20 OPERATION AND FUCTIONS CONTENTS REMARKS 1. Fan voltage of each control mode 2. Control against (under) load (Load Control) 1) Purpose : To restore F/R-temperature which has risen by load (much foods in or frequent door openings) as soon as possible 2) Display : SPEED lights until the mode and speed icons flicker. 3) Conditions to start (from both Normal and Silence) F or R door open time exceeds 30 seconds at a time Freezer and Refrigerator load control starts respectively. Over...
Page 22
21 OPERATION AND FUCTIONS CONTENTS REMARKS 3. Control Time Chart of Each Mode 1) Start & stop of load control mode (Normal Control) Door F/ S F Fan R/ S R Fan Door Open30 sec. af ter OpenLoad Mode StartFrz. Load StopRez. Load Stop On + 5deg On + 5deg Frz. Overl oad InputFrz. Start Condition Frz. Stop ; after 20mi n. 20min. 20min. Ref. Load 14V 14V 12V 12V 2) Start & stop of load control mode (Silence Control) Door F/S F Fan R/S R Fan Door Open30sec. after openLoad Mod e St artRef . Lo ad...
Page 23
22 OPERATION AND FUCTIONS CONTENTS REMARKS 4. Flow Chart of Load Control Mode Sart F/R door open time is over 30 sec. ? F/S ON + 5deg? R-sensor ON + 5deg? Fan RPM F Fan : 12V R Fan : 12V C Fan : 10VFan RPM Normal Overload F Fan : 10V 12V R Fan : 10V 12V C Fan : 10V 12V Overload of both compartments Y N Freezer Compartment Overload Refrigerator Compartment Overload Y N Y N F load control ; over 20 min. ? F-sensor OFF point ? Overload mode...
Page 24
23 OPERATION AND FUCTIONS Defrosting Cycle INPUT Control Object 1. Total comp. work time 2. Comp. work rate 3. RT temperature 4. Total door open time 1. Defrosting Mode CONTENTS REMARKS 1. Conditions to start defrosting cycle 1) Total comp. work time : 6, 8, 10 hours 2) Comp. work rate (by the 2 hours) : over 65% 3) Total door open time : 3 minutes (Any door - F or R - open time is over 3 minutes.) 4) Total time of [comp. ON + comp. OFF] : 60 hours 5) Ambient...
Page 25
24 OPERATION AND FUCTIONS CONTENTS REMARKS 3. Flow Chart of Defrosting Start Start Ambient temp. is over 35 ? Comp. work time is over 10 hours ? Total time is over 60 hours ? Comp. work time is over 6 hours ? Any error ? Comp. work rate is over 65 % ? EndDefrosting mode starts. Yes Yes Yes Yes Yes Yes No No No No No NoComp. work time is over 2 hours ? Total door open time is over 3 minutes ? Yes Yes No No Comp. work time is over 8 hours ? No No
Page 26
25 OPERATION AND FUCTIONS Defrosting Mode INPUT Control Object 1. Defrosting Cycle 1. COMP 2. F-FAN 3. R-FAN 4. HEATER CONTENTS REMARKS 1. Defrosting Mode 1) Time ; 50 minutes 2) Comp. / F-fan : ON R-fan : Control Heater : OFF 3) If F-sensor≤- 27 , PRE-COOL becomes OFF. 1) If D-sensor ≥10 , Heater becomes OFF. 2) In case of Heater return by time limit of 40 or 80 min (F3-Error) 3) Heater is ON for 30 minutes (time limit) in case of D- sensor error. 4) Time...
Page 27
26 OPERATION AND FUCTIONS Error Display (LCD Display of F-PCB) E1 I sensor; disconnection, short EF FLOW sensor; disconnection, short Et Level sensor sw error E9 Water supply Error EA Continuously Ice drop 3times at Et. Eu Fully Ice sensor sw error INPUT Control Object 1. Temperature Control Buttons CUSTOM LCD CONTENTS REMARKS 1. How to start 1) Set LOCK ON first. 2) Push Refrigerator Set button 5 times while pushing Freezer Set button. 2. Display Error code is displayed on...
Page 28
27 OPERATION AND FUCTIONS CONTENTS REMARKS 6. Control Way of Errors (if any) 1) F1 ERROR Cause : F-sensor disconnection / short (pull-down) Control : Comp. / F-fan ON for 25min., OFF for 25min. if F-sensor is normal, the error is terminated automatically. 2) r1 ERROR Cause : R-sensor disconnection / short (pull-down) Control : Condition of ambient temperature RT/S In ERROR ~13 14 ~19 20 ~29 29 ~ Work rate ON/OFF 8 / 12 7 / 13 8 / 12 8 / 12 9...
Page 29
28 OPERATION AND FUCTIONS 9) EI ERROR Cause : I-SENSOR disconnection / short (pull-down) Control : After water suppy, Ice drop every 4.8hour. Termination : When I-SENSOR is normal. 10) Ft ERROR Cause : When Level SW is ERROR Control : Time control (Skip water supply mode) Termination : Normal 11) EF Error Cause : When Flow-sensor is ERROR(There is no Pulse during some time.) When water supply valve is ON...
Page 30
29 OPERATION AND FUCTIONS Forced Defrosting INPUT Control Object 1. FREEZER SET. Button 2. REFRIGERATOR SET. button 3. LOCK button Defrosting Mode CONTENTS REMARKS 1. How to start Set LOCK ON first, then push REFRIGERAOTR SET. button 5 times while pushing FREEZER SET. button simultaneously. 2. How to proceed 1) Delete Pre-cool mode. (Others are same as normal defrosting.) 2) Heater is ON regardless of D-sensor temp. at first 30 seconds. ( Check of defrosting current)...