Page 51
Power management 51 Power management Power management software HP Power Manager software ensures maximum power reliability of computer systems through comprehensive control of UPSs. The easy -to -use browser interface enables novice users to configure and manage power protecti on settings. To download the latest version of HP Power Manager software, see the HP website (http://www.hp.com/go/rackandpower ). NOTE: To install and configure the software, see the software user guide. The...
Page 52
Troubleshooting 52 Troubleshootin g LED troubleshooting Utility LED On Batter y LED On Bypas s LED Self Test LED Battery Fault LED Site Wiring Fault LED Over Temp LED Overloa d LED Condition On— Load 10% On— Load >25% On— Load >50% On— Load >75% Off UPS is in Operate mode (on page 38) Flashin g Off Off Off * * * Off UPS is in Standby mode (on page 38) Off Off On On— Load >10% On— Load >25% On— L oad >50% On— Load >75% Off...
Page 53
Troubleshooting 53 Off On Off On— Battery capacity 25% On— Batt ery capacity >50% On— Battery capacity >75% Off UPS is on battery (on page 55) —No utility power * * * Off * * Flashing * Overtemperature condition (on page 56) Off Off On Flashing Flashing Flashing Flashing Flashing Internal UPS fault condition (on page 56) Flashin g Off Off Flashing Flashing Flashing Flashing Flashing REPO condition (on page 56) * Off * Off * Flashing * *...
Page 54
Troubleshooting 54 • Overload The load is supported, but not protected while in Auto -Bypass mode. Action : 1. If power management software is b eing used, check the log files to obtain specific error information to help identify the problem. For more information about the causes of a general fault condition, see the HP Power Manager user guide available for download from the HP website (http://www.hp.com/go/rackandpower ). 2. Verify that no blockage of airflow to the front bezel and...
Page 55
Troubleshooting 55 b. If the Battery Fault LED is red, replace the batteries (" UPS battery replacement procedure " on page 46). 3. Reduce the load: a. Power down the UPS (" Powering down the UPS " on page 42). b. Remove one or more load devices to reduce the power requirements. c. Wait at least 5 seconds and restart the UPS. d. If the condition persists, verify that the load devices are not defective. 4. Allow the UPS to cool: a. Power down the UPS ("...
Page 56
Troubleshooting 56 Input voltage is out of range Action: 1. Check the input voltage and reconfigure the UPS (" Configuring the UPS " on page 40). 2. Contact a qualified electrician to verify that the utility power is suitable for the UPS. Overtemperature condition Possible cause: The UPS internal temperature is too high, or a fan has failed. Action : 1. Power down the UPS (" Powering down the UPS " on page 42). 2. Allow the UPS to cool: a. Clear vents and remove...
Page 57
Troubleshooting 57 O verload conditi on All the load LEDs are illuminated. Action : 1. Power down the UPS (" Powering down the UPS " on page 42). 2. Remove one or more load devices to reduce the power requirements. 3. Wait at least 5 seconds and restart the UPS. 4. If the condition persists, verify that the load devices are not defective. Checksum failure error A Checksum failure error occurs when executing a bad load sequence, or having an incorrect EEPROM map while...
Page 58
Troubleshooting 58 5. During extended power outages, save your work, power down the load devices, and then power down the UPS (" Poweri ng down the UPS " on page 42) to conserve battery power. UPS frequently switches between utility and battery power Action: 1. Check the input voltage and reconfigure the UPS (" Configuring the UPS " on page 40). 2. Contact a qualified electrician to verify that the utility power is suitable for the UPS.
Page 59
Specifications 59 Specifications UPS physical specifications Parameter Value Height 8.9 cm (3.5 in) Depth 63.5 cm (25 in) Width 44.5 cm (17.5 in) Weight 37 kg (82 lb) ERM physical specifications Parameter Value Height 8.9 cm (3.5 in) Depth 63.5 cm (25 in) Width 44.5 cm (17.5 in) Weight 55 kg (122 lb) UPS input specifications UPS model Utility voltage frequency (Hz) Available settings utility voltage (VAC) Branch circuit rating (A) Line...
Page 60
Specifications 60 UPS model Load segment Output receptacles 2 2 x 5-20T R/T3000h NA/JPN 1 3 x IEC-320- C13 1 x IEC -320- C19 1 x L6 -20R 2 3 x IEC-320- C13 1 x IEC -320- C19 R/T3000 INTL 1 3 x IEC-320- C13 1 x IEC -320- C19 2 3 x IEC-320- C13 1 x IEC -320- C19 Power protection specifications UPS model VA Nominal power rating (W) Nominal voltage setting R/T3000 NA/JPN 2880 2700 100, 110, 120, 127 R/T3000h NA/JPN 3300 3000...