Rack-Mount module when he or she is having audio and/or other problems on a particular connection. The remote user does this by pressing the Hold key four times and then pressing the # key when the display shows “Disconnect?”. This causes the DEFINITY ECS and the module connected to this remote user to display this sequence until either the module is unplugged or the module’s diagnostics counts are reset through the Administration Port. RRR Module is waiting for connection to DEFINITY DCP port. RRGG Module has not detected a ring on analog line connection since power-up or since the diagnostic counts have been reset. If this LED sequence continues for a long time, this indicates a serious problem, such as incorrect wiring. Continued on next page
Troubleshooting Issue 3 July 1997 4-5 Table 4-1. Rack-Mount Module LED Blink Sequence ( Continued) LED Sequence Meaning RRG Module has detected at least one ring but is waiting for a ring on analog line connection. Since power-up or since diagnostic counts have been reset, the Rack-Mount Module has not been successfully connected to the Remote Module. RGG Module is waiting for ring on analog line. The Rack-Mount Module has had at least three connect sessions with a Remote Module, but each session has lasted less than an hour. RGGGG Module is attempting to connect to a Remote Module but has not been connected to a Remote Module within the last three connect sessions for at least one hour. RG Module is online to a Remote Module but has not been connected to a Remote Module within the last three connect sessions for at least one hour. GG Module is waiting for a ring on the analog line; no abnormalities have been detected. GGGG Module is attempting to connect to a Remote Module; no abnormalities have been detected. G Module is online to a Remote Module; no abnormalities have been detected.
Troubleshooting 4-6 Issue 3 July 1997 Error Messages If a problem has been encountered during the connection process, an error message appears on the remote telephone. Table 4-2 shows the error messages and the suggested actions to take. Table 4-2. Error Messages Message Cause Action No Dial Tone The Remote Module is not properly connected to the local telephone company.Connect a regular telephone to the telephone company jack, and listen for dial tone. Make sure the line is properly connected to the jack on the Remote Module. If there still is no dial tone, have the local telephone company check the line. Line Busy The line that the Switch Module is connected to is already in use.Verify that the correct telephone number has been programmed and that no one else is using the Switch Module the remote user is calling. Continued on next page
Troubleshooting Issue 3 July 1997 4-7 Table 4-1. Error Messages— Continued Message Cause Action No Answer ToneThe Switch Module is not responding. The Remote Module does not receive a Ring- Back Tone or an Answer Back Tone.Verify that the correct telephone number has been programmed. Verify that the Switch Module is connected to the line. Rate Too SlowThe rate at which the modem is connecting is not fast enough to allow for successful operation of the system.Have the local telephone company lines checked.
Troubleshooting 4-8 Issue 3 July 1997 Specific Problems Problems that may develop with the DEFINITY Extender system usually reflect what type of line is being used, dial line or dedicated line. In either case you should try the Switch Modules at the DEFINITY ECS location so you can determine if the problem is with the Switch Module or with the communications system. Dial Line Problems The following problems may occur with Switch Modules connected to analog dial lines. The possible steps to solve the problem are listed after each problem’s heading. No Display on Telephone at Remote Location To correct this problem, answer or do the following: 1. Is the correct module at each location? 2. If this is an existing installation, has the installation moved or has any new wiring been done? Verify the connections. 3. Does the Remote Module have power? 4. Compare the LED on the Remote Module to the LED diagnostic sheet. The Remote Module may be defective. 5. Is the telephone working properly?
Troubleshooting Issue 3 July 1997 4-9 No Connection/No Answer Tone To correct this problem, answer or do the following: 1. Does the display on the telephone say “Go Online”? If so, press 2 to start the session. (A new user may never have seen the Remote Module off-line before.) 2. Check the power connection on the Switch Module. 3. Check the LED on the Switch Module and compare it to the LED diagnostic sheet. The Switch Module may be defective. 4. Check that the DIP switches on the Switch and Remote Modules are set for dial line (DIP switch #2 should be OFF). 5. Have there been any electrical storms that may have popped the line fuses? 6. Go on-line and monitor call progress on the Remote Module speaker. 7. If there still is no dial tone, do the following: a. Check the cables on the Remote Module; replace if necessary. b. Use a regular telephone to get dial tone on the jack. If there is no dial tone, check the installation wiring or call the telephone company. If there is dial tone present, the cable to the Module or a popped line fuse is probably the problem.