Honeywell Tz 4 Manual
Here you can view all the pages of manual Honeywell Tz 4 Manual. The Honeywell manuals for Control panel are available online for free. You can easily download all the documents as PDF.
Page 11
TZ-4 TOTALZONE® ZONE CONTROL PANEL 11 68-0259-1 Fig. 16. Wiring conventional heating and cooling equipment to TZ-4 panel. Heat Pump Equipment See Fig. 17-22 for heat pump wiring. Refer to manufacturer instructions for additional wiring details and substitute the TZ-4 equipment terminals for the thermostat terminals shown. — Connect the changeover relay to O/B equipment terminal. — Set switch number 5-7 to on for O (cool) changeover, or to off for B (heat) changeover. — Set switch number 5-1 to...
Page 12
TZ-4 TOTALZONE® ZONE CONTROL PANEL 68-0259-1 12 Fig. 17. Wiring single-stage heat pump with auxiliary heat. Fig. 18. Wiring single-stage heat pump with separate auxiliary and emergency heat. Two-speed Compressor: Wire the first stage compressor to Y1 and the second stage compressor to Y2. If the same heat source is used for auxiliary heat and emergency heat: — Wire a jumper from W3/AUX (auxiliary heat) to W1/E (emergency heat), see Fig. 19. If auxiliary heat is separate from emergency heat: — Wire...
Page 13
TZ-4 TOTALZONE® ZONE CONTROL PANEL 13 68-0259-1 Fig. 21. Dual Fuel with single-stage heat pump and single- stage fossil fuel. Fig. 22. Dual fuel with two-stage heat pump and one- or two-stage fossil fuel. Water Source Heat Pumps Wire the equipment, as applicable, to the TZ-4 as shown in Fig. 17-19. Refer to manufacturer instructions for additional wiring instructions and substitute the TZ-4 equipment terminals for the thermostat terminals shown. — Wire first stage compressor to Y1, second...
Page 14
TZ-4 TOTALZONE® ZONE CONTROL PANEL 68-0259-1 14 Purge Mode At the end of every call for heat or cool, the panel enters a Purge mode that holds open the calling zone damper for two (default) or three and one-half minutes. During this time, the panel or the HVAC equipment can be configured to operate the fan. The Purge LED lights to signal that the system is in the Purge mode. Pressing the purge override button overrides the Purge mode. Unless there is a new call for heat or cool during the Purge...
Page 15
TZ-4 TOTALZONE® ZONE CONTROL PANEL 15 68-0259-1 HEAT PUMP OPERATION The panel can control single- or two-stage heat pumps with or without auxiliary heat. Set DIP switch 5-1 to Off for heat pump control. This energizes equipment terminal Y1 on a call for first stage heat or cool. If second stage is configured to operate with DIP switch 4-1 and 4-2, Y2 energizes to call for second stage compressor. When in heat pump mode, the panel energizes the fan with a call for heat and a call for cool....
Page 16
TZ-4 TOTALZONE® ZONE CONTROL PANEL 68-0259-1 16 Thermostat Operation Conventional Thermostats Conventional (R,W,Y,G) heat/cool thermostats can be used with the TZ-4 to control single or multi-stage gas, electric or oil systems and heat pumps with auxiliary heat. The panel can be configured to control second stage heat and cool and third stage heat using a 5-60 minute timer, or staging can be controlled by the percentage of zones calling. When using conventional thermostats on heat pump...
Page 17
TZ-4 TOTALZONE® ZONE CONTROL PANEL 17 68-0259-1 Use DIP switch 5-2 to change cooling limit settings: Zone-A-Lone Switch When the Zone-A-Lone switch is in the occupied (up) position and the OC/OC terminals are not used, the system functions as a zone control system. When switched to the unoccupied (down) position, all dampers are opened and all requests for heat, cool, or fan, except from zone one, are not honored. The zone one thermostat becomes the controlling thermostat for the entire system....
Page 18
TZ-4 TOTALZONE® ZONE CONTROL PANEL 68-0259-1 18 TROUBLESHOOTING Table 8. Troubleshooting. SymptomPossible CauseAction No LEDs are IlluminatedNo power to the board.Check for 24 Vac (±10%) across R and C. Transformers out of phaseIf 48 Vac across R and T1, reverse T1 and T2 wires. Shorted wire.Check thermal circuit breaker. If hot, a short exists in thermostat or damper wiring. Damper LEDs on, but no other LEDs illuminated.Insufficient voltage.Check for 24 Vac (±10%) across R and C. Incorrect...
Page 19
TZ-4 TOTALZONE® ZONE CONTROL PANEL 19 68-0259-1 Table 9. LED Indicators. LEDColorIlluminatedNot IlluminatedFlashing HeatRedHeat call.No heat calls.High limit reached. CoolGreenCool call.No cool calls.Low limit reached. PurgeAmberPurge mode.Not in Purge mode.•DATS failure: slow flash. •OT failure: fast flash. •DATS and OT failure: alternating fast and slow flash. FanGreenFan only call.No fan only call.— EM HeatRedEmergency Heat mode or dual-fuel mode.Not in emergency Heat mode or dual-fuel mode.— Zones...
Page 20
68-0259-1 G.H. Rev. 12-02 www.honeywell.com/yourhome Automation and Control Solutions Honeywell Honeywell Limited-Honeywell Limitée 1985 Douglas Drive North 35 Dynamic Drive Golden Valley, MN 55422 Scarborough, Ontario M1V 4Z9 TZ-4 TOTALZONE® ZONE CONTROL PANEL