Home > HP > Power Products > HP Rt3000 Instruction Manual

HP Rt3000 Instruction Manual

    Download as PDF Print this page Share this page

    Have a look at the manual HP Rt3000 Instruction Manual online for free. It’s possible to download the document as PDF or print. UserManuals.tech offer 1114 HP manuals and user’s guides for free. Share the user manual or guide on Facebook, Twitter or Google+.

    							
     
    Power  management  51 
    Power management  
    Power management software  
    HP Power Manager software ensures maximum power reliability of computer systems through 
    comprehensive control of UPSs. The easy -to -use browser interface enables novice users to configure and 
    manage power protecti on settings. To download the latest version of HP Power Manager software, see 
    the  HP website  (http://www.hp.com/go/rackandpower
    ).    
     
    NOTE:  To install and configure the software, see the software user guide.  The software user 
    guide is available for download from the HP website 
    ( http://www.hp.com/go/rackandpower
    ).    
    HP Power Manager:  
    • Does not require complex management systems, which simplifies deployment, conf iguration, and 
    management of UPS -protected environments.  
    • Manages a graceful shutdown of attached devices during utility power failures.  
    • Prioritizes the timing of attached load device shutdowns. 
    • Shuts down and reboots any UPS and attached load devices based  on a user-specified schedule.  
    • Customizes alert generation with modifiable dialog boxes, command execution, and email and 
    broadcast messages.  
    • Monitors the status of the UPS and reports alarms.  
    • Displays a power log for analysis. 
    • Manages independent UPS load segments to provide separate power control of attached load 
    devices.  
    • Delays reboot by load segment after a power outage to sequence the startup of system components.   
    						
    							
     
    Troubleshooting  52 
    Troubleshootin g 
    LED troubleshooting            
    Utility 
    LED  On 
    Batter
    y LED
     On 
    Bypas
    s LED
     Self 
    Test 
    LED
      Battery 
    Fault 
    LED
      Site 
    Wiring 
    Fault 
    LED
      Over 
    Temp 
    LED
      Overloa
    d LED
      Condition
     
    On—
    Load 
    10% On—
    Load 
    >25%
     On—
    Load 
    >50%
     On—
    Load 
    >75%
     Off
     
    UPS is in Operate mode  (on 
    page  38) 
    Flashin
    g  Off
      Off  Off  *  *  *  Off 
    UPS is in Standby mode  (on 
    page  38) 
    Off  Off  On 
    On—
    Load 
    >10% On—
    Load 
    >25%
     On—
    L
    oad 
    >50%  On—
    Load 
    >75%
     Off
     
    UPS is in Auto -Bypass mode  
    (on page 39)  
    Flashin
    g  Flashin
    g
      Flashin
    g
      Off
      Off  Off  Off  Off 
    UPS is in Converter Off mode  
    (on page 54)  
    Off  Off  Off  Off  Off  Off  Flashing Flashing  
    General alarm condition  (on 
    page  54)—UPS is in Auto -
    Bypass mode  
    On  Off 
    Flashin
    g  *
      *  *  *  * 
    Bypass is out of range  (on 
    page  55) 
    *  Off  *  Off  Flashing *  *  * 
    Battery condition  (on page 
    55) —Batteries are 
    disconnected or battery test 
    failure  
    Off 
    Flashin
    g  Off
      Off  Off  Off  Off  Off 
    Low battery (no utility power)  
    (" UPS is on battery " on page 
    55)   
    						
    							
     
    Troubleshooting  53 
    Off
      On  Off 
    On—
    Battery 
    capacity 
    25%
     On—
    Batt
    ery 
    capacity 
    >50%  On—
    Battery 
    capacity 
    >75%
     Off
     
    UPS is on battery  (on page 
    55) —No utility power  
    *  *  *  Off  *  *  Flashing * 
    Overtemperature condition  
    (on page 56)  
    Off  Off  On  Flashing  Flashing  Flashing  Flashing  Flashing  
    Internal UPS fault condition  
    (on page 56)  
    Flashin
    g  Off
      Off  Flashing  Flashing  Flashing  Flashing  Flashing  
    REPO condition  (on page 
    56)  
    *  Off  *  Off  *  Flashing *  * 
    Site wiring condition  (on 
    page  56) 
    *  Off  *  On  On  On  On  Flashing 
    Overload condition  (on page 
    57) —UPS power capacity is 
    exceeded with no other faults  
    *  Off  *  Off  *  *  *  Flashing 
    Overload condition  (on page 
    57) —UPS power capacity is 
    exce eded while other faults 
    exist  
    Off  On  Off 
    On—
    Battery 
    capacity 
    25%
     On—
    Battery 
    capacity 
    >50%
     On—
    Battery 
    capacity 
    >75%
     Flashing
     
    Overload condition  (on page 
    57) —UPS power capacity is 
    exceeded while on battery 
    with no other faults  
    Off  On  Off  Off  Off  Off  Flashing Flashing  
    Overload condition  (on page 
    57) —UPS power capacity is 
    exceeded while on battery 
    with overtemperature fault 
    Off  
    Flashin
    g  Off
      Flashing  Flashing  Flashing  Flashing  Flashing  Unit is powering down  
    Flashin
    g  Flashin
    g
      Flashin
    g
      Flashing
     Flashing  Flashing  Flashing  Flashing  
    Checksum failure error  (on 
    page  57) 
     
    * This LED can be in any state.  
    For the location of individual LEDs, see " UPS front panel LED indicators (on page 8 )."  
    UPS is in Auto -Bypass mode 
    The UPS transfers from Operate mode  (on page 38 ) to Auto-Bypass when one of the following fault 
    conditions is detected:  
    • Inverter AC over voltage  
    • Inverter AC under voltage  
    • Rectifier input over current  
    • Inverter output over current  
    • Inverter fault 
    • Heat sink over temperature  
    • Fan failure  
    						
    							
     
    Troubleshooting  54 
    • Overload  
    The load is supported, but not protected while in Auto -Bypass mode.  
    Action : 
    1.  If power management software is b eing used, check the log files to obtain specific error information 
    to help identify the problem.  
    For more information about the causes of a general fault condition, see the HP Power Manager user 
    guide available for download from the HP website  (http://www.hp.com/go/rackandpower
    ).  
    2.  Verify that no blockage of airflow to the front bezel and rear panel exists.   
    UPS is in Converter Off mode 
    Fault conditions cause the UPS to transfer to Converter Off mode from Standby mode  (on page 38 ) only. 
    If the UPS is powering the load, fault conditions cause the UPS to transfer to Auto -Bypass mode instead.  
    If a fault condition exist and the UPS is running  in  Auto -Bypass mode  (on page 39 ), press the Off button to 
    transfer the UPS to Converter Off mode.  
    The load is not supported while in Converter Off mode.  
    The following fault conditions trigger Converter Off mode:  
    • Inverter AC over voltage 
    • Inverter AC under voltage  
    • Rectifier input over current  
    • Inverter output over current  
    • Inverter fault 
    • Heat sink over temperature  
    Action:  
    1. If power management software is being used, check the log files to obtain specific error information 
    to help identify  the problem.  
    For more information about the causes of a general fault condition, see the HP Power Manager user 
    guide available for download from the HP website  (http://www.hp.com/go/rackandpower
    ).  
    2.  Verify t hat no blockage of airflow to the front bezel and rear panel exists.   
    General alarm condition 
    Action: 
    1.  If power management software is being used, check the log files to obtain specific error information 
    to help identify the pr oblem.  
    For more information about the causes of a general alarm condition, see the HP Power Manager 
    user guide available for download from the HP website  (http://www.hp.com/go/rackandpower
    ).  
    2.  Check the batte ries: 
    a. Allow the UPS batteries to charge for 24 hours.   
    						
    							
     
    Troubleshooting  55 
    b.
     
    If the Battery Fault LED is red, replace the batteries  (" UPS battery replacement procedure " on 
    page  46). 
    3.  Reduce the load:  
    a. Power down the UPS  (" Powering down the UPS " on page 42). 
    b.  Remove one or more load devices to reduce the power requirements.  
    c. Wait at least 5 seconds and restart the UPS.  
    d. If the condition persists, verify that the load devices are not defective.  
    4. Allow the UPS to cool:  
    a. Power down the UPS  (" Powering down the UPS " on page 42). 
    b.  Clear vents and remove any heat sources.  
    c. Verify that the airflow around the UPS is not restricted.  
    5. Wait at least 5 minute s and restart the UPS. 
    6. If the condition persists, contact an HP authorized service representative.   
    Bypass is out of range 
    The input voltage is not within ±12 percent of nominal voltage.  
    The UPS is receiving utility power that might be unstable or in brownout conditions. The UPS continues to 
    supply power to the connected equipment. If conditions worsen, the UPS might switch to battery power.  
    Bypass out of range is only a status and does not keep the UPS from transferring to  Auto-Bypass mode  (on 
    page  39). 
    Action:  
    1. Check the input voltage and reconfigure the UPS  (" Configuring the UPS " on page 40). 
    2.  Contact a qualified electrician to verify that the utility power i s suitable for the UPS.  
    Battery condition 
    Action: 
    1.  Install the battery module. If the battery module is already installed, remove and reinsert the module.  
    2. Allow the UPS batteries to charge for 24 hours.  
    3. If the LED does not turn off,  replace the batteries  (" UPS battery replacement procedure " on page 46). 
    4.  If the condition persists, contact an HP authorized service representative.   
    UPS is on battery  
    Action: 
    1.  Save fil es and shut down connected equipment.  
    2. Allow the UPS batteries to charge for 24 hours.    
    						
    							
     
    Troubleshooting  56 
    Input voltage is out of range  
    Action: 
    1.  Check the input voltage and reconfigure the UPS  (" Configuring the UPS " on page 40). 
    2.  Contact a qualified electrician to verify that the utility power is suitable for the UPS.   
    Overtemperature condition 
    Possible cause: The UPS internal temperature is too high, or a fan has failed.  
    Action : 
    1.  Power down the UPS  (" Powering down the UPS " on page 42). 
    2.  Allow the UPS to cool:  
    a. Clear vents and remove any heat sources.  
    b. Be sure that the that the airflow around the UPS is not restricted.  
    3. Wait at least 5 minutes, and the n restart the UPS. 
    4. If the condition persists, contact an HP authorized service representative.   
    Internal UPS fault condition 
    Action : 
    1.  Power down the UPS  (" Powering down the UPS " on page 42). 
    2.  If the condition persists, contact an HP authorized service representative.   
    REPO condition  
    Action: 
    • If the remote switch is closed, then open the switch to enable power to the output receptacles.  
    • If the condition occurred while reconnecting a disconnected REPO port, then verify the polarity of the 
    REPO connector pins.  
    For more information about REPO ports, see " Connecting the REPO port (on page 21 )." 
     
    Site wiring condition  
    Action: Contact a qualified electrician to be sure that:  
    • The utility power receptacle is grounded. 
    • There is a ground wire in the UPS power cord.  
    • The line and neutral wires are not reversed in the wall outlet.    
    						
    							
     
    Troubleshooting  57 
    O verload conditi on 
    All the load LEDs are illuminated.  
    Action : 
    1.  Power down the UPS  (" Powering down the UPS " on page 42). 
    2.  Remove one or more load devices to reduce the power requirements.  
    3. Wait at least 5 seconds and restart the UPS.  
    4. If the condition persists, verify that the load devices are not defective.   
    Checksum failure error  
    A Checksum failure error occurs when executing a bad load sequence, or having an incorrect EEPROM 
    map while loading software through the serial or USB port.  
    Action:  
    1. Rerun the firmware upgrade.  
    2. If the condition persists, contact an HP authorized service representative.   
    UPS does not start  
    Action: 
    1.  Be sure that the power cord is plugged in to a utility  power receptacle.  
    2. Check the power source at the utility power receptacle.   
    Low battery shutdowns  
    Ungraceful shutdown of attached servers occurs when the UPS is in a low battery condition.  
    Action : 
    1.  Verify that the power management software is not delaying the shutdown of attached servers when 
    the UPS is in a low battery condition.  
    2. Allow the UPS batteries to charge for 24 hours.  
    3. If the Battery Fault LED is red, replace the batteries  (" UPS battery replacement procedure " on page 
    46 ). 
     
    U PS does not provide the expected backup time  
    Action: 
    1. If the Overload LED  (" UPS front panel controls " on page 8) is illuminated, remove one or more load 
    devices to reduce the power requirements.  
    2. Power down the UPS  (" Powering down the UPS " on page 42). 
    3.  Allow the UPS batteries to charge for 24  hours.  
    4. Initiate a self -test  (" Initiating a self -test " on page 41 ).  
    						
    							
     
    Troubleshooting  58 
    5.
     
    During extended power outages, save your work, power down the load devices, and then power 
    down the UPS  (" Poweri ng down the UPS " on page 42) to conserve battery power.  
     
    UPS frequently switches between utility and battery 
    power  
    Action: 
    1.  Check the input voltage and reconfigure the UPS  (" Configuring the UPS " on page 40). 
    2.  Contact a qualified electrician to verify that the utility power is suitable for the UPS.   
    						
    							
     
    Specifications  59 
    Specifications  
    UPS physical specifications      
    Parameter   Value 
    Height   8.9 cm (3.5 in) 
    Depth  63.5 cm (25 in) 
    Width  44.5 cm (17.5 in) 
    Weight  37 kg (82 lb)   
    ERM physical specifications       
    Parameter   Value 
    Height   8.9 cm (3.5 in) 
    Depth  63.5 cm (25 in) 
    Width  44.5 cm (17.5 in) 
    Weight  55 kg (122 lb)   
    UPS input specifications         
    UPS model  
    Utility voltage 
    frequency (Hz)  Available settings 
    utility voltage (VAC)   Branch circuit 
    rating (A)
     Line cord
     
    R/T3000 
    NA/JPN 50/60
      100, 110, 120, 127  30 
    Nondetachable power 
    cord with NEMA L5 -30 
    plug  
    R/T3000h 
    NA/JPN  50/60
     
    200/2081, 220, 230, 
    240   20 
    Nondetachable power 
    cord with NEMA L6 -20 
    plug  
    R/T3000 INTL  50/60  
    200/208, 220, 230, 
    240  16 
    Detachable power cord 
    with country-specific 
    plug  
     1 The output voltage is 204 for this setting.   
    UPS output spe cifications        
    UPS model   Load segment  Output receptacles  
    R/T3000 NA/JPN  1  2 x 5-20T  
       1 x L5
    -30R   
    						
    							
     
    Specifications  60 
    UPS model   Load segment  Output receptacles  
      2
      2 x 5-20T  
    R/T3000h NA/JPN  1  3 x IEC-320- C13 
       1 x IEC
    -320- C19 
       1 x L6
    -20R  
      2
      3 x IEC-320- C13 
       1 x IEC
    -320- C19 
    R/T3000 INTL  1  3 x IEC-320- C13 
       1 x IEC
    -320- C19 
      2
      3 x IEC-320- C13 
       1 x IEC
    -320- C19   
    Power protection specifications       
    UPS model  VA 
    Nominal power rating 
    (W)  Nominal voltage 
    setting
     
    R/T3000 
    NA/JPN   2880
      2700  100, 110, 120, 127 
    R/T3000h 
    NA/JPN  3300
      3000  204, 220, 230, 240 
    R/T3000 INTL 3300  3000  204, 220, 230, 240   
    Output tolerance specifications      
    Source of power  Regulation 
    Utility power (nominal 
    range)  -
    10% to +6% of nominal output voltage rating 
    (within the guidelines of the Computer 
    Business Equipment Manufacturers 
    Association)  
    Battery power   ±5% of nominal output voltage rating    
    Output feature specifications     
    Feature   Specification 
    Online efficiency  94% nominal input voltage  
    Voltage wave shape  Sine wave; 5% THD with typical PFC load  
    Surge suppression 300J via MOVs  
    Noise filtering 
    EN 55022 line filter for normal and common mode 
    use 
       
    						
    All HP manuals Comments (0)

    Related Manuals for HP Rt3000 Instruction Manual