Home > Honeywell > Integrated Circuit > Honeywell Fire Force 8 Manual

Honeywell Fire Force 8 Manual

    Download as PDF Print this page Share this page

    Have a look at the manual Honeywell Fire Force 8 Manual online for free. It’s possible to download the document as PDF or print. UserManuals.tech offer 178 Honeywell manuals and user’s guides for free. Share the user manual or guide on Facebook, Twitter or Google+.

    							FireForce 8 Installation & Operation Manual  P/N 52257:B  09/27/2006 11
    Section 2: Installation 
    2.1  Mounting Instructions
    The standard mounting is a surface mount cabinet.  The unit must be securely attached to a 
    permanent partition using suitable fasteners.  Four mounting holes are provided to accept 1/4-inch 
    dia. screws max.  There are nine combination knockouts provided, located three on the top and 
    three on each side of the cabinet. Knockouts can accept 1/2, or 3/4 inch conduit. 
    2.2  Electrical Connections
    For field wiring connections, refer to Inter-equipment Wiring DWG. No. B-W479 in Appendix C.1.
    2.3  Function of Input/Output Connections
    2.3.1  AC Connections
    120VAC or 240VAC connects to the AC Terminal Block on the Power Supply    
    2.3.2  Battery Connections
    Batteries connect to the BATT+, BATT- terminals. Sealed Lead Acid Batteries are required to 
    provide 24 Volts DC @ 8 Amps max. The maximum battery size allowable is 26AH. Larger battery 
    packs with there own enclosures and chargers can be accommodated by removing the jumper on J1, 
    which disables the internal battery charger. Connect ONLY using a 15A fuse.
    2.3.3  24 VDC Out Terminals (Power Limited)
    Auxiliary Power Output  @ 24 Volts DC, 150 mA, (2.0 Amps maximum if an external disconnect is 
    used during periods of power failure). Two terminals are provided (+, -). Power limited output of 
    2.0 amps. (Deduct the current used from the 8 Amps total system load). 
    Connections for the A.C. Mains
    J1 Terminal
    L1 (Hot) GND L2 (Neutral)
    !WARNING: When installing to operate from 240VAC, it is necessary to remove the jumper E1 - E2 
    on the power supply printed circuit board.  Failure to do so will result in damage to the power 
    supply when AC voltage is applied.
    Connections for the Battery
    TB1 TERMINALS
    BATT+ BATT-
    Connections for the 
    Auxiliary 24VDC 
    TB4 TERMINALS
    A+ A- 
    						
    							12 FireForce 8 Installation & Operation Manual  P/N 52257:B  09/27/2006
    Installation Function of Input/Output Connections
    2.3.4  Earth Ground
    Connect to Earth Ground on the Power Supply module.  
    2.3.5  Trouble Relay
    The common trouble relay is a normally energized Form C relay that transfers when the 
    FIREFORCE 8 detects a trouble condition.  The contacts are rated for 2 amps @ 30VDC with a 
    power factor of 0.6 or higher.  
    2.3.6  Power Fail 
    The Power Fail relay is a normally energized Form C relay that transfers when a power failure or 
    brown out condition exists.  The contacts are rated for 2 amps @ 30VDC with a power factor of 0.6 
    or higher. 
    2.3.7  Extender Output Circuit Wiring (Power Limited) 
    The FIREFORCE 8 Notification Appliance Circuit outputs can provide up to 3.0 Amps (power 
    limited) of 24 VDC each (total panel output is limited to 8 Amps). The outputs can be arranged as 4 
    Style Y (Class B), 2 Style Z (Class A) or 1 Style Z and 2 Style Y circuits. The EOL resistor value 
    for Style Y wiring is 3.9K ohms unless a reference resistor of a different value is used. Terminals 
    (n) L1 and (n) L2 are connections for style Y (Class B) wiring These designations are preceded by 
    the circuit number (n). When Style Z (Class A) wiring is used, terminal 1L1 will return to terminal 
    2L1 and terminal 1L2 will return to terminal 2L2, likewise, terminal 3L1 will return to terminal 
    4L1 and terminal 3L2 will return to terminal 4L2 for the second Class A circuit. Terminal L1 
    switches negative and terminal L2 switches positive during alarm condition. Either pair of 
    circuits can be designated Class A or Class B independently of the other pair.  
    Earth Ground Connections
    J1 Terminals
    GND
    Trouble Fail
    TB2 Terminals
    NC Comm NO
    Power Fail
    TB2 Terminals
    NC Comm NO
    Style Z - Class A
    Notification Appliance Circuit  Connections
     TerminalsCircuit Style Y - Class B
    Notification Appliance 
    Circuit  Connections
     Terminals
    1L1 2L1 1L2 2L2 1 1L1 2L2
    - - - - 2 2L1 2L2
    3L1 4L1 3L2 4L2 3 3L1 3L2
    - - - - 4 4L1 4L2 
    						
    							FireForce 8 Installation & Operation Manual  P/N 52257:B  09/27/2006 13
    Function of Input/Output ConnectionsInstallation 
    2.3.8  Reference EOL Resistor (Power Limited)
    To accommodate existing Notification Appliance circuits that have EOL resistors of various values, 
    provisions are made to attach a reference EOL resistor, matching the existing EOL, within the 
    range of 2.0K to 25.0K ohms. Normally, a 3.9K resistor should be attached to the Ref. 
    Terminals. All Style Y (Class B) outputs must have EOL resistors of the same value as the 
    reference resistor. EOL values outside of the 2.0K – 25.0 K range will cause all of the Style Y NAC 
    output Trouble LEDs to light steady.  
    2.3.9  Input signal wiring (Power Limited)
    The main FACP notification appliance circuit inputs are +IN, -IN. When polarity is reversed on the 
    main FACP notification appliance circuit, the output circuits on the FIREFORCE 8 will activate 
    according to their programming. These inputs restore when the Main FACP circuit is restored. +IN 
    and -IN are internally connected to +OUT and -OUT for connection to devices beyond the 
    FIREFORCE 8. Should a trouble condition occur, the circuit is opened. If an alarm is received 
    during trouble the circuit is restored to allow devices beyond the FIREFORCE 8 to be operated. 
    Signal 1 always activates output Signal Circuits 1 and 2., and depending on the position of switch 
    SW1-8 can also control output Signal Circuits 3 and 4. Otherwise, Signal 2 controls output Signal 
    Circuits 3 and 4.     
    Ref
    TB3 Terminals
    REF+ REF-
    NOTE:When the Strobe Sync. Added mode is selected, and Ckts. 3 and 4 are controlled by Input 
    1, and a single input is to control both the Horns and the Strobes, The Output of Input 1 should be 
    connected to the Input of Input 2, and the signal Ckt. continuation or EOL resistor should be 
    connected to the output of Input 2. 
    Signal 1 
    Te r m i n a l s1+IN 1-IN 1+OUT 1-OUT
    Signal 2 
    Te r m i n a l s2+IN 2-IN 2+OUT 2-OUT 
    						
    							14 FireForce 8 Installation & Operation Manual  P/N 52257:B  09/27/2006
    Installation Function of Input/Output Connections 
    						
    							FireForce 8 Installation & Operation Manual  P/N 52257:B  09/27/2006 15
    Section 3: Function of Switches, LEDs and Jumpers
    3.1  Programming Switches  
    Outputs 1 & 2
    SW-1.1 SW-1.2 Function
    SIG1/2A SIG1/2B
    Open Open Output follows the Input (Also passes Sync. signals) Should NOT 
    be used for Full Wave Rectified inputs
    Closed Open Steady Input, Temporal Output
    Open Closed Steady Input, Steady Output, Strobe Sync. added
    Closed Closed Steady input, steady output, noise eliminated.
    (Does NOT pass Sync. signals)
    Outputs 3 & 4
    SW-1.3 SW-1.4 Function
    SIG3/4A SIG3/4
    Open Open Output follows the Input (Also passes Sync. signals) Should NOT 
    be used for Full Wave Rectified inputs
    Closed Open Steady Input, Temporal Output
    Open Closed Steady Input, Steady Output, Strobe Sync. added
    Closed Closed Steady input, steady output, noise eliminated. 
    (Does NOT pass Sync. signals)
    Sync. Codes 
    ( Used ONLY if synchronizes. Added option is selected with switch 1-1 through 4)
    SW-1.5 SW-1.6 Function
    SYN/SEL A SYN/SEL B
    Open Open Gamewell Sync and Wheelock Sync
    Closed Open System Sensor Sync
    Open Closed Faraday Sync and Amseco Sync
    Closed Closed Gentex Sync
    Power Fail Reporting
    SW-1.7 Function
    AC 6HR
    Open TROUBLE FAIL reported immediately on power failure
    Closed  TROUBLE FAIL delayed for 6 hours on power failure
    Input Select 
    SW-1.8 Function
    SIG SEL
    Closed Outputs 3 / 4 controlled by Input 2
    Open Outputs 3 / 4 controlled by Input 1, also in Strobe Sync. Added mode, Input 1 controls 
    strobe synch. signals and, Input 2 controls the horn synch. signals, both of which can 
    be combined on all 4 outputs. 
    						
    							16 FireForce 8 Installation & Operation Manual  P/N 52257:B  09/27/2006
    Function of Switches, LEDs and JumpersFunction of LED Indicators
    3.2  Function of LED Indicators 
    3.3  Jumper Functions
    3.3.1  Jumper J1  
    When the jumper on J1 is in place, the internal Battery Charger is enabled. To disable the charger 
    and allow an external charger to maintain the batteries, remove this jumper.
    3.3.2  Jumper J2 
    When the jumper on J2 is in place, the FF 8 performs its own ground fault tests. When the power 
    supply common is connected to the power supply common of another device, such as when a 
    common battery is used for a FACP and the FF8, remove this jumper.
    3.4  Optional Class A Adapter
    The optional Class A Adapter allows the connection of four class A NAC circuits to the FireForce 
    8. This is a passive device that uses no power from the FF8. Install the adapter as described in 
    Drawing A-M1192, and attach the field wiring according to Drawing B-W479-4 in Appendix C.1.
    INDICATOR LED# Color Description
    PWR ON LED # 8 Green Indicates AC line operation.
    AUX TRBL LED # 7 Yellow Indicates a short or overload on the Aux. 
    Output.
    BATT TRBL LED # 6 Yellow Indicates a low battery voltage or missing 
    battery. 
    GF TRBL LED # 5 Yellow Indicates an external wiring connection is not 
    adequately isolated from the earth ground.
    NAC #4 LED # 4 Yellow Indicates a short or open circuit in the external 
    wiring.
    NAC #3 LED # 3 Yellow Indicates a short or open circuit in the external 
    wiring.
    NAC #2 LED # 2 Yellow Indicates a short or open circuit in the external 
    wiring.
    NAC #1 LED # 1 Yellow Indicates a short or open circuit in the external 
    wiring. 
    						
    							FireForce 8 Installation & Operation Manual  P/N 52257:B  09/27/2006 17
    Section 4: Operation
    4.1  Start-up Procedure
    Connect A.C. first, then connect batteries
    4.2  Operating Instructions
    4.2.1  Alarm Condition
    Alarm devices operate in unison with the Main FACP alarm devices. The alarm-activated outputs 
    are reset through operation of the Reset switch on the Main FACP.
    4.2.2  Trouble Condition
    The associated trouble LED (yellow) will illuminate.
    4.2.3  Testing and Maintenance
    System Testing should be performed periodically to insure proper operation.
    1. Test the indicating circuits by initiating an alarm or test at the Main FACP.
    2. Test for proper operation by actuating the notification appliance circuit the FIREFORCE 8 is 
    monitoring.
    3. Standby batteries and AC transfer are tested by interrupting the AC power line while an alarm 
    test condition exists (see 1 above).
    4.3  Battery Applications
    4.3.1  Battery Capacity
    Battery Capacity is 26 ampere-hours maximum for the FIREFORCE 8 using the internal battery 
    charger. The max. charging rate is 0.75 amps. Larger capacity batteries can be used with the 
    FireForce 8 if they are housed in an external UL listed enclosure, and use an external UL listed 
    battery charger with sufficient capacity to restore the full charge to the batteries in the required 
    time. To use an external battery charger, remove the jumper at J1. The alternate enclosure and 
    battery charger shall be Listed for Fire Protective Signaling use. 
    						
    							18 FireForce 8 Installation & Operation Manual  P/N 52257:B  09/27/2006
    OperationBattery Applications 
    						
    							FireForce 8 Installation & Operation Manual  P/N 52257:B  09/27/2006 19
    Appendix A: Compatible Devices 
    A.1  Compatible Notification Devices  
    Part # Catalog # Part # Catalog # Part # Catalog #
    70871 MIZ-24-R 71562 SR-24110-HFR 71717 RSSP-24110W-FR
    70873 MIZ-24-W 71569 RSP-241575-VFR 71727 AS-2415C-FW
    71138 MT-12/24-R 71573 AMT-12/24-R 71728 AS-2430C-FW
    71140 MT-24-WM-VFR 71574 AMT-24-LS-VFR 71729 AS-2475C-FW
    71287 MIZ-24-LS-VFR 71575 AMT-24-IS-VFR 71730 RSS-2415C-FW
    71288 MIZ-24-LSM-VFR 71576 AMT-24-LSM-VFR 71731 RSS-2430C-FW
    71289 MIZ-24-MS-VFR 71614 MT4-12/24-R 71732 RSS-2475C-FW
    71290 MIZ-24-IS-VFR 71616 SR-2475-VFR 71733 RSSP-2415W-FR
    71292 MT-24 -LS-VFR 71679 AS-2415W-FR 71736 ET70-2415W-FR
    71293 MT-24-LSM-VFR 71680 AS-241575W-FR 71737 ET70-241575W-FR
    71294 MT-24-MS-VFR 71681 AS-2430W-FR 71738 ET70-2430W-FR
    71295 MT-24-IS-VFR 71682 AS-2475W-FR 71739 ET70-2475W-FR
    71426 MT-24 -SL-VFR 71683 AS-24110W-FR 71740 ET90-2415C-FW
    71427 MT-24-SLM-VFR 71684 AS-24100C-FW 71741 ET90-2430C-FW
    71543 AS-2415-VFR 71685 NH-12/24-R 71742 ET90-2475C-FW
    71544 AS-241575-VFR 71686 NS-2415W-FR 71743 ET90-24100C-FW
    71545 AS-2430-VFR 71687 NS-241575W-FR 71744 E70-2415W-FR
    71546 AS-2475-VFR 71688 NS-2430W-FR 71745 E70-241575W-FR
    71547 AS-24110-HFR 71689 NS-2475W-FR 71746 E70-2430W-FR
    71548 SM-12/24-R 71690 NS-24110W-FR 71747 E70-2475W-FR
    71549 DSM-12/24-R 71691 RSS-2415W-FR 71748 E70-24110W-FR
    71550 RS-2415-VFR 71692 RSS-241575W-FR 71749 E90-2415C-FW
    71551 SR-2415-VFR 71693 RSSP-241575W-FR 71750 E90-2430C-FW
    71552 SRP-2415-VFR 71694 RSSP-2430W-FR 71751 E90-2475C-FW
    71553 RS-241575-VFR 71695 RSS-2430W-FR 71752 E90-24100C-FW
    71554 SRP-241575-VFR 71696 RSSP-2475W-FR 71758 CH90-24-W
    71555 SR-241575-VFR 71697 RSS-2475W-FR 71759 CH70-24-R
    71556 RS-2430-VFR 71698 RSS-24110W-FR 71760 CH70-2415W-FR
    71557 RSP-2430-VFR 71699 RSS-24100C-FW 71761 CH70-241575W-FR
    71558 RSP-2475-VFR 71711 AH-24WP-R 71762 CH70-2430W-FR
    71559 RS-2475-VFR 71712 RS-2415W-FR 71763 CH70-2475W-FR
    71560 RS-24110-HFR 71713 RS-241575W-FR 71764 CH70-24110W-FR
    71561 SRP-24110-HFR 71714 W3MT-24-VFR 
    						
    							20 FireForce 8 Installation & Operation Manual  P/N 52257:B  09/27/2006
    Compatible Devices Synchronized Horns and Strobes
    A.2  Synchronized Horns and Strobes
     
    System Sensor FaradayGentex
    (Max 25 per ckt)Wheelock Gamewell Amseco
    SC2415_ 2700 Sync Series GEC Series AS-24MCW 72032 SHW24-153075
    SC241575_ GES Series RSS-24MCW 72033 SLW24-153075
    SC2430_ GEH Series 72035 SHW24W-75110
    SC2475_72036 SLW24W-75110
    SC2495_HW-24A
    SC24115_HW-24
    SC24177_
    PC2415_
    PC241575_
    PC2430_
    PC2475_
    PC2495_
    PC24115_
    PC24177_ 
    						
    All Honeywell manuals Comments (0)