PRODUCT DATA 68-0259-1 ® U.S. Registered Trademark Copyright © 2002 Honeywell • All Rights Reserved TZ-4 TotalZone® Zone Control Panel APPLICATION The TZ-4 TotalZone Zone Control Panel controls single-stage, multi-stage, conventional or heat pump heat/cool equipment. It controls 2, 3 or 4 zones, and is expandable up to 32 zones with optional TotalZone® Add-A-Zone™ Four Zone Control Panel. FEATURES • Up to three stages heat and two stages cooling can be controlled by thermostat, built-in timer, or based on the percentage of zones calling. • Controls single-stage, multi-stage, conventional, heat pump or dual-fuel equipment. • Controls up to four zones and can be expanded up to 32 zones with Add-A-Zone Control Panels. • Uses Honeywell four-wire, single-stage, multi-stage, or select heat pump thermostats. • Zone-A-Lone central setback feature. • Purge timer protects equipment between calls for heat or cool with choice of panel or HVAC equipment controlled fan. • System and zone damper LEDs indicate system and damper status. • Individual zone fan control. • Discharge Air Temperature Sensor for capacity control with adjustable high and low limits. • Thermal circuit breaker protects panel and transformer from damage if miswired. For Internet access: www.honeywellzoning.com For technical support, call 1-800-828-8367. To download Zoning literature: http://hbctechlit.honeywell.com Contents Application ......................................................................... 1 Features ............................................................................ 1 Specifications .................................................................... 2 Installation ......................................................................... 4 Startup and Checkout ........................................................ 12 Operation........................................................................... 12 Troubleshooting ................................................................. 17
TZ-4 TOTALZONE® ZONE CONTROL PANEL 68-0259-1 2 SPECIFICATIONS Input Ratings: Voltage: 20-30 Vac, 50/60 Hz. Power: 13 VA, nominal. Output Ratings: 1.5A run, 200,000 cycles (30 Vac). 3.5 inrush. 1.5A run, 100,000 cycles (30 Vac) 7.5A inrush. Humidity Ratings: 5 to 90 percent RH, non-condensing. Temperature Ratings: Shipping: -20° to 120°F. Operating: -40° to 150°F. Dimensions: 10-3/4 in. H x 12-3/4 in. W x 1-7/8 in. D. See Fig. 1. Mounting: Mounts with four 1 in. no. 8 screws (provided) through holes in cabinet back. Wall anchors are provided.Wiring: 18-gauge wire for all equipment and system connections. Wiring Connections: Thermostat: R, C, W1/E, W2, W3/AUX, Y1, Y2, G, L, O/B Dampers: M6 (Closed); M4 (Open); M1 (Common). Discharge Air Temperature Sensor (C7735A1000); DATS, DATS. Zone-A-Lone: OC, OC. Outdoor Temperature: OT, OT. Transformer 1: R (hot), C (common). Transformer 2: T1 (hot), T2 (common). Equipment: Rc-Rh, W1/E, W2, W3/AUX Y1, Y2, G, O/B. Thermostats (See Table 1): Most conventional four-wire (R,W,Y,G) thermostats can be used to control conventional, heat pump, or multi-stage equipment. Manual or automatic changeover switching thermostats can be used. Multi-stage or select heat pump thermostats can also be used. Fig. 1. TZ-4 dimensions in in. (mm). M20516 10-3/4 (273) 12-3/4 (273)1-7/8 (47)
TZ-4 TOTALZONE® ZONE CONTROL PANEL 3 68-0259-1 aHeat pump thermostat with single Y first-stage terminals. See Heat Pump Thermostats section and Fig. 6.bMulti-stage and heat pump thermostats are not required to control multi-stage and heat pump systems with TotalZone. They are used only when second stage or emergency heat control from the zone thermostat is needed. cThe Y594R1243 must be wired to the panel using the B terminal for changeover.dCut thermostat second-stage variable heating anticipator wire (gray).eCut thermostat first-stage fixed heating anticipator wire (bare) and second-stage variable heating anticipator wire (gray).fCut thermostat second-stage cooling anticipator wire (lowest bare wire). Recommended Dampers (See Table 2): Ten ZD or ARD dampers maximum connected to each panel and a maximum of five dampers per zone when using two 40 VA transformers. Use SDCR and 40 VA transformer for additional dampers required on one zone. Dampers are connected to M1 Common, M4 Open, and M6 Closed (see Fig. 7-10 for hookups). Accessories: For required accessories, see Table 3. Table 1. Recommended Thermostats. System Non-Programmable Programmable Single Stage T87F1859/Q539A1014 T87F4010/Q539A4026 T8501D1046 T8400C1016 T8400C1040 T8400C1099T8601D2027 T8600D2069 T8600D2028 T8601D2019 T8602D2018 T8602D2000 T8000C1002 T8000C1010 T8001C1019 PC8900/W8900A/C Heat Pumpb Y594R1243a,c,d Y594G1252a,e T8411R1002 T8411R1028 T8611G2051 T8011R1006 T8011R1014 Multi-Stageb Y594D1347f T8524D1015 T8624D2004 T8624D2012 Motor Terminal Damper Action Common/M1Common Open/M4Power Open Closed/M6Power Close Table 2. Recommended Dampers. Honeywell Damper TypeRoundRectangular Power-open/power-closed (for systems > 2000 cfm)MARDD643 using ML6161 Motor Actuator Spring-open/power-closed (for systems
TZ-4 TOTALZONE® ZONE CONTROL PANEL 68-0259-1 4 INSTALLATION Mounting CAUTION Equipment Damage Hazard. Do not mount TZ-4 inside HVAC equipment Mount only on wall or on cold air return. Identifying DIP Switches This panel has two banks of DIP switches, DIP switch 4 (S4) and DIP switch 5 (S5), see Fig 15. Each bank has eight individual switches that are identified by two numbers; the first number is the bank number (4 or 5) and the second number identifies the individual switch. For example, DIP 5-1 is bank 5, switch 1. 1.Mount the thermostats in each zone of the living space using the installation instructions provided with each thermostat. 2.Mount the dampers in the ductwork using the installa- tion instructions provided with each damper.3.Mount the TZ-4 zone panel near the HVAC equipment; (on a wall or on the cold-air return). See Fig. 2. 4.Level the TZ-4 for appearance only. Wiring CAUTION Vo l ta g e H a z a r d . Can cause electrical shock or equipment damage. Disconnect power before continuing installation. Wiring must comply with applicable codes, ordinances, and regulations. 1.Connect thermostats as shown in Fig. 3-6. 2.Connect dampers as shown in Fig. 7-10. 3.Connect C7735A Discharge Air Temperature Sensor (not supplied) to the DATS terminals. The wires are not polarized. See Fig. 13. 4.Connect Add-A-Zone panels (if used) to the AZ1 and AZ2 terminals. 5.Connect the HVAC equipment to the EQUIP terminals on the panel. See Fig. 15-21. 6.Connect a 40 VA, 24 volt transformer to R (hot) and C (common). This must be a dedicated transformer and each TAZ-4 board also requires a transformer. See Fig. 12. 7.The auxiliary 40 VA 24-volt transformer can be con- nected to T1 and T2 if additional power for dampers is required. This second transformer is not required; how- ever, total power consumption of panel and damper is limited to 40VA without it. Fig. 2. TZ-4 mounting location. Table 3. Required Accessories (Not Supplied). AccessoryDescriptionBypass Rating (cfm) 40 VA transformers AT140D1046 (PMT-40)— Capacity protectorC7735A1000— Outdoor Temperature Sensor (Required for dual-fuel applications)C7089B1000— Round static pressure regulator damperSPRD7 SPRD8 SPRD9 SPRD10 SPRD12 SPRD14 SPRD16300 400 600 750 1200 1800 2400 Rectangular static pressure regulator damperSPRD12x8 SPRD12x10 SPRD12x12 SPRD20x8 SPRD20x10 SPRD20x121000 1200 1400 1600 2000 3000 M20517 WATER HEATERTZ-4E LEC TR ONIC AIR CL EA N ER RETURNAIR TZ-4 OPTIONAL LOCATION FURNACE OR BOILER HIGH EFFICIENCY AIR CLEANER
TZ-4 TOTALZONE® ZONE CONTROL PANEL 5 68-0259-1 Wiring Diagrams (Fig. 3 and 4) Conventional Thermostats Conventional (RWYG) thermostats can be used to control conventional, multi-stage, and heat pump equipment. If the thermostat has a common terminal, it is wired to C on the panel, see Fig. 3. A multi-stage thermostat is wired with the second and third stage of heat to W2 and W3 on the panel thermostat connections, and with the second stage of cooling to Y2. Leave the zone O/B thermostat jumper on the TZ-4 disconnected. See Single and Multi-Stage Operation in the Operation section for instructions on staging the TZ-4. The PC8900 with the W8900A or W8900C can be used as a zone thermostat. See Fig. 4 for hookup. This thermostat can be used to control up to 2 heat and 2 cool stages of conventional equipment. When used to control heat pump equipment, the W8900A is recommended. Connect a jumper on the W8900 from Rc to Rh as shown in Fig. 4. Wire terminals R and C to a transformer. If the system current draw is within specifications, the R and C on the W8900 could alternately be connected to R and C on the TZ-4. The PC8900/W8900 draws 5 VA. Fig. 3. Typical single-stage thermostat wiring. M20509B G C R Y W COMMON (C) TERMINAL IS USED ONLY BY THERMOSTATS THAT REQUIRE A COMMON WIRE. MULI-STAGE THERMOSTATS ARE WIRED SIMILARLY BUT WITH Y2 AND W2 USED FOR SECOND STAGE COOL AND HEAT. THIRD STAGE OF HEAT (W3) CAN BE WIRED TO W3/AUX. LEAVE O/B JUMPER ON TZ-4 DISCONNECTED.TZ-4 THERMOSTAT CONNECTORS TYPICAL SINGLE STAGE THERMOSTAT WIRING1 2 3 1 3 2
TZ-4 TOTALZONE® ZONE CONTROL PANEL 68-0259-1 6 Fig. 4. PC8900 with W8900A,C Thermostat wiring. Heat Pump Thermostats Select a heat pump thermostat from Table 1. If the thermostat selected has a separate Y1 and W1 wire, as shown in Fig. 5, leave the zone O/B thermostat type jumper on the TZ-4 disconnected, and wire as shown in Fig. 5.If the PC8900/W8900 /Thermostat is used in a heat pump application, use the W8900A, not the W8900B, and wire as shown in Fig. 4. M20508B W8900A/C IS RECOMMEDED FOR CONVENTIONAL AND HEAT PUMP APPLICATIONS. THE W8900B CANNOT SWITCH THE PANEL TO EMERGENCY HEAT. LEAVE O/B JUMPER ON TZ-4 DISCONNECTED.TZ-4 THERMOSTAT CONNECTORS1 2 1 S1 S T1 T OUT OUT LED G Y2 Y1 W1 W2 1 2 3 4 GND C R RH RC HUM HUM VNT VNT W8900A,C PC8900 CO2 1234 2 24 VAC 120 VAC
TZ-4 TOTALZONE® ZONE CONTROL PANEL 7 68-0259-1 . Fig. 5. Heat pump thermostat with separate Y1 and W1 terminals and multi-stage thermostat wiring. If the thermostat selected from Table 1 has a single Y terminal for first stage heat and cool, wire as shown in Fig. 6. Wire either O or B (not both) from the thermostat to the O/B terminal on the panel. Locate the O/B thermostat jumper on the TZ-4 near each zone thermostat wiring terminal. Connect the jumper if O was used or leave disconnected if B was used. Connect second stage, auxiliary heat to W2. When using two- or three-stage heat pump thermostats with single Y first-stage hookup, place a jumper from W2 to Y2 on the TZ-4 thermostat connections. See Fig. 7. See Single and Multi-Stage Operation in the Operation section for instructions on staging the TZ-4.ARD or ZD Dampers Wire the ARD or ZD Damper to the panel as shown in Fig. 8. Multiple dampers can be wired in parallel. Use these dampers on systems up to 2000 cfm. AOBD Dampers Wire the AOBD dampers to the panel as shown in Fig. 9. Two AOBD can be wired in tandem as shown in Fig. 10. More than two AOBD dampers require the Slave Damper Control Relay (SDCR). Fig. 6. Heat pump thermostat with single Y thermostat wiring. M20506B G C R Y W1L W2 E B O COMMON (C) TERMINAL IS USED ONLY BY THERMOSTATS THAT REQUIRE A COMMON WIRE. JUMP E TERMINAL TO W1 FOR EMERGENCY HEAT. LEAVE O/B JUMPER ON TZ-4 DISCONNETED.TZ-4 THERMOSTAT CONNECTORS HEAT PUMP THERMOSTAT WITH SEPARATE Y1 AND W1 THERMOSTAT WIRING1 2 3 12 3 M20507B G C R Y1 W1L W2 E B O COMMON (C) TERMINAL IS USED ONLY BY THERMOSTATS THAT REQUIRE A COMMON WIRE. NORMALLY, CONNECT E ON THERMOSTAT TO W1 ON PANEL. ALTERNATIVELY, INSTALL JUMPER FROM E TO Y1 ON THERMOSTAT. CONNECT O/B TERMOSTAT JUMPER ON TZ-4 PANEL IF USING O FROM THERMOSTAT; DISCONNECT IF USING B.TZ-4 THERMOSTAT CONNECTORS HEAT PUMP THERMOSTAT WITH SINGLE Y THERMOSTAT WIRING1 2 3 1 3 2
TZ-4 TOTALZONE® ZONE CONTROL PANEL 68-0259-1 8 Fig. 7. Heat pump thermostat with 3-stage heat, 2-stage cool single Y thermostat wiring. Fig. 8. Wiring ARD or ZD damper to panel.Fig. 9. Wiring AOBD damper to panel. Fig. 10. Wiring two AOBD dampers in parallel. MARD Dampers or Dampers Using an ML6161 Motor Actuator Wire the MARD Damper or ML6161 Actuator to the panel as shown in Fig. 11. These are floating control actuators, but are controlled as two-position devices on the TZ-4 panel. Multiple dampers can be wired in parallel. The ML6161 Motor causes the damper LED to illuminate green constantly. WIre a relay as shown in Fig. 12 to restore damper position indication. Use the MARD or D643 with the ML6161 on systems above 2000 cfm. Fig. 11. Wiring MARD Damper or ML6161 Actuator to panel. M20891 G C R Y1 Y2L W3 E B O COMMON (C) TERMINAL IS USED ONLY ON THERMOSTATS THAT REQUIRE A COMMON WIRE. ALTERNATIVELY, JUMPER E THERMOSTAT TERMINAL TO Y1 FOR EMERGENCY HEAT. CONNECT O/B JUMPER ON TZ-4 WHEN USING O OR DISCONNECT WHEN USING B FOR CHANGEOVER. FIELD INSTALLED JUMPER FROM Y2 TO W2 ON PANEL THERMOSTAT CONNECTIONS.TZ-4 THERMOSTAT CONNECTORS HEAT PUMP THERMOSTAT WITH SINGLE Y THERMOSTAT WIRING1 2 3 4 14 3 2 4M6 M4 M1 56 123Z X DAMPER MOTOR FIELD JUMPER M19067 MOTOR TERMINALS 4M6 M4 M1 56 12 3 DAMPER MOTORS M19068 MOTOR TERMINALS 456 123Z XZ X FIELD JUMPER M1 M4 M20136A ZONE PANEL CONNECTIONS M6 CW COM CCW MARD
TZ-4 TOTALZONE® ZONE CONTROL PANEL 9 68-0259-1 Fig. 12. MARD or ML6161 Damper Motor Actuator using R8222 Relay wiring. Transformer 1.Wire the transformers to the panel as shown in Fig. 13. One 40 VA, 24 Vac transformer controls up to five ARD or ZD dampers. 2.Connect the transformer to terminals R and C. 3.Add the auxiliary transformer if six to ten ARD or ZD dampers are used. a. Wire auxiliary transformer to terminals T1 and T2. b. It is important that these two transformers be wired in phase. If they are wired out of phase, the internal circuit breaker trips and the board de-powers. If this occurs, remove power, correct the wiring and restore power to the board. IMPORTANT If more than five dampers are required for one zone or if more than ten dampers are used for the TZ-4, use the Slave Damper Control Relay (SDCR). Fig. 13. Wiring transformer(s) to panel. Discharge Air and Outdoor Temperature Sensors Wire the C7735A Discharge Air Temperature Sensor (DATS) to the panel as shown in Fig. 14. The Purge LED (yellow) flashes in all modes except purge if no DATS is connected to the TZ-4 or if there is a problem with the DATS or the wiring. For dual fuel applications, connect the C7089 Outdoor Temperature Sensor as shown in Fig. 14. Fig. 14. Wiring C7735A Discharge Air Temperature Sensor (DATS) to panel. Add-A-Zone Panel Remove power from TZ-4 before connecting AZ-1 and AZ-2. Wire the Add-A-Zone (TAZ-4) Panel to the TotalZone (TZ-4) Panel as shown in Fig.15. Up to seven TAZ-4 Panels can be wired to one TZ-4 panel to control up to 32 zones. COM CCW CWML6161 R8222 RELAY ZONE CONTROL PANEL DAMPER TERMINALS M20548A M6M4 M1RC R C T1 T2 C R C R 24 VAC, 40 VA Transformer (Required if more than four dampers) 24 VAC, 40 VA Transformer DAMPER XFRM PANEL XFRM M20518 M20519 DATS DATS DATSOT OT OT Sensor
TZ-4 TOTALZONE® ZONE CONTROL PANEL 68-0259-1 10 Fig. 15. TotalZone Add-A-Zone wiring. Conventional Equipment Wire the heating and cooling equipment to the equipment terminals on the TZ-4 Panel as shown in Fig. 16. Conventional Equipment: Set DIP switch 5-1 to on. Electric Furnaces: Set DIP switch 5-6 to off to energize the fan with a call for heat. Hydro-Air: Wire the zone valve or circulator relay to the Rh and W1 equipment terminals. (If the circulator relay has powered terminals, remove the Rh Rc jumper.) Set DIP switch 5-6 to off to energize the fan with a call for heat. Oil Heat: Wire the oil primary T, T terminals to the Rh and W equipment terminals. (If the oil primary has powered terminals, remove the Rh Rc jumper.) Multi-Stage: Wire the equipment as shown in Fig. 16 using the W2 and W3 terminals for second and third stages of heat. Wire Y2 for second stage of cooling. See Single and Multi-Stage Operation in the Operation section to configure DIP switches 4-1, 4-2, 4-3, and 4-4. M20362 TotalZone Panel TotalZone Add-A-Zone Panel AZ1 DIP-SWITCHES AZ2AZ1 AZ2 AZ1 AZ2TO NEXT ADD-A-ZONE PA N E L 54321O N