Installation 31 4. Attach the chassis to the rack using th e supplied screws. Connecting the battery leads
Page 33
Installation 33 Connecting the ERM to the UPS 1. Re move the ERM connector bracket from the UPS. 2. Plug the ERM cable (2) in the socket (1) at the rear of the UPS.
Page 34
Installation 34 3. Attach the ERM connector bracket to the UPS as a cord retention bracket for the ERM cable. 4. To install a second ERM: a. Remove the ERM connector bracket from the first ERM. b. Plug the cable from the second ERM into the socket at the rear of the first ERM. Up to two ERM units can be connected. c. Attach the ERM connector bracket to the first ERM as a cord retention bracket for the ERM cable. Switching on the ERM circuit breaker Charging the ERM batteries...
Page 35
Installation 35 Installing the ERM as a tower Before installing the unit, review and adhere to all warnings provided in " Precautions (on page 13 )." The tower stands and associated hardware ship with the UPS. Rotating the logo badge Gently pull out the logo badge, rotate it 90 deg rees, and then replace it in the bezel. Attaching the ERM front bezel Attaching the tower conversion stands
Page 36
Installation 36 WARNING: To reduce the risk of personal injury or damage to the equipment, the tower conversion stands must be properly attached when the unit is installed as a tower. 1. Using the preinstalled screws, attach the tower conversion stands to the unit. 2. Remove a screw from the inner -most, rear corner of the UPS and ERM. 3. To attach the tower brackets: o For the front bracket, use the mounting ear screws.
Page 37
Installation 37 o For the rear bracket, use the screws removed from the chassis. Continuing the installation To continue the ERM installation, follow the instructions starting with " Connecting the ERM to the UPS (on page 33)."
Page 38
UPS operations 38 UPS operations Modes of operation The UPS has five modes of operation: • Standby mode (on page 38 ) • Operate mode (on page 38 ) • Configure mode (on page 39 ) • Battery mode (on page 39 ) • Auto -Bypass mode (on page 39 ) S tandby mode In Standby mode: • No power is available at the UPS output receptacles. • The UPS charges the batteries as necessary. The UPS can be placed in Standby mode when the UPS is in Ope rate mode (on page 38 ). To place the UPS in...
Page 39
UPS operations 39 For the location of buttons, see "UPS front panel controls (on page 8 )." For the location of LEDs, see " UPS front panel LED indicators (on page 8 )." Configure mode The UPS can be placed in Configure mode while in Operate mode (on page 38 ), Bat tery mode (on page 39 ) or Standby mode (on page 38 ). In Configure mode: • Power is available at the UPS receptacles when entered from Operate mode. Power is not available at the receptacles when entered...
Page 40
UPS operations 40 NOTE: If the On and Off buttons are simultaneously pressed, the Off button has priority over the On button. Button Assertion time Audible alarm Mode before assertion Utility present ? Action On 0.5 seconds Every 0.5 seconds until the but ton is released Standby Yes Energizes the load and resets the bypass entry count to 0 Operate Yes Resets the bypass entry count to 0 Auto -Bypass Yes Clears the UPS On audible alarms,...