    							PRODUCT DATA
    68-0259-1
    ® U.S. Registered Trademark
    Copyright © 2002 Honeywell •  All Rights Reserved 
    TZ-4 TotalZone® Zone Control Panel
    APPLICATION
    The TZ-4 TotalZone Zone Control Panel controls single-stage, 
    multi-stage, conventional or heat pump heat/cool equipment. 
    It controls 2, 3 or 4 zones, and is expandable up to 32 zones 
    with optional TotalZone® Add-A-Zone™ Four Zone Control 
    Panel.
    FEATURES
    • Up to three stages heat and two stages cooling can be 
    controlled by thermostat, built-in timer, or based on 
    the percentage of zones calling.
    • Controls single-stage, multi-stage, conventional, heat 
    pump or dual-fuel equipment.
    • Controls up to four zones and can be expanded up to 
    32 zones with Add-A-Zone Control Panels.
    • Uses Honeywell four-wire, single-stage, multi-stage, or 
    select heat pump thermostats.
    • Zone-A-Lone central setback feature.
    • Purge timer protects equipment between calls for heat 
    or cool with choice of panel or HVAC equipment 
    controlled fan.
    • System and zone damper LEDs indicate system and 
    damper status.
    • Individual zone fan control.
    • Discharge Air Temperature Sensor for capacity control 
    with adjustable high and low limits.
    • Thermal circuit breaker protects panel and transformer 
    from damage if miswired.
    For Internet access: 
    www.honeywellzoning.com
    For technical support, call 1-800-828-8367.
    To download Zoning literature: http://hbctechlit.honeywell.com
    Contents
    Application ......................................................................... 1
    Features ............................................................................ 1
    Specifications .................................................................... 2
    Installation ......................................................................... 4
    Startup and Checkout ........................................................ 12
    Operation........................................................................... 12
    Troubleshooting ................................................................. 17 
    						
    							TZ-4 TOTALZONE® ZONE CONTROL PANEL
    68-0259-1 2
    SPECIFICATIONS
    Input Ratings: 
    Voltage: 20-30 Vac, 50/60 Hz.
    Power: 13 VA, nominal.
    Output Ratings:
    1.5A run, 200,000 cycles (30 Vac). 3.5 inrush.
    1.5A run, 100,000 cycles (30 Vac) 7.5A inrush.
    Humidity Ratings: 
    5 to 90 percent RH, non-condensing.
    Temperature Ratings:
    Shipping: -20° to 120°F.
    Operating: -40° to 150°F.
    Dimensions:  10-3/4 in. H x 12-3/4 in. W x 1-7/8 in. D.
    See Fig. 1.
    Mounting:  Mounts with four 1 in. no. 8 screws (provided) 
    through holes in cabinet back. Wall anchors are provided.Wiring:  18-gauge wire for all equipment and system 
    connections.
    Wiring Connections:
    Thermostat: R, C, W1/E, W2, W3/AUX, Y1, Y2, G, L, O/B
    Dampers: M6 (Closed); M4 (Open); M1 (Common). 
    Discharge Air Temperature Sensor (C7735A1000); DATS, 
    DATS.
    Zone-A-Lone: OC, OC.
    Outdoor Temperature: OT, OT.
    Transformer 1: R (hot), C (common).
    Transformer 2: T1 (hot), T2 (common).
    Equipment: Rc-Rh, W1/E, W2, W3/AUX Y1, Y2, G, O/B.
    Thermostats (See Table 1):
    Most conventional four-wire (R,W,Y,G) thermostats can be 
    used to control conventional, heat pump, or multi-stage 
    equipment. 
    Manual or automatic changeover switching thermostats can 
    be used. 
     Multi-stage or select heat pump thermostats can also be 
    used.
    Fig. 1. TZ-4 dimensions in in. (mm).
    M20516
    10-3/4
    (273)
    12-3/4
    (273)1-7/8
    (47) 
    						
    							TZ-4 TOTALZONE® ZONE CONTROL PANEL
    3 68-0259-1
    aHeat pump thermostat with single Y first-stage terminals. See Heat Pump Thermostats section and Fig. 6.bMulti-stage and heat pump thermostats are not required to control multi-stage and heat pump systems with TotalZone. They are 
    used only when second stage or emergency heat control from the zone thermostat is needed.
    cThe Y594R1243 must be wired to the panel using the B terminal for changeover.dCut thermostat second-stage variable heating anticipator wire (gray).eCut thermostat first-stage fixed heating anticipator wire (bare) and second-stage variable heating anticipator wire (gray).fCut thermostat second-stage cooling anticipator wire (lowest bare wire).
    Recommended Dampers (See Table 2):
    Ten ZD or ARD dampers maximum connected to each panel 
    and a maximum of five dampers per zone when using two 
    40 VA transformers. 
    Use SDCR and 40 VA transformer for additional dampers 
    required on one zone.
    Dampers are connected to M1 Common, M4 Open, and M6 
    Closed (see Fig. 7-10 for hookups).
    Accessories: For required accessories, see Table 3. Table 1. Recommended Thermostats.
    System Non-Programmable Programmable
    Single Stage
    T87F1859/Q539A1014
    T87F4010/Q539A4026
    T8501D1046
    T8400C1016
    T8400C1040
    T8400C1099T8601D2027
    T8600D2069
    T8600D2028
    T8601D2019
    T8602D2018
    T8602D2000
    T8000C1002
    T8000C1010
    T8001C1019
    PC8900/W8900A/C
    Heat Pumpb 
    Y594R1243a,c,d
    Y594G1252a,e
    T8411R1002
    T8411R1028
    T8611G2051
    T8011R1006
    T8011R1014
    Multi-Stageb 
    Y594D1347f
    T8524D1015
    T8624D2004
    T8624D2012
    Motor Terminal Damper Action
    Common/M1Common
    Open/M4Power Open
    Closed/M6Power Close
    Table 2. Recommended Dampers.
    Honeywell Damper TypeRoundRectangular
    Power-open/power-closed (for 
    systems > 2000 cfm)MARDD643 using 
    ML6161 
    Motor 
    Actuator
    Spring-open/power-closed (for 
    systems 
    						
    							TZ-4 TOTALZONE® ZONE CONTROL PANEL
    68-0259-1 4
    INSTALLATION
    Mounting
    CAUTION
    Equipment Damage Hazard. 
    Do not mount TZ-4 inside HVAC equipment
    Mount only on wall or on cold air return.
    Identifying DIP Switches
    This panel has two banks of DIP switches, DIP switch 4 (S4) 
    and DIP switch 5 (S5), see Fig 15. Each bank has eight 
    individual switches that are identified by two numbers; the first 
    number is the bank number (4 or 5) and the second number 
    identifies the individual switch. For example, DIP 5-1 is bank 
    5, switch 1.
    1.Mount the thermostats in each zone of the living space 
    using the installation instructions provided with each 
    thermostat.
    2.Mount the dampers in the ductwork using the installa-
    tion instructions provided with each damper.3.Mount the TZ-4 zone panel near the HVAC equipment; 
    (on a wall or on the cold-air return). See Fig. 2.
    4.Level the TZ-4 for appearance only.
    Wiring
    CAUTION
    Vo l ta g e  H a z a r d .  
    Can cause electrical shock or equipment damage.
    Disconnect power before continuing installation.
    Wiring must comply with applicable codes, ordinances, and 
    regulations.
    1.Connect thermostats as shown in Fig. 3-6. 
    2.Connect dampers as shown in Fig. 7-10.
    3.Connect C7735A Discharge Air Temperature Sensor 
    (not supplied) to the DATS terminals. The wires are not 
    polarized. See Fig. 13.
    4.Connect Add-A-Zone panels (if used) to the AZ1 and 
    AZ2 terminals. 
    5.Connect the HVAC equipment to the EQUIP terminals 
    on the panel. See Fig. 15-21.
    6.Connect a 40 VA, 24 volt transformer to R (hot) and C 
    (common). This must be a dedicated transformer and 
    each TAZ-4 board also requires a transformer. See Fig. 
    12.
    7.The auxiliary 40 VA 24-volt transformer can be con-
    nected to T1 and T2 if additional power for dampers is 
    required. This second transformer is not required; how-
    ever, total power consumption of panel and damper is 
    limited to 40VA without it.
    Fig. 2. TZ-4 mounting location. Table 3. Required Accessories (Not Supplied).
    AccessoryDescriptionBypass Rating
    (cfm)
    40 VA 
    transformers AT140D1046 
    (PMT-40)—
    Capacity 
    protectorC7735A1000—
    Outdoor 
    Temperature 
    Sensor
    (Required for 
    dual-fuel 
    applications)C7089B1000—
    Round static 
    pressure 
    regulator 
    damperSPRD7
    SPRD8
    SPRD9
    SPRD10
    SPRD12
    SPRD14
    SPRD16300 
    400 
    600 
    750 
    1200 
    1800 
    2400 
    Rectangular 
    static pressure 
    regulator 
    damperSPRD12x8
    SPRD12x10
    SPRD12x12
    SPRD20x8
    SPRD20x10
    SPRD20x121000 
    1200 
    1400 
    1600 
    2000 
    3000 
    M20517
    WATER 
    HEATERTZ-4E
    LEC
    TR
    ONIC
     AIR 
    CL
    EA
    N
    ER
    RETURNAIR
    TZ-4
    OPTIONAL
    LOCATION
    FURNACE 
    OR BOILER
    HIGH
     EFFICIENCY
    AIR CLEANER 
    						
    							TZ-4 TOTALZONE® ZONE CONTROL PANEL
    5 68-0259-1
    Wiring Diagrams (Fig. 3 and 4)
    Conventional Thermostats
    Conventional (RWYG) thermostats can be used to control 
    conventional, multi-stage, and heat pump equipment. If the 
    thermostat has a common terminal, it is wired to C on the 
    panel, see Fig. 3. A multi-stage thermostat is wired with the 
    second and third stage of heat to W2 and W3 on the panel 
    thermostat connections, and with the second stage of cooling 
    to Y2. Leave the zone O/B thermostat jumper on the TZ-4 
    disconnected. See Single and Multi-Stage Operation in the 
    Operation section for instructions on staging the TZ-4.
    The PC8900 with the W8900A or W8900C can be used as a 
    zone thermostat. See Fig. 4 for hookup. This thermostat can 
    be used to control up to 2 heat and 2 cool stages of 
    conventional equipment. When used to control heat pump 
    equipment, the W8900A is recommended.
    Connect a jumper on the W8900 from Rc to Rh as shown in 
    Fig. 4. Wire terminals R and C to a transformer. If the system 
    current draw is within specifications, the R and C on the 
    W8900 could alternately be connected to R and C on the    
    TZ-4. The PC8900/W8900 draws 5 VA.
    Fig. 3. Typical single-stage thermostat wiring.
    M20509B
    G
    C
    R
    Y
    W
    COMMON (C) TERMINAL IS USED ONLY BY THERMOSTATS
    THAT REQUIRE A COMMON WIRE.
    MULI-STAGE THERMOSTATS ARE WIRED SIMILARLY BUT WITH
    Y2 AND W2 USED FOR SECOND STAGE COOL AND HEAT.
    THIRD STAGE OF HEAT (W3) CAN BE WIRED TO W3/AUX.
    LEAVE O/B JUMPER ON TZ-4 DISCONNECTED.TZ-4 THERMOSTAT
    CONNECTORS
    TYPICAL SINGLE STAGE
    THERMOSTAT WIRING1
    2
    3
    1
    3
    2 
    						
    							TZ-4 TOTALZONE® ZONE CONTROL PANEL
    68-0259-1 6
    Fig. 4. PC8900 with W8900A,C Thermostat wiring.
    Heat Pump Thermostats
    Select a heat pump thermostat from Table 1. If the thermostat 
    selected has a separate Y1 and W1 wire, as shown in Fig. 5,   
    leave the zone O/B thermostat type jumper on the TZ-4 
    disconnected, and wire as shown in Fig. 5.If the PC8900/W8900 /Thermostat is used in a heat pump 
    application, use the W8900A, not the W8900B, and wire as 
    shown in Fig. 4.
    M20508B
    W8900A/C IS RECOMMEDED FOR CONVENTIONAL AND HEAT PUMP APPLICATIONS. THE W8900B CANNOT
    SWITCH THE PANEL TO EMERGENCY HEAT.
    LEAVE O/B JUMPER ON TZ-4 DISCONNECTED.TZ-4 THERMOSTAT
    CONNECTORS1
    2
    1
    S1
    S
    T1
    T
    OUT
    OUT
    LED
    G
    Y2
    Y1
    W1
    W2
    1
    2
    3
    4
    GND
    C
    R
    RH
    RC
    HUM
    HUM
    VNT
    VNT
    W8900A,C PC8900
    CO2
    1234
    2
    24 VAC
    120 VAC 
    						
    							TZ-4 TOTALZONE® ZONE CONTROL PANEL
    7 68-0259-1
    .
    Fig. 5. Heat pump thermostat with separate Y1 and W1 
    terminals and multi-stage thermostat wiring.
    If the thermostat selected from Table 1 has a single Y terminal 
    for first stage heat and cool, wire as shown in Fig. 6. Wire 
    either O or B (not both) from the thermostat to the O/B 
    terminal on the panel. Locate the O/B thermostat jumper on 
    the TZ-4 near each zone thermostat wiring terminal. Connect 
    the jumper if O was used or leave disconnected if B was used. 
    Connect second stage, auxiliary heat to W2.
    When using two- or three-stage heat pump thermostats with 
    single Y first-stage hookup, place a jumper from W2 to Y2 on 
    the TZ-4 thermostat connections. See Fig. 7.
    See Single and Multi-Stage Operation in the Operation 
    section for instructions on staging the TZ-4.ARD or ZD Dampers
    Wire the ARD or ZD Damper to the panel as shown in Fig. 8. 
    Multiple dampers can be wired in parallel. Use these dampers 
    on systems up to 2000 cfm.
    AOBD Dampers
    Wire the AOBD dampers to the panel as shown in Fig. 9. Two 
    AOBD can be wired in tandem as shown in Fig. 10. More than 
    two AOBD dampers require the Slave Damper Control Relay 
    (SDCR).
    Fig. 6. Heat pump thermostat with single Y thermostat 
    wiring.
    M20506B
    G
    C
    R
    Y W1L
    W2
    E
    B
    O
    COMMON (C) TERMINAL IS USED ONLY BY THERMOSTATS
    THAT REQUIRE A COMMON WIRE.
    JUMP E TERMINAL TO W1 FOR EMERGENCY HEAT.
    LEAVE O/B JUMPER ON TZ-4 DISCONNETED.TZ-4 THERMOSTAT
    CONNECTORS
    HEAT PUMP THERMOSTAT WITH
    SEPARATE Y1 AND W1 
    THERMOSTAT WIRING1
    2
    3
    12
    3
    M20507B
    G
    C
    R
    Y1 W1L
    W2
    E
    B
    O
    COMMON (C) TERMINAL IS USED ONLY BY THERMOSTATS
    THAT REQUIRE A COMMON WIRE.
    NORMALLY, CONNECT E ON THERMOSTAT TO W1 ON PANEL. 
    ALTERNATIVELY, INSTALL JUMPER FROM E TO Y1 ON 
    THERMOSTAT.
    CONNECT O/B TERMOSTAT JUMPER ON TZ-4 PANEL IF
    USING O FROM THERMOSTAT; DISCONNECT IF USING B.TZ-4 THERMOSTAT
    CONNECTORS
    HEAT PUMP THERMOSTAT WITH
    SINGLE Y THERMOSTAT WIRING1
    2
    3
    1
    3
    2 
    						
    							TZ-4 TOTALZONE® ZONE CONTROL PANEL
    68-0259-1 8
    Fig. 7. Heat pump thermostat with 3-stage heat, 2-stage 
    cool single Y thermostat wiring.
    Fig. 8. Wiring ARD or ZD damper to panel.Fig. 9. Wiring AOBD damper to panel.
    Fig. 10. Wiring two AOBD dampers in parallel.
    MARD Dampers or Dampers Using an ML6161 Motor 
    Actuator
    Wire the MARD Damper or ML6161 Actuator to the panel as 
    shown in Fig. 11. These are floating control actuators, but are 
    controlled as two-position devices on the TZ-4 panel. Multiple 
    dampers can be wired in parallel. 
    The ML6161 Motor causes the damper LED to illuminate 
    green constantly. WIre a relay as shown in Fig. 12 to restore 
    damper position indication.
    Use the MARD or D643 with the ML6161 on systems above 
    2000 cfm.
    Fig. 11. Wiring MARD Damper or ML6161 Actuator to 
    panel. M20891
    G
    C
    R
    Y1 Y2L
    W3
    E
    B
    O
    COMMON (C) TERMINAL IS USED ONLY ON THERMOSTATS
    THAT REQUIRE A COMMON WIRE.
    ALTERNATIVELY, JUMPER E THERMOSTAT TERMINAL TO Y1 FOR 
    EMERGENCY HEAT.
    CONNECT O/B JUMPER ON TZ-4 WHEN USING O OR DISCONNECT
    WHEN USING B FOR CHANGEOVER.
    FIELD INSTALLED JUMPER FROM Y2 TO W2 ON PANEL 
    THERMOSTAT CONNECTIONS.TZ-4
    THERMOSTAT
    CONNECTORS
    HEAT PUMP THERMOSTAT WITH
    SINGLE Y THERMOSTAT WIRING1
    2
    3
    4
    14
    3
    2
    4M6 M4
    M1
    56
    123Z
    X
    DAMPER MOTOR FIELD JUMPER
    M19067
    MOTOR TERMINALS
    4M6 M4
    M1
    56
    12
    3
    DAMPER MOTORS
    M19068
    MOTOR TERMINALS
    456
    123Z
    XZ
    X
    FIELD JUMPER
    M1 M4
    M20136A
    ZONE PANEL
    CONNECTIONS
    M6
    CW
    COM
    CCW MARD 
    						
    							TZ-4 TOTALZONE® ZONE CONTROL PANEL
    9 68-0259-1
    Fig. 12. MARD or ML6161 Damper Motor Actuator using 
    R8222 Relay wiring.
    Transformer
    1.Wire the transformers to the panel as shown in Fig. 13. 
    One 40 VA, 24 Vac transformer controls up to five ARD 
    or ZD dampers.
    2.Connect the transformer to terminals R and C. 
    3.Add the auxiliary transformer if six to ten ARD or ZD 
    dampers are used. 
    a. Wire auxiliary transformer to terminals T1 and T2. 
    b. It is important that these two transformers be wired 
    in phase. If they are wired out of phase, the internal 
    circuit breaker trips and the board de-powers. If this 
    occurs, remove power, correct the wiring and 
    restore power to the board.
    IMPORTANT
    If more than five dampers are required for one zone 
    or if more than ten dampers are used for the TZ-4, 
    use the Slave Damper Control Relay (SDCR). Fig. 13. Wiring transformer(s) to panel.
    Discharge Air and Outdoor Temperature Sensors
    Wire the C7735A Discharge Air Temperature Sensor (DATS) 
    to the panel as shown in Fig. 14. The Purge LED (yellow) 
    flashes in all modes except purge if no DATS is connected to 
    the TZ-4 or if there is a problem with the DATS or the wiring. 
    For dual fuel applications, connect the C7089 Outdoor 
    Temperature Sensor as shown in Fig. 14.
    Fig. 14. Wiring C7735A Discharge Air Temperature Sensor 
    (DATS) to panel. 
    Add-A-Zone Panel
    Remove power from TZ-4 before connecting AZ-1 and AZ-2.
    Wire the Add-A-Zone (TAZ-4) Panel to the TotalZone (TZ-4) 
    Panel as shown in Fig.15. Up to seven TAZ-4 Panels can be 
    wired to one TZ-4 panel to control up to 32 zones. 
    COM
    CCW
    CWML6161
    R8222 RELAY ZONE CONTROL PANEL
    DAMPER TERMINALS
    M20548A
    M6M4 M1RC
    R
    C
    T1
    T2
    C
    R C R
    24 VAC, 40 VA 
    Transformer
    (Required if
    more than
    four dampers) 24 VAC, 40 VA 
    Transformer
    DAMPER
    XFRM
    PANEL
    XFRM
    M20518
    M20519
    DATS
    DATS DATSOT
    OT OT
    Sensor 
    						
    							TZ-4 TOTALZONE® ZONE CONTROL PANEL
    68-0259-1 10
    Fig. 15. TotalZone Add-A-Zone wiring.
    Conventional Equipment
    Wire the heating and cooling equipment to the equipment 
    terminals on the TZ-4 Panel as shown in Fig. 16. 
    Conventional Equipment: Set DIP switch 5-1 to on.
    Electric Furnaces: Set DIP switch 5-6 to off to energize the fan 
    with a call for heat.
    Hydro-Air: Wire the zone valve or circulator relay to the Rh 
    and W1 equipment terminals. (If the circulator relay has 
    powered terminals, remove the Rh Rc jumper.) Set DIP switch 
    5-6 to off to energize the fan with a call for heat.
    Oil Heat: Wire the oil primary T, T terminals to the Rh and W 
    equipment terminals. (If the oil primary has powered 
    terminals, remove the Rh Rc jumper.)
    Multi-Stage: Wire the equipment as shown in Fig. 16 using the 
    W2 and W3 terminals for second and third stages of heat. 
    Wire Y2 for second stage of cooling.
    See Single and Multi-Stage Operation in the Operation 
    section to configure DIP switches 4-1, 4-2, 4-3, and 4-4.
    M20362
    TotalZone Panel
    TotalZone
    Add-A-Zone Panel
    AZ1 DIP-SWITCHES
    AZ2AZ1
    AZ2
    AZ1
    AZ2TO NEXT
    ADD-A-ZONE
    PA N E L
    54321O
    N 
    						