    Specifications  61 
    Battery specifications          
    Feature   Specification  
    Type 
    12 V, 5 AH, sealed, maintenance -free, rechargeable, valve 
    regulated lead- acid batteries with a 3 -5 year service life at 
    25°C (77°F).  
    Voltage  The battery modules have a battery string voltage of 120 V.  
    Charging 
    Complete charge takes no  more than 48 hours. After 
    approximately 3 hours, the batteries reach 80% charge at 
    default nominal utility voltage and no load.  
      
    High -voltage UPS battery runtimes       
    Load, percent  
    Estimated battery  
    runtime   Runtime with one ERM
     Runtime with two ERMs  
    20 40 minutes  125 minutes  225 minutes 
    50  12 minutes  50 minutes  89 minutes 
    80  6 minutes  30 minutes  54 minutes 
    100  4 minutes  24 minutes  43 minutes       
    Low -voltage UPS battery runtimes       
    Load, percent  
    Estimated battery 
    runtime   Runtime with one ERM
     Runtime with two ERMs  
    20 45 minutes  142 minutes  256 minutes 
    50  15.5 minutes 55 minutes  99 minutes 
    80  7 minutes  34 minutes  60 minutes 
    100  5 minutes  26 minutes  47 minutes       
    Environmental specifications     
    Feature   Specification 
    Operating temperature  
    10°C to 40°C (50°F to 104°F); UL -tested at 25°C 
    (77°F)  
    Nonoperating 
    temperature  -
    20°C to 50°C ( -4°F to 122°F)  
    Relative humidity  20% to 80%; noncondensing  
    Operating altitude Up to 2,000 m (6,600 ft) above sea level  
    Nonoperating altitude 15,000 m (49,212 ft) above sea level  
    Audible noise Less than 45 dBA, normal operation 
    Less than 50 dBA, on battery power  
       
    						
    							
     
    Specifications  62 
    REPO port specifications  
    The REPO port meets the requirements of NFPA Articles 645 -10 and 645 -11 for a Disconnecting Means.   
    						
    							
     
    Spares  63  
    Spares  
    Ordering spares  
    To order a spare, visit the HP website  (ht tp://www.hp.com/buy/parts). 
    To replace parts under warranty, contact an HP authorized service representative.  
     
    UPS spare parts list  
            
    Item Description   Spare part number 
    1  UPS unit NA/JPN   517699-001  
    *  UPS unit HV NA/JPN   517700-001  
    *  UPS unit INTL   517701-001  
    2  X-slot serial card   419180-001 
    3  Battery module   517703-001  
    *  Mounting rail s with screws  419181-001 
    *  UPS/ERM mounting brackets  582931-001 
    *  Cord retention clips   407409-001 
    *  Serial download cable  397642-001     
    * not shown    
    						
    							
     
    Spares  64  
    ERM spare parts list  
         
    Item   Description   Spare part number  
    1  ERM unit  517702-001  
    * 
    UPS/ERM mounting 
    brackets  582931-
    001 
    *  Mounting rails with screws  419181- 001  
    * not shown   
    Hardware options  
    For information on the supported hardware options, see the HP website 
    ( http://www.hp.com/go/rackandpower
    ).   
    						
    							
     
    Technical  support  65 
    Technical support  
    Before you contact HP  
    Be sure to have the following information available before you call HP:  
    • Technical support registration number (if applicable)  
    • Product serial number 
    • Product model name and number  
    • Product identification number 
    • Applicable error messages 
    • Add-on boards or hardware  
    • Third-party hardware or software  
    • Operating system type and revision level   
    HP contact information  
    For the name of the nearest HP authorized reseller:  
    • See the Contact HP worldwide (in English) webpage  
    ( http://welcome.hp.com/country/us/en/wwcontact.html
    ).  
    For HP technical support:  
    • In the United States, for contact options see the Contact HP United States webpage  
    ( http://w elcome.hp.com/country/us/en/contact_us.html
    ). To contact HP by phone:  
    o Call 1 -800 -HP -INVENT (1 -800 -474 -6836). This service is available 24  hours a day, 7  days a 
    week. For continuous quality improvement, calls may be recorded or monitored.   
    o If you have purc hased a Care Pack (service upgrade), call 1 -800 -633 -3600. For more 
    information about Care Packs, refer to the HP website  (http://www.hp.com/hps
    ).  
    • In other locations, see the Contact HP worldwide (in English) webpage  
    ( http://welcome.hp.com/country/us/en/wwcontact.html
    ).   
    						
    							
     
    Warranty information  66 
    W arranty information  
    Limited warranty  
    To back up the wide range of features offered with the UPS, a 3 -year limited warranty is provided.   
    $250,000 Computer Load Protection Guarantee  
    In addition to the limited warranty, a $250,000 Computer Load Protection Guarantee (provided by the 
    original equipment manufacturer) is offered. 
      
      IMPORTANT:
      The $250,000 Computer Load Protection Guarantee is offered only in The 
    United States and Canada.  
      
    The $250,000 Computer Load Protection Guarantee only applies if:  
    • The UPS is plugged into a suitably grounded and wired outlet using no extension cords, adapters, 
    other ground wires, or other electrical connections. 
    • The UPS installation complies with all applicable electrical and safety codes specified by the NEC.  
    • The UPS is used under normal operating conditions and users comply with all instructions and labels.  
    • The UPS is not damaged by accident (other than a utility power transient), misuse, or abuse.  
    o The Guarantee applies only to the original end -user and is non -transferable.  
    o Th e Guarantee does not include reimbursement for or restoration of any data loss.  
    • The UPS is either connected directly to an enterprise class PDU, which is then connected directly to a 
    server, workstation, or personal computer, or the UPS is connected directly to a server, workstation, 
    or personal computer.  
     
    Pre-Failure Battery Warranty  
    The Pre-Failure Battery Warranty, standard on all UPS units, extends the advantage of a 3 -year limited 
    warranty by applying it to the battery before it actually fails. The Pre -Failure Battery Warranty ensures that 
    the battery is replaced free of charge when a notification that the battery might fail is received from 
    power management software. The battery warranty coverage is 3 years for parts. The warranty for the 
    first year of ownership includes parts and labor. If battery spares are not available for a particular UPS 
    model, the entire UPS, including its battery, is replaced.  
    A Pre -Failure Battery warning is given 30 days before a battery failure. The war ning is indicated in one or 
    both of the following ways:  
    • An LED showing the battery is low 
    • Notification from power management software    
    						
    							
     
    Warranty information  67 
    Recommended duration of use  
    Although tests and a multitude of cus tomer experiences have shown no noticeable performance issues 
    with UPSs for significant time periods after expiration of the 3 -year limited warranty, we strongly 
    recommend considering replacing UPSs after a maximum of 5 to 6 years of use to assure full fun ctionality 
    and a safe operating environment. This recommendation does not extend or in any way alter the warranty 
    for UPSs which is limited to a time period of 3 years and a coverage as stated in the applicable warranty 
    statement.   
    						
    							
     
    Regulatory compliance  notices  68 
    Regulatory compliance notices  
    Regulatory compliance identification numbers  
    For the purpose of regulatory compliance certifications and identification, this product has been assigned 
    a unique regulatory model number. The regulatory model number can be found on the product nameplate 
    label, along with all required approval markings and information. When requesting compliance 
    information for this product, always refer to this reg ulatory model number. The regulatory model number is 
    not the marketing name or model number of the product.  
     
    Federal Communications Commission notice  
    Part 15 of the Federal Communications Commission (FCC ) Rules and Regulations has established Radio 
    Frequency (RF) emission limits to provide an interference -free radio frequency spectrum. Many electronic 
    devices, including computers, generate RF energy incidental to their intended function and are, therefore , 
    covered by these rules. These rules place computers and related peripheral devices into two classes, A 
    and B, depending upon their intended installation. Class  A devices are those that may reasonably be 
    expected to be installed in a business or commercia l environment. Class B devices are those that may 
    reasonably be expected to be installed in a residential environment (for example, personal computers). 
    The FCC requires devices in both classes to bear a label indicating the interference potential of the device 
    as well as additional operating instructions for the user.  
     
    FCC rating label  
    The FCC rating label on the device shows the classification (A or B) of the equipment. Class  B devices 
    have an FCC logo or ID on the label. Class  A de vices do not have an FCC logo or ID on the label. After 
    you determine the class of the device, refer to the corresponding statement.  
     
    Class A equipment  
    This equipment has been tes ted and found to comply with the limits for a Class  A digital device, pursuant 
    to Part  15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful 
    interference when the equipment is operated in a commercial environment. This equipment generates, 
    uses, and can radiate radio frequency energy and, if not installed and used in accordance with the 
    instructions, may cause harmful interference to radio communications. Operation of this equipment in a 
    residential area is likely t o cause harmful interference, in which case the user will be required to correct 
    the interference at personal expense.  
     
    Class B equipment  
    This equipment has been tested and found to comply with the limits for a Class  B digital device, pursuant 
    to Part  15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful 
    interference in a residential installation. This equipment generates, uses, and can rad iate radio frequency 
    energy and, if not installed and used in accordance with the instructions, may cause harmful interference  
    						
    							
     
    Regulatory compliance  notices  69 
    to radio communications. However, there is no guarantee that interference will not occur in a particular 
    installation. If this equipment does cause harmful interference to radio or television reception, which can 
    be determined by turning the equipment off and on, the user is encouraged to try to correct the 
    interference by one or more of the following measures:  
    • Reorient or relocate the receiving antenna. 
    • Increase the separation between the equipment and receiver.  
    • Connect the equipment into an outlet on a circuit that is different from that to which the receiver is 
    connected. 
    • Consult the dealer or an experienced radio or television te chnician for help.  
    Declaration of conformity for products marked with 
    the FCC logo, United States only  
    This device complies with Part 15 of the FCC Rules. Operation is su bject to the following two conditions: 
    (1) this device may not cause harmful interference, and (2) this device must accept any interference 
    received, including interference that may cause undesired operation.  
    For questions regarding this product, contact u s by mail or telephone: 
    • Hewlett-Packard Company  
    P. O. Box 692000, Mail Stop 530113  
    Houston, Texas 77269 -2000  
    • 1-800 -HP -INVENT (1 -800 -474 -6836). (For continuous quality improvement, calls may be recorded 
    or monitored.)  
    For questions regarding this FCC declar ation, contact us by mail or telephone: 
    • Hewlett-Packard Company  
    P. O. Box 692000, Mail Stop 510101  
    Houston, Texas 77269 -2000  
    • 1- 281 -514 -3333  
    To identify this product, refer to the part, series, or model number found on the product.  
     
    Modifications 
    The FCC requires the user to be notified that any changes or modifications made to this device that are 
    not expressly approved by Hewlett-Packard Company may void the user’s authori ty to operate the 
    equipment.  
     
    Cables  
    Connections to this device must be made with shielded cables with metallic RFI/EMI connector hoods in 
    order to maintain compliance with FCC Rules and Regulations.  
      
    						
    							
     
    Regulatory compliance  notices  70 
    Canadian notice (Avi s Canadien) 
    Class A equipment  
    This Class  A digital apparatus meets all requirements of the Canadian Interference -Causing Equipment 
    Regulations.  
    Cet appareil numérique de la classe A respecte toutes les exigences du Règlement sur le matériel 
    brouilleur du C anada. 
    Class  B equipment  
    This Class  B digital apparatus meets all requirements of the Canadian Interference -Causing Equipment 
    Regulations.  
    Cet appareil numérique de la classe B respecte toutes les exigences du Règlement sur le matériel 
    brouilleur du Canada.  
     
    European Union regulatory notice  
    This product complies with the following EU Directives:  
    • Low Voltage Directive 2006/95/EC 
    • EMC Directive 2004/108/EC 
    Compliance with these directives implies conformity to applicable harmonized European standards 
    (European Norms) which are listed on the EU Declaration of Conformity issued by Hewlett -Packard for this 
    product or product family.  
    This compliance is indicated by the following conformity marking placed on the product:   
     
    This marking is valid for non -Telecom products and EU harmonized Telecom products (e.g. Bluetooth).  
     
     
    This marking is valid for EU non- harmonized Telecom products. 
    *Notified body number (used only if applicable —refer to the product label) 
    Hewlett -Packard GmbH, HQ -TRE, Herrenberger Strasse 140, 71034 Boeblingen, Germany   
    The official EU CE declaration of conformity for this device can be found on the HP w ebsite 
    ( http://www.hp.com/go/certificates
    ).   
    Disposal of waste equipment by users in private 
    households in the European Union 
     
      
    						
    All HP manuals Comments (0)

    Related Manuals for HP Rt3000 Instruction Manual