Page 31
Operation TP1MAN Issue 4_03-10 (MAN0630)31 Control Buttons The control buttons are located beneath an access panel underneath the display screen. They are used to cancel alarms and access/navigate the menu system. To access the buttons carry out the following procedure: 1 Access the controller interior. See page 12. Note The Control Buttons Access Panel cannot be opened until access is made. 2 Push down on the finger grip located at the bottom of the Control Buttons Access panel. See the subsequent...
Page 32
Operation TP1MAN Issue 4_03-10 (MAN0630)32 Menus Touchpoint 1 has 6 menus for configuring/controlling the unit. They are represented on the display by the icons shown in the following table lists them and explains what they are for. Using Menus The controller uses a menu system for configuration/control that is displayed/navigated in the following ways. Displaying Menus „Press the and — Up and Down — control buttons at the same time. 000 is displayed in the gas reading position and the Gas...
Page 33
Operation TP1MAN Issue 4_03-10 (MAN0630)33 Cancelling Operations/Choices To cancel operations/choices: „Press the — Cancel — button. This returns to the previous menu level, setting, etc. Pressing Cancel again returns to normal operation. Note The system automatically returns to normal operation if no buttons are pressed for more than 30 minutes. For details of the Common Module menu see page 37. For details of the Channel Module menu see page 43. To change user settings/configuration using the...
Page 34
Commissioning TP1MAN Issue 4_03-10 (MAN0630)34 WARNINGS Touchpoint 1 is designed for installation and use in indoor safe area non-explosive atmospheres. Installation must be in accordance with the recognized standards of the appropriate authority in the country concerned. Before carrying out any work ensure local regulations and site procedures are followed. Access to the interior of the controller, when carrying out any work, must only be conducted by trained personnel. Switch off and isolate...
Page 35
Commissioning TP1MAN Issue 4_03-10 (MAN0630)35 2 Apply power to the controller and switch it on. See page 25. To skip the warm up sequence press the Cancel button for 3 seconds. 3 Check for a minimum voltage of 2.9 Vdc at the detector. If incorrect check for constant current supply of 200 mA +/-2 mA. For detectors other than Sensepoint Flammable refer to their operating instructions. . 4 Close the detector enclosure. For gas detector details see its user manual. 5 Press the Up/Down buttons on the...
Page 36
Commissioning TP1MAN Issue 4_03-10 (MAN0630)36 Note Honeywell Analytics recommend the use of half full-scale gas for calibration purposes (contact a distributor for the supply of calibration gas). The controller now displays the actual gas measurement at the gas detector. 12 Adjust the reading to the actual concentration of the calibration gas applied to the sensor. Use the Up/Down buttons. 2-wire 4-20 mA Sink This describes connection to gas detectors such as Sensepoint Toxic. 1 Set up the gas...
Page 37
Commissioning TP1MAN Issue 4_03-10 (MAN0630)37 3-wire 4-20 mA Source This covers connection to gas detectors such as Sensepoint Plus and Sensepoint Pro. 1 Set up the gas detector. Refer to the detector’s user manual for details describing how to set up the detector. 2 Check that all power and electrical connections to the controller, and electrical connections to the gas detector are correct. For gas detector access see its user manual. For detector to controller wiring details see page 20 and page...
Page 38
User Settings TP1MAN Issue 4_03-10 (MAN0630)38 The controller is supplied pre-configured with factory defaults, see page 45. These can be used if suitable, or customized by the user to suit site requirements. This chapter explains how to: • set gas units and range, see page 38 • set zero and span, see page 40 • browse Touchpoint 1’s event record, see page 41 • set alarm levels and relay actions, see page 42 • set the real-time clock, see page 44 • set the power source, see page 45 Before performing...
Page 39
User Settings TP1MAN Issue 4_03-10 (MAN0630)39 %v/v / / / / / Units and Range Select kppm, ppm, %LEL or %v/v Change range value Finished. Returns to Configuration Menu CalibrationSet Zero (C0). With zero gas at detector adjust value to zero For O 2 only apply N 2 at 0.3 liter/minWait for 10s count down. If OK GOOD is displayed. If fail FA I L is displayed and return to set Zero Set Span (CS). Apply cal. gas. When stable adjust value to cal. gas concentration Wait for 10s...
Page 40
User Settings TP1MAN Issue 4_03-10 (MAN0630)40 6 When settings are complete press OK. Returns to the menu selection screen. 7 Press Cancel. Returns controller to normal operation. Zero and Span This menu is for calibrating controller measurements to the connected gas detector. 1 Access the menu system and select the menu option. Press Up or Down. The icon flashes. 2 Press OK. The top left of the display reads CO to indicate the set zero menu mode. The gas reading displays the current real zero...