FireForce 8 Installation & Operation Manual P/N 52257:B 09/27/2006 11 Section 2: Installation 2.1 Mounting Instructions The standard mounting is a surface mount cabinet. The unit must be securely attached to a permanent partition using suitable fasteners. Four mounting holes are provided to accept 1/4-inch dia. screws max. There are nine combination knockouts provided, located three on the top and three on each side of the cabinet. Knockouts can accept 1/2, or 3/4 inch conduit. 2.2 Electrical...
Page 12
12 FireForce 8 Installation & Operation Manual P/N 52257:B 09/27/2006 Installation Function of Input/Output Connections 2.3.4 Earth Ground Connect to Earth Ground on the Power Supply module. 2.3.5 Trouble Relay The common trouble relay is a normally energized Form C relay that transfers when the FIREFORCE 8 detects a trouble condition. The contacts are rated for 2 amps @ 30VDC with a power factor of 0.6 or higher. 2.3.6 Power Fail The Power Fail relay is a normally energized Form C relay...
Page 13
FireForce 8 Installation & Operation Manual P/N 52257:B 09/27/2006 13 Function of Input/Output ConnectionsInstallation 2.3.8 Reference EOL Resistor (Power Limited) To accommodate existing Notification Appliance circuits that have EOL resistors of various values, provisions are made to attach a reference EOL resistor, matching the existing EOL, within the range of 2.0K to 25.0K ohms. Normally, a 3.9K resistor should be attached to the Ref. Terminals. All Style Y (Class B) outputs must have EOL...
Page 14
14 FireForce 8 Installation & Operation Manual P/N 52257:B 09/27/2006 Installation Function of Input/Output Connections
Page 15
FireForce 8 Installation & Operation Manual P/N 52257:B 09/27/2006 15 Section 3: Function of Switches, LEDs and Jumpers 3.1 Programming Switches Outputs 1 & 2 SW-1.1 SW-1.2 Function SIG1/2A SIG1/2B Open Open Output follows the Input (Also passes Sync. signals) Should NOT be used for Full Wave Rectified inputs Closed Open Steady Input, Temporal Output Open Closed Steady Input, Steady Output, Strobe Sync. added Closed Closed Steady input, steady output, noise eliminated. (Does NOT pass Sync....
Page 16
16 FireForce 8 Installation & Operation Manual P/N 52257:B 09/27/2006 Function of Switches, LEDs and JumpersFunction of LED Indicators 3.2 Function of LED Indicators 3.3 Jumper Functions 3.3.1 Jumper J1 When the jumper on J1 is in place, the internal Battery Charger is enabled. To disable the charger and allow an external charger to maintain the batteries, remove this jumper. 3.3.2 Jumper J2 When the jumper on J2 is in place, the FF 8 performs its own ground fault tests. When the power supply...
Page 17
FireForce 8 Installation & Operation Manual P/N 52257:B 09/27/2006 17 Section 4: Operation 4.1 Start-up Procedure Connect A.C. first, then connect batteries 4.2 Operating Instructions 4.2.1 Alarm Condition Alarm devices operate in unison with the Main FACP alarm devices. The alarm-activated outputs are reset through operation of the Reset switch on the Main FACP. 4.2.2 Trouble Condition The associated trouble LED (yellow) will illuminate. 4.2.3 Testing and Maintenance System Testing should be...
Page 18
18 FireForce 8 Installation & Operation Manual P/N 52257:B 09/27/2006 OperationBattery Applications
Page 19
FireForce 8 Installation & Operation Manual P/N 52257:B 09/27/2006 19 Appendix A: Compatible Devices A.1 Compatible Notification Devices Part # Catalog # Part # Catalog # Part # Catalog # 70871 MIZ-24-R 71562 SR-24110-HFR 71717 RSSP-24110W-FR 70873 MIZ-24-W 71569 RSP-241575-VFR 71727 AS-2415C-FW 71138 MT-12/24-R 71573 AMT-12/24-R 71728 AS-2430C-FW 71140 MT-24-WM-VFR 71574 AMT-24-LS-VFR 71729 AS-2475C-FW 71287 MIZ-24-LS-VFR 71575 AMT-24-IS-VFR 71730 RSS-2415C-FW 71288 MIZ-24-LSM-VFR 71576...
Page 20
20 FireForce 8 Installation & Operation Manual P/N 52257:B 09/27/2006 Compatible Devices Synchronized Horns and Strobes A.2 Synchronized Horns and Strobes System Sensor FaradayGentex (Max 25 per ckt)Wheelock Gamewell Amseco SC2415_ 2700 Sync Series GEC Series AS-24MCW 72032 SHW24-153075 SC241575_ GES Series RSS-24MCW 72033 SLW24-153075 SC2430_ GEH Series 72035 SHW24W-75110 SC2475_72036 SLW24W-75110 SC2495_HW-24A SC24115_HW-24 SC24177_ PC2415_ PC241575_ PC2430_ PC2475_ PC2495_ PC24115_ PC24177_