Carrier Air 5 Manual
Have a look at the manual Carrier Air 5 Manual online for free. It’s possible to download the document as PDF or print. UserManuals.tech offer 29 Carrier manuals and user’s guides for free. Share the user manual or guide on Facebook, Twitter or Google+.
T-- 298 3-7 3.5.4 Upper Scroll Assembly Removal a. Remove exterior cover assembly. Refer to paragraph 3.5.1. b. Remove 4 screws securing upper scroll assembly to the lower scroll assembly. (See Figure 3-18) c. Gently pry 4 snap clips open and lift the upper scroll assembly off of the lower scroll assembly. d. Reverse above procedure for reassembly. Screws 4 Places Snap Clip 4 Places Figure 3-18 Upper Scroll Assembly 3.5.5 Motor Assembly and Condenser Fan Removal a. Remove exterior cover assembly. Refer to paragraph 3.5.1. b. Remove control box assembly. Refer to paragraph 3.5.3. c. Remove upper scroll assembly. Refer to paragraph 3.5.4. d. Remove 4 screws securing the condenser cover to the condenser orifice. (See Figure 3-24.) e. Carefully disconnect motor wire terminations from within the control box. f. Remove 1 screw securing the motor ground lead to the motor bracket assembly. (See Figure 3-19) g. Using flat-- nosed pliers, depress the motor spring clamp and slide it off of the condenser fan (See Figure 3-20). h. Lift and slide motor towards evaporator coil to remove condenser fan from the motor shaft.i. Remove condenser fan from motor shaft and lift fan out through the top of the condenser orifice. (See Figure 3-22) j. Remove motor assembly. k.Reverse above procedure for reassembly. Motor Ground Lead Ground screw Figure 3-19 Motor Assembly Spring Clamp Figure 3-20 Spring Clamp Removal Motor Clip Figure 3-21 Motor Clip Removal
T-- 2983-8 Condenser Fan Figure 3-22 Condenser Fan Removal 3.5.6 Evaporator Blower Wheel Adjustment or Removal a. Remove exterior cover assembly. Refer to Exterior Cover Assembly Removal instructions 3.5.1 b. Remove control box assembly. Refer to Control Box Assembly Removal instructions 3.5.3 c. Remove upper scroll assembly. Refer to Upper Scroll Assembly Removal instructions 3.5.4 d. Loosen motor assembly. Refer to Motor Assembly Removal instructions 3.5.5. e. Mark shaft at a point where wheel hub and motor shaft meet to aid in reassembly.(See Figure 3-23.) f. Remove 1 set screw holding the blower wheel to the motor shaft. (See Figure 3-23) g. Slide off blower wheel from motor shaft h. Reverse above procedure for reassembly. Set Screw Figure 3-23 Blower Wheel 3.5.7Air Handling System Removal a. Remove exterior cover assembly. Refer to paragraph 3.5.1. b. Remove control box assembly. Refer to paragraph 3.5.3. c. Remove upper scroll assembly. Refer to paragraph 3.5.4. d. Remove motor assembly. Refer to paragraph 3.5.5. e. Remove 8 screws securing lower scroll assembly to the base pan assembly. f. Remove 1 screw from clamp securing suction tube to the base pan assembly. g. Remove 3 nuts securing the compressor to the base pan assembly. h. Remove 2 screws securing the condenser orifice to the base pan assembly. i. Remove 2 screws securing the condenser coil as- sembly to the base pan assembly. j. Carefully lift the entire assembly off of the base pan assembly. k. Reverse the above procedure for reassembly, ensur- ing that the air handling systemis positioned correct- ly. Tighten all screws. Condenser Cover Condenser Cover Screws Compressor Motor Assembly Base Pan Base Pan Figure 3-24 Condenser With Motor Assembly & Compressor
T-- 298 3-9 3.5.8Capacitor Troubleshooting WARNING Disconnect power to the AirV unit before checking the capacitor. To test capacitor to determine if good, open or shorted, an ohm meter can be used. To determine a capacitor ’s capacitance, a capacitor meter is required. Capacitors showing signs of leaks or bulging should be replaced immediately. 3.5.9Capacitor Testing and Replacement Capacitors must be discharged properly before testing. a. Place a 20,000 ohm, 2 watt resistor across the termi- nals of the capacitor for approximately 30 seconds (See Figure 3-25 for a suggested tool). WARNING Do not touch the metal of the screwdriver when discharging the capacitor. You could receive a shock. b. After the capacitor has been discharged and all wires removed from the capacitor terminals, use an ohm-- meter to test its resistance. c. Set the scale to R x 1K or 10K ohm and place the ohmmeter leads across the capacitor terminals. d. If the ohmmeter first reads 0, then rises toward infinity or some higher resistance, the capacitor is good. e. If the ohmmeter goes to 0 or a low resistance and stays there, the capacitor is shorted and needs to be replaced. f. If the ohmmeter reads infinity (OL) the capacitor is open and needs to be replaced. CLIP TO SCREWDRIVERTOUCH TO CAPACITOR TERMINALS TO DISCHARGE CAPACITOR 20,000 -- OHM 2 -- WATT RESISTOR INSULATED SCREWDRIVER ATTACH TO CLEAN UNPAINTED METAL PART OF UNIT FRAME Figure 3-25 Set--Up For Discharging a Capacitor 3.5.10 Positive Temperature Coefficient Thermister (PTC) (Start Thermistor) Troubleshooting a. Disconnect power from the AirV unit. b. Disconnect the wires to the PTC. c. Using an ohm meter, check for continuity across the PTC. If the PTC does not have continuity, it must be replaced. If continuity exists, reconnect the wires to the PTC. d. Reconnect power to the AirV unit. e. Turn on the AirV unit to start. f. Use a clamp-- on amp probe to monitor the amp draw of the compressor during its start-- up.When the compressor starts, an amp draw will be indicated for almost a second. If no amp draw is indicated or if the amp draw occurs for much longer than a second, the PTC is defective and must be replaced. 3.5.11 Line Voltage -- 10% Line voltage should be checked during peak electrical load periods. With the AirV unit on and the compressor operating, use a voltmeter to check the voltage being supplied to the AirV unit. The voltage must be within 10% of the units required voltage. A voltage drop greater than 10% will cause a premature compressor failure and needs to be corrected immediately.
T-- 2983-10 3.6 SERVICE -- UPPER UNIT -- LOW PROFILE 3.6.1 Exterior Cover Removal CAUTION Coil fins are sharp. Use care when removing the cover form the base pan to avoid per- sonal injury. To remove the exterior cover, do the following: a. Before working on unit place the master switch in the OFF position and disconnect all electrical power. b. Remove (8) screws securing the unit cover to the base pan assembly. See Figure 3-26. c. Carefully lift the exterior cover off of the unit base pan assembly. d. Reverse above procedure for reassembly. Screws Screws Figure 3-26 Cover Assembly -- Low Profile 3.6.2 Upper Scroll Assembly Removal To remove the upper scroll assembly, do the following: a. Remove exterior cover assembly. Refer to paragraph 3.6.1. b. Release the (2) front, (2) rear, (1) left side and (1) right side locking tabs (See Figure 3-27) by pulling back on the tabs (See Figure 3-28). c. Remove the screw (1) from the control box cover (See Figure 3-27). d. With all (6) locking tabs released and control box screw removed, lift the upper scroll assembly off of the lower scroll assembly. e. Reverse above procedure for reassembly. Ensure all (6) locking tabs snap shut & lock. b. b. b.b. b. b.c. Figure 3-27 Upper Scroll Assembly Locking Tabs (b.) & Screw Locations (c.) Figure 3-28 Upper Scroll Assembly Keeper Tab Release
T-- 298 3-11 Evaporator Coil Condenser Coil Figure 3-29 Upper Scroll & Control Box Cover Removed 3.6.3 Condenser Fan Assembly Removal To remove condenser fan assembly, do the following: a. Perform steps outlined in Section 3.6.2. b. Depress and remove Retaining Ring (See Figure 3-30). c. Using both hands, carefully pull up on fan assembly until it is free of the motor shaft. d. When replacing the fan assembly make sure the fan assembly is against the stop on the shaft (See Figure 3-31) e. Push back on tab to allow fan assembly to rest against stop (See Figure 3-32). Fan assembly will now be flush with the end of the motor shaft. f. Reverse above procedure for reassembly. Retaining Ring Figure 3-30 Condenser Fan Assembly & Retaining Ring Fan Stop Condenser Motor13MM Bolt13MM Bolt Grommet Figure 3-31 Condenser Fan Motor & Fan Assembly Stop Ta b Figure 3-32 Condenser Fan Motor & Fan Assembly Tab
T-- 2983-12 3.6.4 Condenser Motor Removal To remove condenser fan motor, do the following: a. Perform steps outlined in Section 3.6.2. b. Remove (3) 13MM bolts (See Figure 3-31). c. Remove (3) Grommets. Inspect, replace or reuse. d. Cut Tie-- Wraps & discard (2 locations). When re- assembling, tie-- wrap at same 2 locations. e. Remove ground wire from compressor bracket (See Figure 3-33). f. Un-- plug (yellow/brown/white) from control box as- sembly. g. Reverse above procedure for reassembly. Cond. Motor Ground Screw Comp. Mounting Bolt Figure 3-33 Condenser Motor Ground 3.6.5 Evaporator Motor/Blower Assembly Removal To remove the evaporator motor, do the following: a. Perform steps outlined in Section 3.6.2. b. Pull back on and release the (4) locking tabs. There are 2 on each side of the control box assembly. (See Figure 3-34). c. Lift control box assembly from lower scroll assembly, exposing evaporator motor. d. Un-- plug (black/blue/white/brown) evaporator motor from control box assembly. e. Remove ground wire (green/yellow) from motor housing. f. Lift motor/blower assembly from lower scroll assem- bly cradle. g. Carefully remove the blower wheel from the evapora- tor motor shaft by pushing out from the motor side. Blower Side Locking Tabs Outside Locking Tabs Figure 3-34 Evaporator Motor Locking Tabs Cradle Lower Scroll Assembly Capacitor Figure 3-35 Evaporator Motor/Blower Assembly In Cradle
T-- 298 3-13 NOTE When reassembling the blower wheel on to the motor shaft ensure that the blower wheel is flush with the end of the motor shaft(SeeFigure 3-36). h. Reverse above procedure for reassembly. Wheel Flush With Motor Shaft Figure 3-36 Evaporator Blower Wheel (Flush With End Of Motor Shaft)NOTE When placing the evaporator motor/blower assembly back into the lower scroll assem- bly cradle, make sure that the assembly is seated securely in the cradle. (See Figure 3-35). 3.6.6 Compressor Replacement Perform the procedures outlined in Section 3.5.2 There are 4 bolts with the Low Profile Compressor. The system charge for the Low Profile unit is 16.9 OZ. 3.6.7 Capacitor Removal To remove the capacitor, do the following: a. Perform steps a., b. & c. as outlined in Section 3.6.5. b. Perform steps outlined in Sections 3.5.8 & 3.5.9. c. The Low Profile Capacitor is removed from the con- trol box assembly by pushing on the capacitor from under the control box assembly (See Figure 3-35). Capacitor Control Box Assembly Terminal Block Upper Scroll Assembly Figure 3-37 Control Box Assembly With Capacitor 3.6.8 Remote Control (Fahrenheit to Celsius) All Remote Control Assemblies in the United States are pre-- set to display in Fahrenheit degrees (see Figure 3-38). To change from a Fahrenheit display to a Celsius display do the following: CAUTION The change from Fahrenheit to Celsius will be permanent. It cannot be changed back to Fahrenheit.
T-- 2983-14 a. Remove the batteries from the remote control. b. Carefully remove the remote cover by inserting a nar- row flat object between the cover and remote body and prying apart. c. Remove the brass screw holding the PCB in place. d. Carefully remove the PCB board from the remote body, making sure the battery springs release from their holders. e. Locate FR9 on the PCB board (see Figure 3-39).f. Carefully cut the FR9 jumper wire. g. Reverse above procedure for reassembly. CAUTION When re-- assembling, ensure the battery springs are correctly placed in the battery spring holders. PCB COVER BODY BATTERIES & COVER Battery SpringsSpring Holders Figure 3-38 Remote Control Components FR9 PCB Figure 3-39 Remote Control PCB (FR9 Location)
T-- 298 3-15 3.7 THERMOSTAT INSTALLATION AND START -- UP INSTRUCTIONS (WALL MOUNTED) 3.7.1 Introduction The thermostat is a wall mounted, low-- voltage thermostat which maintains room temperature by controlling the operation of a heating and air conditioningsystem. Batteriesare not required; temperature and mode settings are preserved with the power off. CAUTION Improper wiring or installation may damage thermostat. Wiring must conform to local and national electrical codes. WARNING Before installing thermostat, turn off all power to unit. There may be more than one power disconnect. Electrical shock can cause personal injury or death. 3.7.2 Installation NOTE Read all instructions before starting the installa- tion. NOTE The thermostat requires no batteries. The ther- mostat is not a power stealing device and MUST have both R and C connected. 3.7.3 Thermostat Location The thermostat should be mounted: Approximately 5 foot (1.5m) from the floor. Close to or in a frequently used room, preferably on an inside partitioning wall. On a section of wall without pipes or duct work. The thermostat should NOT be mounted: Close to a window, or an outside wall, or next to a door leading to the outside. Exposed to direct light and heat from a lamp, sun, fire- place, or other temperature-- radiating object which may cause a false reading. Close to or in direct airflow from supply registers and return-- air grilles. In areas with poor air circulation, such as behind a door or in an alcove. 3.7.4 Install Thermostat -- 12VDC a. Turn off all power to unit. b. If an existing thermostat is being replaced: 1.Remove existing thermostat from wall.2.Disconnect wires from existing thermostat, one at a time. Be careful not to allow wires to fall back into the wall. 3.As each wire is disconnected, record wire color and terminal marking. 4.Discard or recycle old thermostat. NOTE Mercury is a hazardous waste and must be des- posed of properly. c. Seperate the front and back pieces of plastic. d. Route thermostat wires through hole in back piece of plastic. Level plastic against wall (for aesthetic value only -- thermostat need not be leveled for proper op- eration) and mark wall through 2 mounting holes. e. Drill two 3/16 inch mounting holes in wall where marked. NOTE Mounting holes on thermostat are designed to fit on a horizontal J-- Box. f. Secure back plastic to wall with 2 anchors and screws provided, making sure all wires extend through hole in plastic. g. Connect wires to proper terminal of the connector block in the front piece of plastic. h. Pusr any excess wire back into wall. Excess wire in- side the thermostat plastic case can interfere with proper air flow across the temperature sensor. Seal hole in wall to prevent air leaks. Leaks can effect op- eration. i. Snap front and back pieces of plastic together. j. Turn on power to the unit. 3.8 LCD DISPLAY 3.8.1 Cool Only Thermostat (Part No. 1110-- 421) On power up, the LCD readout will display C (Cool Only). 3.8.2 Heat/Cool Thermostat (Part No. 1110-- 420) On power up, the LCD readout will display HC (Heat/ Cool). 3.9 SET THERMOSTAT CONFIGURATION While in configuration mode, three option choices can be made. A--Anticipator Value Adjustment d--Display Temperature Fahrenheit/Celcius Selection oF--Offset Adjustment For Room Temperature 3.9.1 Enter Configuration Mode Enter and hold the FAN button for approximately 10 sec- onds until room temperature disappears and the display readsA. You are now in the configuration mode.
T-- 2983-16 NOTE If the FAN button is pressed again or if no button is pressed for two minutes, the thermostat will exit the configuration mode and return to nor- mal operation. To re-- enter the configuration mode, the FAN button must be pressed and held for 10 seconds again. While in the configuration mode, the following options are available: A. ANTICIPATOR -- Value Adjustment This adjustment controls the sensitivity and cycle rate of the thermostst. Higher numbers decrease the sensitivity and slow the cycle rate. Lower numbers increase the sensitivity and increase the cycle rate. However, a limiting feature will not allow more than 4 equipmentcyclesper hour, regardless of setting. Values can range from 1 to 3. Factory default setting is 2. This default selection will provide optimum performance in nearly all installations. Try it first. Do not change settings unless there is evidence of need to do so. Unlike conventional anticipators, this setting is not determined by current draw. There is no need to measure, know, or compensate for current. To A d j u s t : a. Enter configuration mode (if not already there). b. Use UP & DOWN buttons to displayA. c. Press MODE button once to display current value. d. Use UP & DOWN buttons to move between values. e. Press MODE buttonto return toA.UP &DOWN buttons now move between option choicesA,d,oFor press FAN button to exit configuration mode. d.Fahrenheit/Celsius Selection This selection operates the thermostat in either Fahrenheit or Celsius. To Select: a. Enter configuration mode (if not already there). b. Use UP & DOWN buttons to displayd. c. Press MODE button once to display current selection ofForC. d. Use UP & DOWN buttons to change betweenF&C. e. Press MODE buttonto return tod.UP &DOWN buttons now move between option choices; or press FAN button to exit configuration mode. oF. Room Temperature Offset Adjust Selection The selected number is the number of degrees, plus or minus, which will be added to the actual temperature. The numbers can range between -- 5 and +5. Factory default is 0. This adjusted value will be used as actual temperature for both display and control action. The effect is that a positive number selection will make the room temperature lower, and vice versa. The thermostat is calibrated within an accuracy of plus or minus 2 degrees when shipped from the factory; this adjustment will provide the best accuracy when set to o. To Select: a. Enter configuration mode (if not already there). b. Use UP & DOWN buttons to displayoF.c. Press MODE button once to display offset value. d. Use UP & DOWN buttons to select a value between -- 5 and 5. e. Press MODE buttonto return tooF.UP &DOWN buttons now move between option choices; or press FAN button to exit configuration mode. 3.10 CHECK THERMOSTAT OPERATION 3.10.1 Fan Operation (Cool Only) 1. Press FAN button, starting fan operation. FAN an- nunciator turns on; Lo is displayed in the room tem- perature area for 5 seconds indicating Fan Low Speed. 2. Press FAN button, FAN annunciator remains on; Hi is displayed in room temperature area for 5 seconds indicating Fan High Speed. 3. Press FAN button, stopping fan operation. FAN an- nunciator turns off. 3.10.2 Fan Operation (Heat/Cool) 1. Press FAN button, starting low fan (Lo) operation. FAN annunciator turns on. 2. Press FAN button, starting high fan (Hi) operation. FAN annunciator remains on. 3. Press FAN button, stopping fan operation. FAN an- nunciator turns off. 3.10.3 Cooling Operation (Cool Only) 1. Press and release MODE button until COOL is dis- played. 2. Press DOWN button until LCD readout reads 10 de- grees below room temperature. Cooling and High Fan system should begin to operate within 5 min- utes. 3.10.4 Cooling Operation (Heat/Cool) 1. Press and release MODE button until COOL is dis- played. 2. Press DOWN button until LCD readout reads 10 de- grees below room temperature. Cooling and High Fan system should begin to operate within 5 min- utes. 3.10.5 Heating Operation (Heat/Cool) 1. Press and release MODE button until HEAT is dis- played. 2. Press UP button until LCD readout reads 10 degrees above room temperature. Heating system should begin to operate within 1 minute. 3.11 CHECK THERMOSTAT OPERATION 3.11.1 Temperature Display The thermostat will display room temperature until the UP or DOWN button is pressed. The word SET appears when these buttons are pressed and the current set point is displayed. If no buttons are pressed for 5 seconds, the display will change back to show room temperature.