Home > Honeywell > Control panel > Honeywell Galaxy 3 User Manual

Honeywell Galaxy 3 User Manual

    Download as PDF Print this page Share this page

    Have a look at the manual Honeywell Galaxy 3 User Manual online for free. It’s possible to download the document as PDF or print. UserManuals.tech offer 178 Honeywell manuals and user’s guides for free. Share the user manual or guide on Facebook, Twitter or Google+.

    							Galaxy 3 Series Programming Manual
    85
    52 - Program Zones (cont’d)
    48-51 ATM-1, ATM-2, ATM-3 & ATM-4
    There are four AT M (Automatic Teller Machine) zone types. These zone functions are continuously opera-
    tional and are designed for the special maintenance and restocking requirements of ATM’s.
    A single AT M zone type can be omitted for the duration of the period entered in the ATM Timeout param-
    eter (option 51.39). The ATM Delay parameter (option 51.38) determines the delay before the selected
    AT M zones are omitted once selected by an ATM code. Each of the zones ATM-1 to ATM-4 zones acti-
    vates a corresponding AT M output.
    NOTE:The relevant ATM outputs are activated as soon as the ATM Delay expires.
    On entering an ATM code, the system prompts for one of the AT M zone types to be selected; to select the
    AT M zone type to be omitted use the A or B key or enter the number of the AT M zone type. Once the zone
    is selected, the keypad indicates the DELAY ACCESS - the number of minutes remaining until the AT M
    zones are omitted. Once the zone is omitted, the initiating keypad indicates the ACCESS TIMEOUT - the
    number of minutes remaining until the selected ATM zones are reintroduced to the system. The Entry/Exit
    Horns sound a warning ten and five minutes before the zones are reinstated.
    The omitted AT M zone type can be reinstated at any time, or the omit period can be extended by the ATM
    user code.  Enter the ATM code and press the ent key; the system prompts for 1 = RESET ACCESS or 2 =
    ABORT ACCESS. Press 1 to restart the ATM Timeout or 2 to reinstate the omitted ATM’s.
    NOTE:Only one ATM zone type may be omitted at any time.
    52 Alarm Extend
    The Alarm Extend function is identical to the Urgent function, with the exception that if the zone is open (and
    has not been previously omitted) at the end of the bell duration (refer to option 51.1 = PARAMETERS.Bell
    Time) it immediately activates another full alarm condition. Alarm Extend zones can only be omitted by
    option 11 = OMIT ZONES. 
    						
    							Galaxy 3 Series Programming Manual
    86
    Option 53 – Program Outputs
    This option is used by the engineer to modify the programming of the outputs on the system. The option also
    allows the attributes of the outputs to be changed. The programmable options are:
    Table 19. Output Attributes
    Selecting Outputs
    On entering the option, the first output on the system is displayed; the output address, function and mode are
    displayed on the top line, the polarity and assigned groups are displayed on the bottom line.
    From the display of the first output, any output on the system can be displayed by pressing the A or B keys or
    by entering the address of a specific output.
    The output is selected for programming by pressing the ent key; the first output programming attribute 1=Op
    Function   is displayed.
    53 - Program Outputs
    Attributes Description
    1 Output Functi on A ssi gn output type
    2 Output Mode 1 = Latch - requires valid code to reset
    2 = Reflex - follows activation status of zones
    3 = Pulse (001 - 3000 secs) - activates for programmed period
    3 Output Polarity 0 = POS - 12V going to 0V in activation
    1 = NEG - 0V going to 12V in activation
    4 Diag. Recording Assigns output to be active during Diagnostic Test
    5 Output Groups Assign groups to the output
    Note: Groups only appear if the Group option is enabled
    (refer to option  63.1 = OPTIONS. Groups). 
    						
    							Galaxy 3 Series Programming Manual
    87
    Keypad Outputs
    The keypad outputs are fully programmable.  The address of the keypad output is the keypad address pre-
    fixed with a star, for example the output for keypad 06 is 606.  The function of keypad outputs default to
    Entry/Exit Horn.
    The valid addresses of the keypads on each of the panels and the respective output addresses are indicated in
    the following table:
    Table 20. Addresses of Valid Keypad Outputs
    It is possible to add additional keypads at any unused comms module addresses (B, C, D and E) as detailed
    in the following NOTE. These must be standard keypads. An engineer keypad can also be used at address F.
    NOTE: On Line 1, keypad addresses  B, C, D and E are not available if the Ethernet,
    ISDN, RS232 or Telecom modules respectively are fitted.
    Control Horn (
    6 66 6
    699)
    The control unit horn output - addressed as 799 - is fully programmable.
    Attributes
    The attributes can be stepped through by pressing the A or B keys or directly selected by pressing the at-
    tribute number (1–4).  Once the required attribute is on display, press the ent key to gain access for modifica-
    tion.
    Once the attribute has been assigned press the ent key to save the programming and return to the attribute
    selection level.  Pressing the esc key at any time when assigning attributes aborts the programming and returns
    to the attribute selection level.
    1 = Output Function
    Entering the Output Function attribute displays the address and the current function of the selected output
    along with the output function reference number. The output functions can be stepped through, forwards or
    backwards, using the A and B keys. Alternatively, a function can be directly selected by entering the function
    reference number, for example, entering 16 displays output function 16 = FIRE.
    Once the required output function is displayed, it is assigned to the output by pressing the ent key.
    53 - Program Outputs (cont’d)
    Panel Line Address Output Addresses
    3-48 1 0 – 2, B, C, D, E & F (NOTE) 10-12, 15-19
    3-144 1 0 – 2, B, C, D, E & F (NOTE) 10-12, 15-19
    2 0 – 6 & F 20-26, 29
    3-520 1 0 – 2, B, C, D, E & F (NOTE) 10-12, 15-19
    2 0 – 6 & F 20-26, 29
    3 0 – 6 & F 30-36, 39
    4 0 – 6 & F 40-46, 49 
    						
    							Galaxy 3 Series Programming Manual
    88
    2 = Output Mode
    Each output function defaults to a specific, logical output mode.  However, the output mode of each function
    can be modified to meet special requirements: when reprogrammed, the new mode applies to all outputs
    assigned to that function.  The output modes are:
    1 = Latch: the output remains active until a valid code is entered.
    2 = Reflex: the output follows the activity of the triggering event, for example, the Set output follows the
    setting and unsetting of the group.
    3 = Pulse: the output remains active for the programmed pulse time 1-3000 seconds (50 mins).
    Programming the Output Mode
    Select the required mode using the A or B keys or by selecting the number 1 – 3.  Once the required mode is
    on selected, press the ent key to accept the programming. If assigning the Pulse output mode, enter the pulse
    time (001 – 3000 seconds) and press the ent key.
    3 = Output Polarity
    The Output Polarity   determines the normal operational state of the output. All outputs are referred to having
    positive (0 = POS) or negative (1 = NEG) polarity. An output programmed as positive polarity is 12 V in the
    normal condition and goes to 0 V when activated. A negative polarity output goes from the normal condition
    of 0 V to 12 V in the active state. All outputs except SET (09) default to positive output mode.
    NOTE:The Switch DC output is a positive polarity output, however, the normal condition is 0 V, going to
    12 V when activated. The output mode is normally Pulse.
    4 = Diag Recording
    When this attribute is enabled, the selected output will be switched on during the diagnostic test (see Option
    61.2.3=Diagnostics.Historical.Record).
    This test can also be carried out remotely.
    5 = Output Groups
    NOTE:The Groups attribute is only available if groups have been enabled on the system (refer to option 63
    = OPTIONS).
    The Group attribute allows the output to be assigned to the groups on the system; an output can be assigned
    to more than one group. All outputs default to all groups on the system.
    On selecting the Output Groups attribute, the groups that the output is currently assigned to are displayed.
    Press the relevant number keys to toggle the status of the group and press the ent key; if the group number is
    displayed on the top line, then the group is assigned to the output; if a dash (–) appears in place of the group
    number, the group has been removed from the output.
    The output will activate if triggered by an event in any of the groups assigned to that output, unless output
    group status has been programmed.
    53 - Program Outputs (cont’d) 
    						
    							Galaxy 3 Series Programming Manual
    89
    Use the A or B key to select the required group (A1–D8). When the end of a block is reached, the next
    block of eight groups is selected; press keys 1–8 to toggle the status of the relevant group in the current block
    to the output; press the ent key to accept the selection.
    Group Status
    This group attribute offers an additional feature that makes the operation of the output conditional on the set
    status of each of the system groups. An output assigned Group Status only activates if the set conditions of
    the programming are met, for example, an Intruder output used to trigger a communicator can be pro-
    grammed to activate only if groups 2 and 4 are set and group 3 is unset.
    To assign the Group Status conditions, press the 7 key when selecting the groups: an arrow (>) is displayed
    on the bottom line as well as the current Status. Press the relevant number keys to toggle the status of the
    groups and press the ent key to accept the programming. The available group status conditions are:
    S= Set — group must be set to allow output to activate;
    U= Unset — group must be unset to allow output to activate;
    –= Set or unset — output activation is independent of the group status.
    53 - Program Outputs (cont’d)
    Groups  12345678 Groups  12345678Groups  12345678 Groups  12345678
    Groups  12345678
    STATUS >-SUS---- STATUS >-SUS----STATUS >-SUS---- STATUS >-SUS----
    STATUS >-SUS----
    k c o l B p u o r Gsp u o r G l a c i s y h P
    8 - 1 A8- 1
    8 - 1 B61 - 9
    8 - 1 C42 - 7 1
    8 - 1 D23 - 5 2
    Table 21. Output Groups
    Galaxy 520
    The Galaxy 520 panel has 32 groups; these are displayed on the keypad in block of eight groups, sub-divided
    into A, B, C and D: 
    						
    							Galaxy 3 Series Programming Manual
    90
    Output Functions
    The following table shows all the outputs and the zone functions and conditions that result in their activation.
    53 - Program Outputs (cont’d)
    Key:
    S = Activates when system is set? = Activation dependant on system programming
    P = Activates when system is Part SetX= Activates during Exit Time
    U = UnsetE= Activates during Entry Time
    A = Activated in any conditionL= Switches output off if linked to destination output
    -  = No effectT= Activates if zone resistance is less than value for tamper s/c
    O= Activates when zone is omitted    or greater than value for tamper o/c
    Table 22A. Output Activations per Zone
    Output Functions Bells Strobe PA Intruder Tamper 24
    HrsReset Switch
    DCSet Engineer Spare Ready Security AC
    Fail
    Zone Function01 02 03 04 05 06 07 08 09 10 11 12 13 14
     01 FinalSS–S T–X –– – – A – –
     02 ExitSS–S T–– –– – – A – –
     03 IntruderSS–S T–– –– – – A – –
     04 24 HoursSS–S TA– –– – – A – –
     05 SecuritySS–S T–– –– – – A A –
     06 DualSS–S T–– –– – – A – –
     07 EntrySS–S T–– –– – – A – –
     08 Push Set–––– T–X ––– –– – –
     09 Keyswitch–––– T–X XS– –– – –
    10 Secure FinalSS–S T–X –– – – A U –
    11 Part FinalSS–S T–X –– – – A – –
    12 Part EntrySS–S T–– –– – – A – –
    13 PAAAA– T–– –– – – A – –
    14 PA S ilent––A– T–– ––– –A – –
    15 PA DelayAAA– T–– –– – – A – –
    16 PA Delay Silent––A– T–– ––– –A – –
    17 Link???? ?T?? ??? ?? ? ?
    18 Spare–––– T–– ––– –– – –
    19 FireAA–– T–– –– – – – – –
    20 TamperSS–S A–– –– – – A – –
    21 Bell TamperAS–S A–– –– – – A – –
    22 Beam PairSS–S T–– –– – – A – –
    23 B attery Low–––– T–– ––– –– – –
    24 Line Fail–––– T–– ––– –– – –
    25 AC Fail–––– T–– ––– –– – A
    26 Log–––– T–– ––– –A – –
    27 Remote Access–––– T–– ––– –– – –
    28 VideoSS–S T–– –– – – A – –
    29 Video ExitSS–S T–– –– – – A – –
    30 Intruder D elaySS–S T–– –– – – A – –
    31 Log Delay–––– T–– ––– –– – –
    32 Set Log–––– T–– ––– –– – –
    33 Custom-A???? ?T?? ??? ?? ? ?
    34 Custom-B???? ?T?? ??? ?? ? ?
    35 ExitguardLLLL LTLL LLL LL L L
    36 MaskSS–S T–– –– – – A – –
    37 UrgentAA–A T–– –– – – A – –
    38 PA Unset––U– T–– ––– –U – –
    39 Keyswitch Reset–––– T–X ––– –– – –
    40 B ell fail–––– ––– ––– –– – –
    41 Intr LowSS–S T–– –– – – A – –
    42 Intr HighSS–S T–– –– – – A – –
    43 PSU Fault–––– T–– ––– –– – –
    44–46 Not Used–––– ––– ––– –– – –
    47 VibrationAA–A T–– –– – – A – –
    48 ATM-1AA–A T–– –– – – A – –
    49 ATM-2
    AA–A T–– –– – – A – –
    50 ATM-3AA–A T–– –– – – A – –
    51 ATM-4AA–A T–– –– – – A –
    52 Alarm ExtendAA–A T–– –– – – A – – 
    						
    							Galaxy 3 Series Programming Manual
    91
    53 - Program Outputs (cont’d)
    Key:
    S = Activates when system is set? = Activation dependant on system programming
    P = Activates when system is Part SetX= Activates during Exit Time
    U = UnsetE= Activates during Entry Time
    A = Activated in any conditionL= Switches output off if linked to destination output
    -  = No effectT= Activates if zone resistance is less than value for tamper s/c
    O= Activates when zone is omitted    or greater than value for tamper o/c
    Table 22B. Output Activations per Zone
    Output Functions Batt
    LowFire Horn E/E Horn Part
    SetC onfirm Line
    FailVideo Comm
    FailBatt
    TestWrong
    CDAle rt D LYD
    FireNo
    Re-armTimer-A
    Zone Function15 16 17 18 19 20 21 22 23 24 25 26 27 28 29
     01 Final––SSXE– - –S–––––S –
     02 Exit––SSXE– S –S–––––S –
     03 Intruder––SSXE– S –S–––––S –
     04 24 Hours––S A – – –S–––––S –
     05 Security––S A – – –S–––––S –
     06 Dual––SSXE– S –S–––––S –
     07 Entry––SSXE– - –S–––––S –
     08 Push Set––– X – – –– –––––– –
     09 Keyswitch––– – X – –– –––––– –
    10 Secure Final––A A X S –S–––––S –
    11 Part Final––ASXEX S –S–––––S –
    12 Part Entry––AXE– S –S–––––S –
    13 PA––A – – – –– –––––A –
    14 PA S ilent––– – – – –– –––––– –
    15 PA Delay––A A – – –– –––––A –
    16 PA D elay S ilent––– – – – –– –––––– –
    17 Link??? ? ? ? ?? ????? ? ?
    18 Spare––– – – – –– –––––– –
    19 Fire–AA A – – –V––––AA –
    20 Tamper––A A – – –S–––––S –
    21 Bell Tamper––A A – – –S–––––S –
    22 Beam Pair––SSXE– – –S–––––S –
    23 B attery LowU– – – – – –– – –––– – –
    24 Line Fail––– U – – A– –––––– –
    25 AC Fail––– – – – –– –––––– –
    26 Log––– – – – –– –––––– –
    27 Remote Access––– – – – –– –––––– –
    28 Video––SSXE– S –S–––––S –
    29 Video Exit––SSXE– S –S–––––S –
    30 Intruder D elay––SSXE– – –S–––––S –
    31 Log Delay––– – – – –– –––––– –
    32 Set Log––– – – – –– –––––– –
    33 Custom-A??? ? ? ? ?? ????? ? ?
    34 Custom-B??? ? ? ? ?? ????? ? ?
    35 ExitguardLLL L L L LL LLLLL L L
    36 Mask––SSXE– – –S–––––S –
    37 Urgent––A A – – –– –––––A –
    38 PA Unset––– – – – –– –––––– –
    39 Keyswitch Reset––– – – – –– –––––– –
    40 B ell fail––– – – – –– –––––– –
    41 Intr Low––SSXE– S –S–––––S –
    42 Intr High––SSXE– S –S–––––S –
    43 PSU Fault––– – – – –– –––––– –
    44–46 Not Used––– – – – –– –––––– –
    47 Vibration––– – – – –– –––––– –
    48 ATM-1––– – – – –– –––––– –
    49 ATM-2––– – – – –– –––––– –
    50 ATM-3––– – – – –– –––––– –
    51 ATM-4––– – – – –– –––––– –
    52 Alarm ExtendAA– A T – –– – –––A– – 
    						
    							Galaxy 3 Series Programming Manual
    92
    53 - Program Outputs (cont’d)
    Key:
    S = Activates when system is set? = Activation dependant on system programming
    P = Activates when system is Part SetX= Activates during Exit Time
    U = UnsetE= Activates during Entry Time
    A = Activated in any conditionL= Switches output off if linked to destination output
    -  = No effectT= Activates if zone resistance is less than value for tamper s/c
    O= Activates when zone is omitted    or greater than value for tamper o/c
    Table 22C. Output Activations per Zone
    Output Functions Timer-B Walk
    TestZo n e
    OmitWa rn in g C u s to m
    ACustom
    BTest Reset
    RQDMask Valid
    cdFail
    SetD uress Illeg al
    CodeMax
    Ta mpAbort Unset
    Zone Function30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45
     01 Final– UO A – – –S?– –– – – – – –
     02 Exit– UO A – – –S?– –– – – – – –
     03 Intruder– UO A – – –S?– –– – – – – –
     04 24 Hours– UO A – – –S?– –– – – – – –
     05 Security– UO A – – –S?– –– – – – – –
     06 Dual– UO A – – –S?– –– – – – – –
     07 Entry– UO A – – –S?– –– – – – – –
     08 Push Set–UOA – –––––––––– –
     09 Keyswitch–UOA – –––––UX–––– U
    10 Secure Final–UOA – –––––––––– –
    11 P a rt F in a l–UOA – –––––––––– –
    12 Part Entry–UOA – –––––––––– –
    13 PA–UOA – –––––––––– –
    14 PA Silent–UOA – –––––––––– –
    15 PA Delay–UOA – –––––––––– –
    16 PA Delay Silent–UOA – –––––––––– –
    17 Link?U?O? ? ? ? ????? ? ? – ? ?
    18 Spare––– A – – –––––– – ? – –
    19 Fire– UO A – – –A?– –– – – – – –
    20 Tamper– UO A – – –A?– –– – – – – –
    21 Bell Tamper– UO A – – –A?– –– – – – – –
    22 Beam Pair–UOA – –––––––––– –
    23 B attery Low–UOA – –––––––––– –
    24 Line Fail–UOA – –––––––––– –
    25 AC Fail–UOA – –––––––––– –
    26 Log–UOA – –––––––––– –
    27 Remote Access–UOA – –––––––––– –
    28 Video– UO A – – –S?– –– – – – – –
    29 Video Exit– UO A – – –S?– –– – – – – –
    30 Intruder Delay– UO A – – –S?– –– – – – – –
    31 Log Delay–UOA – –––––––––– –
    32 Set Log–UOA – –––––––––– –
    33 Custom-A??O?? ? ? ?????? ? – ? ?
    34 Custom-B??O?? ? ?????????? ?
    35 ExitguardLLLOL L LLLLLLLL?L L
    36 Mask– – – – – – – – SPE – – – – L ? –
    37 Urgent– UO A – – –A?– –– – – – – –
    38 PA Unset– UO A – – –U?– –– – – – – –
    39 Keyswitch Reset–UOA – –––––––––– –
    40 Bell Fail–––A – –––––––––– –
    41 Intr Low– UO A – – –S?– –– – – – – –
    42 Intr High– UO A – – –S?– –– – – – – –
    43 PSU Fault–UOA – –––––––––– –
    44–46 Not Used–––– – –––––––––– –
    47 Vibration– UO A – – –A?– –– – – – – –
    48 ATM-1– UO A – – –A?– –– – – – – –
    49 ATM-2– UO A – – –A?– –– – – – – –
    50 ATM-3– UO A – – –A?– –– – – – – –
    51 ATM-4– UO A – – –A?– –– – – – – –
    52 Alarm Extend– UO A – – –A?– –– – – – – – 
    						
    							Galaxy 3 Series Programming Manual
    93
    53 - Program Outputs (cont’d)
    Key:
    S = Activates when system is set? = Activation dependant on system programming
    P = Activates when system is Part SetX= Activates during Exit Time
    U = UnsetE= Activates during Entry Time
    A = Activated in any conditionL= Switches output off if linked to destination output
    -  = No effectT= Activates if zone resistance is less than value for tamper s/c
    O= Activates when zone is omitted    or greater than value for tamper o/c
    Table 22D. Output Activations per Zone
    Output Functions Set Late U/S
    EarlyPre- Warn Autoset DR
    MaskedLink A-O RF
    JamRF
    SuperBell
    FailLow
    VoltsLockout Vib
    TestAtm 1-4 Fault Bell Test Comms
    Tes t
    Zone Function46 47 48 49 50 51-65 66 67 68 69 70 71 72-75 76 77 78
     01 Final– – ? – – ? –––– – – – – – –
     02 Exit– – ? – – ? –––– – – – – – –
     03 Intruder– – ? – – ? –––– – – – – – –
     04 24 Hours– – ? – – ? –––– – – – – – –
     05 Security– – ? – – ? –––– – – – – – –
     06 Dual– – ? – – ? –––– – – – – – –
     07 Entry– – ? – – ? –––– – – – – – –
     08 Push SetU? S? – – – ? –––– – – – – – –
     09 Keyswitch– – ? – – ? –––– – – – – – –
    10 Secure Final– – ? – – ? –––– – – – – – –
    11 Part Final– – ? – – ? –––– – – – – – –
    12 Part Entry– – ? – – ? –––– – – – – – –
    13 PA– – ? – – ? –––– – – – – – –
    14 PA Silent– – ? – – ? –––– – – – – – –
    15 PA Delay– – ? – – ? –––– – – – – – –
    16 PA Delay Silent– – ? – – ? –––– – – – – – –
    17 Link?? ? ? ? ????–???–––
    18 Spare– – ? – – ? –––– – – – – – –
    19 Fire– – ? – – ? –––– – – – – – –
    20 Tamper– – ? – – ? –––– – – – – – –
    21 Bell Tamper– – ? – – ? –––– – – – – – –
    22 Beam Pair– – ? – – ? –––– – – – – – –
    23 Battery Low– – ? – – ? –––– – – – A – –
    24 Line Fail– – ? – – ? –––– – – – A – –
    25 AC Fail– – ? – – ? –––– – – – A – –
    26 Log– – ? – – ? –––– – – – – – –
    27 Remote Access– – ? – – ? –––– – – – – – –
    28 Video– – ? – – ? –––– – – – – – –
    29 Video Exit– – ? – – ? –––– – – – – – –
    30 Intruder Delay– – ? – – ? –––– – – – – – –
    31 Log Delay– – ? – – ? –––– – – – – – –
    32 Set Log– – ? – – ? –––– – – – – – –
    33 Custom-A?? ? ? ? ????–???–––
    34 Custom-B?? ? ? ? ????–???–––
    35 ExitguardLL L L L LLLL–LLL–––
    36 Mask– – ? – – ? –––– – – – A – –
    37 Urgent– – ? – – ? –––– – – – – – –
    38 PA Unset– – ? – – ? –––– – – – – – –
    39 Keyswitch Reset– – ? – – ? –––– – – – – – –
    40 Bell Fail–– – – – –––A––––A––
    41 Intr Low– – ? – – ? –––– – – – – – –
    42 Intr High
    – – ? – – ? –––– – – – – – –
    43 PSU Fault– – ? – – ? –––– – – – A – –
    44–46 Not Used– – ? – – ? –––– – – – – – –
    47 Vibration– – ? – – ? –––– – A – – – –
    48 ATM-1– – ? – – ? –––– – – O – – –
    49 ATM-2– – ? – – ? –––– – – O – – –
    50 ATM-3– – ? – – ? –––– – – O – – –
    51 ATM-4– – ? – – ? –––– – – O – – –
    52 Alarm Extent– – ? – – ? –––– – – – – – – 
    						
    							Galaxy 3 Series Programming Manual
    94
    01 Bells (Latch)
    The Bells output is activated on a full alarm event when the system is set. This output is subject to the Bell
    Time, Bell Delay and No. Rearm parameters.
    02 Strobe (Latch)
    The Strobe output is activated on a full alarm event during the set state. This output is subject to the Bell
    Delay. The Strobe output follows the Bell Time, but latches on after the last rearm.
    03 PA (Latch)
    The PA output is activated whenever any of the PA zone types activate. The output is not subject to the
    Rearm parameter; it latches on remains active until a valid code, with the appropriate PA Reset level, is
    entered.
    04 Intruder (Latch)
    The Intruder output is activated on a full alarm event during the set state. Dependent upon the programming
    of parameter 51.56 Force Restore the intruder output restore is either subject to the Confirm Time Window
    + unset or entry of a valid code with the appropriate system reset level.. Refer to the 51.56 Force Restore
    description for further details.
    05 Tamper (Latch)
    The Tamper output is activated whenever a circuit tamper or lid tamper occurs.  The output is not subject to
    the Rearm parameter: it latches on and remains active until a valid code, with the appropriate Tamper Reset
    level, is entered.
    The output is also activated on the first entry of the engineer code when accessing engineer mode.
    NOTE:The Tamper output is not activated on the Galaxy 512 when engineer access is authorized by the
    user.
    06 24 Hours
    The 24 Hours output is activated whenever a 24 Hour zone is activated. The output is not subject to the
    Rearm parameter: it latches on and remains active until a valid code, with the appropriate System Reset
    level, is entered.
    07 Reset (Latch)
    The Reset output type is used as a control line output to latch, freeze and reset movement detector LEDs.
    08 Switch DC (Pulse)
    This Switch DC output is used to power detectors that require a momentary power interruption to reset them,
    for example, break glass or vibration detectors. This output reverses its polarity (changes from 0V to 12V) for
    the period of the Pulse output mode when the setting procedure has been initiated.
    NOTE:When installing detectors that require to be powered from a Switch DC output, connect the positive
    lead of the detector to the 12V terminal of a power supply and the negative lead to Switch DC
    output terminal.  Do not change the Output Polarity to 1=Neg: it must remain as positive polarity.
    53 - Program Outputs (cont’d) 
    						
    All Honeywell manuals Comments (0)

    Related Manuals for Honeywell Galaxy 3 User Manual