Page 51
Maintenance 51 6. Double- click the port that is assigned to your USB to serial converter device. This port is usually named with the device manufacturer's name followed by one of the following: o USB t o Serial Bridge (COM 4) o USB Serial port o Communications Port (COM1) The Port Properties screen appears. 7. Click the Port Settings tab. The Port Settings screen appears. 8. Click Restore Defaults. The following default settings appear: o Bits per second: 9600 o Data Bits:...
Page 52
Maintenance 52 8. Verify that the Device Manager screen shows that the USB to serial converter is assigned to COM 1, and that the other USB device is assigned to a different port. If the Device Manager screen does not automatically refresh to show the change: a. Click Action . The Action Menu appears. b. Click Scan for hardware changes to refresh the screen and display the changes.
Page 53
Power management 53 Power management Power Protector software HPE Power Protector software ensures maximum power reliability of computer systems through comprehensive control of UPSs. The easy -to -use browser interface enables novice users to configure and manage power protection settings. To download the latest version of HPE Power Protector software, see the Hewlett Packard Enterprise website (http://www.hpe.com/info/rackandpower ). NOTE: To install and configure the software, see...
Page 54
T roubleshooting 54 Troubleshooting LED troubleshooting Utility LED On Batter y LED On Bypas s LED Self Test LED Battery Fault LED Site Wiring Fault LED Over Temp LED Overloa d LED Condition On —Lo ad 10% On—Loa d >25% On—Loa d >50% On—Loa d >75% Off UPS is in Operate mode (on page 40) Flashing Off Off Off * * * Off UPS is in Standby mode (on page 40) Off Off On On—Loa d >10% On—Loa d >25% On—Loa d >50% On—Loa d >75% Off UPS is in Auto-Bypass mode...
Page 55
Troubleshooting 55 Off On Off On—Batt ery capacity 25% On—Batt ery capacity >50% On—Batt ery capacity >75% Flashing Overload condition (on page 58)—UPS power capacity is exceeded while on battery with no other faults Off On Off Off Off Off Flashing Flashing Overload condition (on page 58)—UPS power capacity is exceeded while on battery with overtemperature fault Off Flashing Off Flashing Flashing Flashing Flashing Flashing Unit is powering down Flashing Flashing Flashing...
Page 56
Troubleshooting 56 •Rectifier input over current •Inverter output over current •Inverter fault •Heat sink over temperature Action: 1.If power management software is being used, check the log files to obtain specific error information to help identify the problem. For more information about the causes of a general fault condition, see the HPE Power Manager user guide available for download from the Hewlett Packard Enterprise website ( http://www.hpe.com/info/rackandpower ). 2.Verify that no...
Page 57
Troubleshooting 57 2. Contact a qualified electrician to verify that the utility power is suitable for the UPS. Battery condition Action: 1. Install the battery module. If the battery module is already installed, remove and reinsert the module. 2. Allow the UPS batteries to charge for 24 hours. 3. If the LED does not turn off, replace the batteries (" UPS battery replacement procedure " on page 47). 4. If the condition persists, contact a Hewlett Packard Enterprise authorized...
Page 58
Troubleshooting 58 •If the condition occurred while reconnecting a disconnected REPO port, then verify the polarity of the REPO connector pins. For more information about REPO ports, see "Connecting the REPO port (on page 20)." Site wiring condition Action: Contact a qualified electrician to be sure that: •The line and neutral wires are not reversed in the wall outlet. •A ground wire connection does not exist. Overload condition All the load LEDs are illuminated. Action : 1.Power...
Page 59
Troubleshooting 59 UPS does not provide the expected backup time Action: 1. If the Overload LED (" UPS front panel controls " on page 7) is illuminated, remove one or more load devices to reduce the power requirements. 2. Power down the UPS (" Powering down the UPS " on page 44). 3. Allow the UPS batteries to charge for 24 hours. 4. Initiate a self -test (" Initiating a self -test " on page 43). 5. During extended power outages, save your work, power down the...
Page 60
Specifications 60 Specifications UPS physical specifications Parameter Value Height 8.9 cm (3.5 in) Depth 63.5 cm (25 in) Width 44.5 cm (17.5 in) Weight 37 kg (82 lb) ERM physical specifications Parameter Value Height 8.9 cm (3.5 in) Depth 63.5 cm (25 in) Width 44.5 cm (17.5 in) Weight 45 kg (100 lb) UPS input specifications UPS model Utility voltage frequency (Hz) Available settings utility voltage (VAC) Branch circuit rating (A) Line cord R/T3000...