Honeywell Fire Force 8 Manual
Have a look at the manual Honeywell Fire Force 8 Manual online for free. It’s possible to download the document as PDF or print. UserManuals.tech offer 178 Honeywell manuals and user’s guides for free. Share the user manual or guide on Facebook, Twitter or Google+.
INSTALLATION & OPERATION MANUAL FireForce 8 NOTIFICATION APPLIANCE CIRCUIT EXPANDER P/N 52257:B • ECN 06-683 • 09/27/2006
2 FireForce 8 Installation & Operation Manual P/N 52257:B 09/27/2006 Fire Alarm System Limitations While a fire alarm system may lower insurance rates, it is not a substitute for fire insurance! An automatic fire alarm system—typically made up of smoke detectors, heat detectors, manual pull stations, audible warning devices, and a fire alarm control panel with remote notification capability—can provide early warning of a develop- ing fire. Such a system, however, does not assure protection against property damage or loss of life resulting from a fire. The Manufacturer recommends that smoke and/or heat detec- tors be located throughout a protected premise following the recommendations of the National Fire Protection Association Standard 72 (NFPA 72), manufacturers recommendations, State and local codes, and the recommendations contained in the Guides for Proper Use of System Smoke Detectors, which are made available at no charge to all installing dealers. These documents can be found at http://www.systemsen- sor.com/html/applicat.html. A study by the Federal Emer- gency Management Agency (an agency of the United States government) indicated that smoke detectors may not go off in as many as 35% of all fires. While fire alarm systems are designed to provide early warning against fire, they do not guarantee warning or protection against fire. A fire alarm sys- tem may not provide timely or adequate warning, or simply may not function, for a variety of reasons: Smoke detectors may not sense fire where smoke cannot reach the detectors such as in chimneys, in or behind walls, on roofs, or on the other side of closed doors. Smoke detectors also may not sense a fire on another level or floor of a building. A second-floor detector, for example, may not sense a first- floor or basement fire. Particles of combustion or “smoke” from a developing fire may not reach the sensing chambers of smoke detectors because: • Barriers such as closed or partially closed doors, walls, or chimneys may inhibit particle or smoke flow. • Smoke particles may become “cold,” stratify, and not reach the ceiling or upper walls where detectors are located. • Smoke particles may be blown away from detectors by air outlets. • Smoke particles may be drawn into air returns before reaching the detector. The amount of “smoke” present may be insufficient to alarm smoke detectors. Smoke detectors are designed to alarm at various levels of smoke density. If such density levels are not created by a developing fire at the location of detectors, the detectors will not go into alarm. Smoke detectors, even when working properly, have sensing limitations. Detectors that have photoelectronic sensing chambers tend to detect smoldering fires better than flaming fires, which have little visible smoke. Detectors that have ion- izing-type sensing chambers tend to detect fast-flaming fires better than smoldering fires. Because fires develop in different ways and are often unpredictable in their growth, neither type of detector is necessarily best and a given type of detector may not provide adequate warning of a fire. Smoke detectors cannot be expected to provide adequate warning of fires caused by arson, children playing with matches (especially in bedrooms), smoking in bed, and violent explosions (caused by escaping gas, improper storage of flammable materials, etc.). Heat detectors do not sense particles of combustion and alarm only when heat on their sensors increases at a predeter- mined rate or reaches a predetermined level. Rate-of-rise heat detectors may be subject to reduced sensitivity over time. For this reason, the rate-of-rise feature of each detector should be tested at least once per year by a qualified fire pro- tection specialist. Heat detectors are designed to protect property, not life. IMPORTANT! Smoke detectors must be installed in the same room as the control panel and in rooms used by the sys- tem for the connection of alarm transmission wiring, communi- cations, signaling, and/or power. If detectors are not so located, a developing fire may damage the alarm system, crip- pling its ability to report a fire. Audible warning devices such as bells may not alert people if these devices are located on the other side of closed or partly open doors or are located on another floor of a building. Any warning device may fail to alert people with a disability or those who have recently consumed drugs, alcohol or medica- tion. Please note that: • Strobes can, under certain circumstances, cause seizures in people with conditions such as epilepsy. • Studies have shown that certain people, even when they hear a fire alarm signal, do not respond or comprehend the meaning of the signal. It is the property owners responsi- bility to conduct fire drills and other training exercise to make people aware of fire alarm signals and instruct them on the proper reaction to alarm signals. • In rare instances, the sounding of a warning device can cause temporary or permanent hearing loss. A fire alarm system will not operate without any electrical power. If AC power fails, the system will operate from standby batteries only for a specified time and only if the batteries have been properly maintained and replaced regularly. Equipment used in the system may not be technically com- patible with the control panel. It is essential to use only equip- ment listed for service with your control panel. Telephone lines needed to transmit alarm signals from a premise to a central monitoring station may be out of service or temporarily disabled. For added protection against tele- phone line failure, backup radio transmission systems are rec- ommended. The most common cause of fire alarm malfunction is inade- quate maintenance. To keep the entire fire alarm system in excellent working order, ongoing maintenance is required per the manufacturers recommendations, and UL and NFPA stan- dards. At a minimum, the requirements of NFPA 72 shall be followed. Environments with large amounts of dust, dirt or high air velocity require more frequent maintenance. A main- tenance agreement should be arranged through the local man- ufacturers representative. Maintenance should be scheduled monthly or as required by National and/or local fire codes and should be performed by authorized professional fire alarm installers only. Adequate written records of all inspections should be kept. Limit-C1-2-2007
FireForce 8 Installation & Operation Manual P/N 52257:B 09/27/2006 3 Installation Precautions Adherence to the following will aid in problem-free installation with long-term reliability: WARNING - Several different sources of power can be connected to the fire alarm control panel. Disconnect all sources of power before servicing. Control unit and associ- ated equipment may be damaged by removing and/or insert- ing cards, modules, or interconnecting cables while the unit is energized. Do not attempt to install, service, or operate this unit until manuals are read and understood. CAUTION - System Re-acceptance Test after Software Changes: To ensure proper system operation, this product must be tested in accordance with NFPA 72 after any pro- gramming operation or change in site-specific software. Re- acceptance testing is required after any change, addition or deletion of system components, or after any modification, repair or adjustment to system hardware or wiring. All compo- nents, circuits, system operations, or software functions known to be affected by a change must be 100% tested. In addition, to ensure that other operations are not inadvertently affected, at least 10% of initiating devices that are not directly affected by the change, up to a maximum of 50 devices, must also be tested and proper system operation verified. This system meets NFPA requirements for operation at 0-49º C/32-120º F and at a relative humidity 93% ± 2% RH (non- condensing) at 32°C ± 2°C (90°F ± 3°F). However, the useful life of the systems standby batteries and the electronic com- ponents may be adversely affected by extreme temperature ranges and humidity. Therefore, it is recommended that this system and its peripherals be installed in an environment with a normal room temperature of 15-27º C/60-80º F. Verify that wire sizes are adequate for all initiating and indi- cating device loops. Most devices cannot tolerate more than a 10% I.R. drop from the specified device voltage. Like all solid state electronic devices, this system may operate erratically or can be damaged when subjected to light- ning induced transients. Although no system is completely immune from lightning transients and interference, proper grounding will reduce susceptibility. Overhead or outside aerial wiring is not recommended, due to an increased susceptibility to nearby lightning strikes. Consult with the Technical Ser- vices Department if any problems are anticipated or encoun- tered. Disconnect AC power and batteries prior to removing or inserting circuit boards. Failure to do so can damage circuits. Remove all electronic assemblies prior to any drilling, filing, reaming, or punching of the enclosure. When possible, make all cable entries from the sides or rear. Before making modifi- cations, verify that they will not interfere with battery, trans- former, or printed circuit board location. Do not tighten screw terminals more than 9 in-lbs. Over- tightening may damage threads, resulting in reduced terminal contact pressure and difficulty with screw terminal removal. This system contains static-sensitive components. Always ground yourself with a proper wrist strap before han- dling any circuits so that static charges are removed from the body. Use static suppressive packaging to protect electronic assemblies removed from the unit. Follow the instructions in the installation, operating, and pro- gramming manuals. These instructions must be followed to avoid damage to the control panel and associated equipment. FACP operation and reliability depend upon proper installation. Precau-D1-9-2005 FCC Warning WARNING: This equipment generates, uses, and can radiate radio frequency energy and if not installed and used in accordance with the instruction manual may cause interference to radio communications. It has been tested and found to comply with the limits for class A computing devices pursuant to Subpart B of Part 15 of FCC Rules, which is designed to provide reasonable protection against such interference when devices are operated in a commercial environment. Operation of this equipment in a residential area is likely to cause interfer- ence, in which case the user will be required to correct the interference at his or her own expense.Canadian Requirements This digital apparatus does not exceed the Class A limits for radiation noise emissions from digital apparatus set out in the Radio Interference Regulations of the Cana- dian Department of Communications. Le present appareil numerique nemet pas de bruits radi- oelectriques depassant les limites applicables aux appa- reils numeriques de la classe A prescrites dans le Reglement sur le brouillage radioelectrique edicte par le ministere des Communications du Canada. Acclimate Plus™, HARSH™, NIS™, Notifier Integrated Systems™, NOTI•FIRE•NET™, and ONYXWorks™ are all trademarks; and FlashScan®, NION®, NOTIFIER®, ONYX®, UniNet®, Ver iFi re ®, and VIEW® are all registered trademarks of Honeywell International Inc. Echelon® is a registered trademark and LonWorks™ is a trademark of Echelon Corporation. ARCNET® is a registered trademark of Datapoint Corporation. Microsoft® and Windows® are registered trademarks of the Microsoft Corporation. LEXAN® is a registered trademark of GE Plastics, a subsidiary of General Electric Company. ©2006 by Honeywell International Inc. All rights reserved. Unauthorized use of this document is strictly prohibited.
4 FireForce 8 Installation & Operation Manual P/N 52257:B 09/27/2006 Documentation Feedback Your feedback helps us keep our documentation up-to-date and accurate. If you have any comments or suggestions about our online Help or printed manuals, you can email us. Please include the following information: • Product name and version number (if applicable) • Printed manual or online Help • Topic Title (for online Help) • Page number (for printed manual) • Brief description of content you think should be improved or corrected • Your suggestion for how to correct/improve documentation Send email messages to: [email protected] Please note this email address is for documentation feedback only. If you have any technical issues, please contact Technical Services.
FireForce 8 Installation & Operation Manual P/N 52257:B 09/27/2006 5 Table of Contents Section 1 Introduction ............................................................................................................ 7 1.1: General Description ....................................................................................................................................... 7 1.2: Functional Description................................................................................................................................... 7 1.2.1: Normal Quiescent Operation ............................................................................................................... 7 1.2.2: Alarm Condition .................................................................................................................................. 7 1.2.3: Reset .................................................................................................................................................... 7 1.2.4: Trouble Condition ............................................................................................................................... 8 1.2.5: Normal AC Power Failure ................................................................................................................... 8 1.2.6: Delayed AC Power Failure .................................................................................................................. 8 1.2.7: Battery Operation ................................................................................................................................ 8 1.3: Electrical Operating Characteristics .............................................................................................................. 9 Section 2 Installation ............................................................................................................ 11 2.1: Mounting Instructions.................................................................................................................................. 11 2.2: Electrical Connections ................................................................................................................................. 11 2.3: Function of Input/Output Connections ........................................................................................................ 11 2.3.1: AC Connections................................................................................................................................. 11 2.3.2: Battery Connections .......................................................................................................................... 11 2.3.3: 24 VDC Out Terminals (Power Limited) .......................................................................................... 11 2.3.4: Earth Ground ..................................................................................................................................... 12 2.3.5: Trouble Relay .................................................................................................................................... 12 2.3.6: Power Fail .......................................................................................................................................... 12 2.3.7: Extender Output Circuit Wiring (Power Limited)............................................................................. 12 2.3.8: Reference EOL Resistor (Power Limited)......................................................................................... 13 2.3.9: Input signal wiring (Power Limited) ................................................................................................. 13 Section 3 Function of Switches, LEDs and Jumpers ......................................................... 15 3.1: Programming Switches .............................................................................................................................. 15 3.2: Function of LED Indicators ........................................................................................................................ 16 3.3: Jumper Functions ......................................................................................................................................... 16 3.3.1: Jumper J1 .......................................................................................................................................... 16 3.3.2: Jumper J2 .......................................................................................................................................... 16 3.4: Optional Class A Adapter ............................................................................................................................ 16 Section 4 Operation ............................................................................................................... 17 4.1: Start-up Procedure ....................................................................................................................................... 17 4.2: Operating Instructions ................................................................................................................................. 17 4.2.1: Alarm Condition ................................................................................................................................ 17 4.2.2: Trouble Condition ............................................................................................................................. 17 4.2.3: Testing and Maintenance ................................................................................................................... 17 4.3: Battery Applications .................................................................................................................................... 17 4.3.1: Battery Capacity ................................................................................................................................ 17 Appendix A: Compatible Devices ........................................................................................ 19 A.1: Compatible Notification Devices .............................................................................................................. 19 A.2: Synchronized Horns and Strobes ................................................................................................................ 20 Appendix B: FireForce 8 Battery Calculation Chart .......................................................... 21 Appendix C: Wiring Drawings ............................................................................................. 23 C.1: B-W479 Wiring Diagram: Notification Circuit Expander ........................................................................ 23 C.2: B-W479-1 Wiring Diagram: Synchronized Horn & Strobe .......................................................................24 C.3: C-M822, Assembly Drawing, FireForce 8 Cabinet .................................................................................... 25
Table of Contents 6 FireForce 8 Installation & Operation Manual P/N 52257:B 09/27/2006
FireForce 8 Installation & Operation Manual P/N 52257:B 09/27/2006 7 Section 1: Introduction 1.1 General Description The FIREFORCE 8 is a notification appliance circuit extender panel designed to extend the power capabilities of the existing notification appliance circuits and provide power for other ancillary devices. An FIREFORCE 8 panel consists of two notification appliance circuit inputs and four class B, style Y, two class A, style Z, or two class B and one class A notification appliance circuits. Two class B (1 class A) circuits will always be controlled by the first input, the other two class B (1 class A) circuits may be operated from either input. Each of these output circuits is capable of providing 3.0 amps of power limited notification appliance power and are supplied from an 8 Amp, 24 VDC power supply. Using the optional Class A Adapter, PN 31076, four class A outputs at 2.5A each may be obtained. Outputs may follow the inputs, or be programmed to provide temporal outputs for a steady input They can also be programmed to provide strobe and horn synchronizing signals when none are on the input. The internal sync. signals can permit horns and strobes to be connected to a single wire pair on each output, controlled by the two inputs, or they can be separated and operated on individual outputs. All inputs and outputs are supervised for open or shorted conditions. EOL resistor values can be changed by connecting a sample EOL resistor to the unit. This allows compatibility with existing NAC circuits. An internal battery charger is also provided with the FIREFORCE 8 to provide standby battery operation. The panel is mounted in a rigid sheet metal enclosure with the dimensions of (12 5/8W x 18H x 4 1/2D). 1.2 Functional Description 1.2.1 Normal Quiescent Operation In the normal quiescent condition the green Power On LED is illuminated indicating AC line operation. The yellow TRBL LEDs are off indicating that all supervision circuits are normal. 1.2.2 Alarm Condition Whenever an alarm condition occurs at the Main FACP the resultant 24V output from its indicating circuit will energize the connected polarity sensing inputs. This input will then activate the notification appliance output circuits on the FIREFORCE 8 according to how they are programmed. Input 1 will always control Outputs 1 and 2. Input 2 normally controls Outputs 3, and 4 (Default) however this pair of outputs can be programmed to operate from Input 1. The FIREFORCE 8 notification appliance circuits will follow steady, march time, temporal or coded signals from the main control panel, and will pass on strobe and horn synchronization signals if they are present on the input. When the unit is programmed to generate synchronization signals, combined horn and strobe synchronization signals are placed on each selected output pair and turned on and off by the inputs in the manner described as default above. NOTE:When the unit is programmed to generate synchronization signals and have all four outputs controlled by input 1, the strobe synchronization signals are placed on all four outputs when input 1 is active. When input 1 and 2 are active, the horn synchronization signals are combined with the strobe synchronization signals on all four outputs. In this manner, horns and strobes can be connected to same pair of wires on any output, and be controlled separately.
8 FireForce 8 Installation & Operation Manual P/N 52257:B 09/27/2006 Introduction Functional Description 1.2.3 Reset The FIREFORCE 8 will return to the quiescent condition automatically upon restoration of the Main FACP to normal operation 1.2.4 Trouble Condition A trouble condition is indicated by a TRBL LED illuminating and the common Form “C” TROUBLE FAIL relay contacts transferring. The trouble signal will be transmitted to the Main FACPs by opening the Indicating Circuits that are used to control the FIREFORCE 8. An alarm from the main control panel will override a trouble condition. The FIREFORCE 8 monitors its output notification appliance circuits for an open or shorted condition. Notification appliance circuits with a short circuit trouble can not be activated. A trouble is indicated by any one of the following conditions: 1.2.5 Normal AC Power Failure When the AC fails or falls below 100VAC at the 120VAC setting or 190VAC at the 240VAC setting, the FIREFORCE 8 will go into the Trouble condition. It will switch to Battery Operation, deactivate the Trouble and Power Fail relays, extinguish the AC On LED (LED 8), and transmit the trouble over the input Signal Circuits. 1.2.6 Delayed AC Power Failure When S7 AC 6HR is set (Dialer Operation) An AC failure will be handled in the same manner as above EXCEPT the TROUBLE relay will not transfer, and the failure notification will not be transmitted over the input Signal Circuits until the failure has existed for 6 hours. The POWER FA I L relay will transfer in order to provide an external trouble indication. 1.2.7 Battery Operation Indicated by the extinguishing of the green Power On LED. Standby operation occurs whenever the main power source fails or falls below 100VAC @ 120VAC setting or 190VAC @ 240VAC setting. In this situation the FIREFORCE 8 will automatically transfer system operation to the standby battery set without the loss of any alarm condition present prior to the transfer. The FIREFORCE 8 panel will transfer back to the main power source when the operating voltage returns to 105VAC @ 120VAC setting or 194VAC @ 240VAC setting. Should the battery become disconnected, have a blown fuse, or develop low voltage, the FIREFORCE 8 will indicate a Battery fault and light LED 2. Replace batteries when required. Indicator Name Trouble Condition LED 8 PWR ON A brown-out or black-out AC line condition LED 7 AUX TRBL A low or missing output, or a short circuit on the AUXilliary output LED 6 BATT TRBL A low or missing battery LED 5 GF TRBL An earth fault on external wiring LED 4, 3, 2, 1 SIG(4,3,2,1) TRBL A short circuit or an open on a supervised notification appliance circuit
FireForce 8 Installation & Operation Manual P/N 52257:B 09/27/2006 9 Electrical Operating CharacteristicsIntroduction 1.3 Electrical Operating Characteristics Input Voltage 120 VAC @ 3.3 Amps or 240 VAC @ 2 Amps (Jumper selected)50/60 Hz. Input Control Signal 10VDC to 30VDC, or 12V to 28V Full Wave Rectified, Polarity Reversing. Output Voltage 24 Volt DC @ 8Amps NAC outputs 1- 4 3.0 Amps Maximum per output. NAC outputs 1- 4 With optional Class A adapter2.5 Amps Maximum per output. AUX Power 0.15 Amps under all conditions. 2.0 Amps if load is removed during operation from battery. Total System Current Total loading on all outputs shall not exceed 8 Amps.
10 FireForce 8 Installation & Operation Manual P/N 52257:B 09/27/2006 Introduction Electrical Operating Characteristics