Carrier 42qg24-h Manual
Have a look at the manual Carrier 42qg24-h Manual online for free. It’s possible to download the document as PDF or print. UserManuals.tech offer 29 Carrier manuals and user’s guides for free. Share the user manual or guide on Facebook, Twitter or Google+.
28 CONNECTING REFRIGERANT PIPING (Cont.) 15.5 DESCRIPTION OF REFRIGERANT CONNECTIONS OF OUTDOOR UNIT. 15.6 DESCRIPTION OF REFRIGERANT CONNECTIONS OF HI WALL INDOOR UNITS 15.7 DESCRIPTION OF REFRIGERANT CONNECTIONS OF REFERIGERANT PIPING LINES 15.8 CUTTING AND FLARING TOOLS Make sure that have the required tools available before preparing refrigerant piping lines (1) Suction flare valve. (2) Suction service valve. (3) Suction port to open & close. (4) Cap for suction service valve. (5) Cap for suction port. (6) Liquid flare valve. (7) Liquid service valve. (8) Liquid port to open & close. (9) Cap for liquid service valve. (10) Cap for liquid port. Half Union Suction Half Union Liquid REFRIGERANT CONNECTIONS Pipe Cutter Flare Tool 7 & 9 4 5 23 1 8 6 10
29 Corrugated CuttingWrap Cutting CONNECTING REFRIGERANT PIPING LINES (Cont.) 15-9 STEPS FOR PREPARING REFRIGERANT PIPING LINES BEFORE CONNECTIONS ( IN CASE OF NOT USING THE OPTIONAL FACTORY REFRIGERANT PIPING LINES WITH THE FLARE NUTS ) STEP (1): Cutting refrigerant piping lines • Remove protective caps from copper pipe ends. • Position tube end downwards, cut the pipe to the required length with a pipe cutter. NOTE: • It is recommended to cut approx. 30→50 cm longer than the estimated pipe length. • Take care to ensure that the cut edge remains at a 90° angle with the side of pipe, and refer to the illustrations for examples of edges cut correctly and incorrectly. Removing the burrs • Remove burrs at the end of the connection pipe with a pipe reamer or a file. This process is important and should be done carefully to make a good flare and to prevent any gas leaking out. NOTE: When reaming, hold the pipe end downward and be sure that no copper scraps fall into the pipe. STEP (2): Removing the flare nuts from the indoor unit. Remove the suction and liquid flare nuts from the indoor unit connections. NOTES: • Do not remove the flare nuts from the indoor unit until refrigerant piping lines are ready for connections. • It is that easier to remove flare nuts from the indoor unit before being installed on the wall hang bracket. STEP (3): Removing the flare nuts from the outdoor unit Remove the suction and liquid flare nuts from the outdoor unit connections. NOTES: • Do not remove the flare nuts from the outdoor unit until refrigerant piping lines are ready for connection. • It is easier to remove flare nuts from the outdoor unit before being installed on the wall support. Debarring After Before 1: Connection pipes 2: Reamer 1 2 Pipe Cutter Correct CuttingInclined Cutting
30 CONNECTING REFRIGERANT PIPING LINES (Cont.) STEPS FOR PREPARING REFRIGERANT PIPING LINES BEFORE CONNECTIONS (Cont.) STEP (4): Mounting flare nuts on the refrigerant piping lines • Mount the suction flare nut on the other side of suction piping line. • Mount the liquid flare nut on the other side of liquid piping line. STEP (5): Flaring the Piping • Use flare tool to flare ends of both suction and liquid piping lines slide a flare nut on to the tube and modify the flare. NOTES: 1) Good flare should have the following characteristics : • Inside surface is glossy and smooth. • Edge is smooth and must not have any burrs or imperfections. • Tapered sides are of uniform length. 2) Be sure to apply a sealing cap or waterproof tape to prevent dust or water from getting into the refrigeration piping lines before they are used. Avoid incorrect flaring, which results in damaged or cracked or inclined with uneven thickness surface. STEP (6): Mounting flare nuts on the other side of refrigerant piping lines • Mount the suction flare nut (Large nut) on the other side of suction refrigerant piping line. • Mount the liquid flare nut (Small nut) on the other side of liquid refrigerant piping line. RecommendFlare tool Refrigerant Piping Flare Nut Flare Tool Liquid Line Suction Line Refrigerant Piping Lines After Connecting Flare Nuts From Both Sides Liquid Piping Line Suction Piping Line
31 CONNECTING REFRIGERANT PIPING (Cont.) 15-10 STEPS FOR CONNECTING REFRIGERANT PIPING LINES TO INDOOR UNIT Connecting suction and liquid piping lines respectively with suction and liquid half unions of indoor unit. A. Lubricate suction and liquid piping line end and the threads of the suction and liquid half unions of indoor unit with anti – freeze oil. This is effective for reducing gas leaks. B. For proper connection, align the centers of suction union pipe and flare pipe straight with each other, then finger tighten several turns the flare nut tightly at first to obtain a smooth match. C. Then hold the union side with a double-ended wrench and tighten the flare nut by applying the tightening torque indicated in the following table (1). Be careful not to damage the flare nut threads. NOTE: One. Insufficient tightening torque will cause Freon leaks. Two. Over tightening the fitting will damage the tube flaring and cause Freon leaks. 15-11 STEPS FOR CONNECTING REFRIGERANT PIPING LINES TO OUTDOOR UNIT • Connecting the other ends of suction and liquid piping lines respectively with suction and liquid flare couplings of the outdoor unit. • Repeat steps (A), (B), (C) when connecting refrigerant piping lines to the couplings of the outdoor unit. (1) Fingers tighten several turns the flare nuts of piping at the outdoor unit valves. Table (1)Half Union Flare Spanner or Torque Wrench Indoor Side Tightening Torque Kg - Cm Flare Nut N.M Kg - cm 3/8” 31-35 310-350 5/8” 50-55 500-550 Piping Lines (2) Tighten the flare nuts with adjustable wrench or torque wrench. Pot only from oil refrigerating her and her Flare nut
32 CONNECTING REFRIGERANT PIPING LINES (Cont.) 15-12 AIR AND MOISTURE PURGE In some countries the law does not permit purging by blowing refrigerant through the lines. If this is the case, please refer to page (31) using the vacuum pump. (A) AIR PURGE USING REFRIGERANT IN THE UNIT OUTDOOR UNIT Air and moisture in the refrigerant system have undesirable effects. They must be purged completely. The outdoor unit includes an extra 50 grams of refrigerant for air purge. • Air purging procedure (1) (2) Remove the valve caps of suction & liquid valve. Loosen the valve stem of liquid valve by 90 degrees (1/4 turn) for 5 seconds with a hex key wrench Push the valve core of the suction valve. Stop pushing the valve core as soon as the refrigerant hissing stops. Open the liquid valve for about 3 seconds, then close quickly to check for gas leaks. After checking for gas leaks, open the liquid and suction valve all the way. Reinstall the caps and of the liquid valve, suction valve and service port nut. (5) (4)(3) COMPLETE (1) Remove service port nut of suction valve. OPEN OPEN & CLOSE CLOSE PUSHOPEN OPEN (1) Suction flare valve. (2) Suction service valve. (3) Suction port to open & close. (4) Cap for suction service valve. (5) Cap for suction port. (6) Liquid flare valve. (7) Liquid service valve. (8) Liquid port to open & close. (9) Cap for liquid service valve. (10) Cap for liquid port. 7 & 9 4 5 23 1 8 6 10
33 CONNECTING REFRIGERANT PIPING LINES (Cont.) AIR AND MOISTURE PURGE (Cont.) (B) AIR PURGE USING THE VACUUM PUMP 1. Connect the gauge manifold and the vacuum pump. 2. Open the low-pressure valve and close the high- pressure valve of gauge manifold completely. 3. Operate the vacuum pump during at least 20 minutes until the pressure reaches – 101Kpa (-760mm Hg). 4. Close the low-pressure valve of the gauge manifold and stop the vacuum pump operation. (If the indicator of gauge manifold is returned within 1-2 minute after stopping the vacuum pump, check the piping connection leakage). 5. Close both the liquid and suction valve caps completely. 6. Remove the gauge manifold and the vacuum pump. (During the disconnection, please be cautious not to loose any refrigerant and oil). 7. Reinstall the valve caps and service port nuts. (C) NOTES: Tighten the valve caps and the service port nut to the specified torque as shown in the table: CONNECTION DIAGRAM OF VACUUM PUMP PART TIGHTENING TORQUE (Kgf – Cm) SERVICE PORT NUT 150 → 200 VALVE CAP 170 → 220 Valve Stem Valve Cap Valve Cap Hex key WrenchLow pressure valve High pressure valve Gauge manifold Vacuum Pump Valve Core Service Port NutIndoor Unit Suction Line Liquid Line Vacuum Pump Outdoor Unit Split System 53QG Series
34 Unit on Cooling Wait about 3 minutes 3 3 1 2 CONNECTING REFRIGERANT PIPING LINES (Cont.) 15-13 REFRIGERANT LEAK CHECK After connecting the refrigerant piping lines, with both outdoor and indoor units check the joints for leakage with electronic leak detector or soapy water. 15-14 INSULATING REFRIGERANT PIPING LINES To conserve energy and prevent wet floors due to condensation, the suction and liquid piping lines must be well insulated with a proper insulation material. The thickness of the insulation should be a minimum of 9 mm. The insulation you select must have good insulation characteristic, be easy to use, resist age and not easily absorb moisture. Finally wrap the flare couplings and pipes with insulation and tighten this with tape without exerting too much pressure on the insulation. CAUTION: • After a pipe has been insulated, never try to bend it into a narrow curve, as this way will cause the pipe to break or crack. • Repair and cover any possible cracks in the insulation • Avoid dripping due to insufficient insulation of piping. 15-15 PUMP DOWN Pump down means collecting all the refrigerant in the system back into the outdoor unit. Pump down must be actuated before disconnection of pipes, to avoid loss of refrigerant gas. Pump down is used when the unit is moved to another installation location or when the system is repaired. PUMP DOWN PROCEDURE : 1. Close the liquid valve with the Allen wrench. 2. Turn the system ON in cooling mode with fan operating at high speed. Then the refrigerant will be collected into the outdoor unit. (Compressor will immediately start, provided 3 minutes have elapsed since the last stop). 3- After 3 minutes of operation, close the suction valve with the Allen wrench. Turn the system off and switch mains supply OFF. Disconnect refrigerant piping lines. After disconnection, protect valves and piping ends from dust. Pipe Insulation Pipe Fastening tape
35 16. CONNECTING CONDENSATE DRAIN LINE 16-1 INSTRUCTIONS FOR CONNECTING CONDENSATE DRAIN LINE The condensate drain line (not supplied) for indoor unit must be made of PVC piping with an inside diameter of 5/8” (16 mm) and have suitable length for the chosen installation site. Instructions for connecting drain hose Possible outlet locations of condensate drain line from the indoor unit a. The drain hose must be gradually inclined downwards to the outside to ensure flow of condensate water to outside. b. The condensate drain line must not be connected to the sewerage system. c. The drain hose must not be looped upwards to avoid over-flowing of condensate water. The condensate drain line is connected to the loose end of the drain hose coming out of the indoor unit in one of the following four outlet locations: d. The drain hose must have no kinks or bends hampering smooth drainage of water due to air stagnation. Avoid horizontal kinks or bends Avoid vertical kinks or bends Avoid horizontal drain line with Avoid any rise in drain line Less than 2 % slope e. Drainage Test Check the drainage of the unit by pouring some water into the unit drain pan and ensure it drains out through the drain hose and there is no leakage from other parts. Sr. Outlet Location Notes 1 Unit Right Remove right side knock-out 2 Unit Bottom Remove bottom knock-out 3 Unit Back Do not remove side or bottom knock-out 4 Unit Left Remove left side knock-out 4 3 2 1
36 17. CONNECTING ELECTRICAL WIRING 17-1 ELECTRICAL WIRING BETWEEN ELECTRICAL POWER SUPPLY AND CIRCUIT BREAKER OF AIR CONDITIONER All electrical connections between electrical power supply and circuit breaker of air conditioner are the responsibility of the customer and must be done by a qualified electrical technician according to national electrical wiring regulations to avoid fire due to short-circuiting. (A) Operating Voltage The operating voltage of electrical power supply should be within the limits of voltage mentioned on unit nameplate data. (B) Electrical kWh Counter KWH The capacity of electrical kWh counter should be lager than the operating currents required for air conditioner(s) and any other electrical domestic appliances in use simultaneously from the same supply. (C) Electrical Distribution Box The installation of electrical distribution box after the electrical KWH counter is necessary to properly distribute the electrical loads. The electrical distribution box should be equipped with circuit breakers according to the electrical loads. For each installed air conditioner, a separate circuit breaker with its own overload should be installed on the electrical distribution box. (D) Operation On / Off Circuit Breaker The installation of two pole automatic circuit breaker is necessary to operate the air conditioner.
37 CONNECTING ELECTRICAL WIRING (Cont.) 17-2 ELECTRICAL WIRING BETWEEN INDOOR UNIT, OUTDOOR UNIT AND CIRCUIT BREAKER OF AIR CONDITIONER All electrical connections between the outdoor unit, indoor unit and circuit breaker are the responsibility of the qualified installer and must be done according to national electrical wiring regulations to avoid fire due to short circuiting. - Both of the outdoor and indoor units leave the factory with complete internal electrical wiring. Do not change any internal electrical wiring of both units. - A qualified electrical technician should carry out the electrical connections. - It is very important before making the electrical connections between the indoor, outdoor units, and the power supply, to pay attention to the following safety instructions: (A) Operating Voltage The operating voltage of electrical power supply should be within the limits of voltage mentioned on unit nameplate data. Shown on the indoor and outdoor units of the air conditioner. (B) Field Electrical Connection Cables * Do not use electrical connection cords except the approved one for use with air conditioners. * Each cable should be a complete unit, without extensions. (C) Electrical Connections a. Check that the electrical connections between the terminal blocks of indoor and outdoor units are in accordance with the wiring diagrams and caution field electrical wiring contained in the manual. Miswiring may cause malfunction of the system and an electric shock. b. Do not connect wires when power is ON. c. Make ground connection prior to any other electrical connections in accordance with the electrical local codes. d. Make electrical connections between outdoor and indoor units prior to proceeding to mains supply connection. e. Before proceeding with the unit connection to the mains supply locates live L and neutral N, then make connections as shown in the wiring diagram. Be sure that the live and neutral wire connected respectively to the Live (L) and the Neutral (N) terminals of terminal block of outdoor units. f. Ensure that mains supply connection is made through a switch that disconnects all poles, with contact gap of at least 3 mm. g. Avoid slack connections of the electrical cords when connected to the terminal blocks of indoor and outdoor units. and also to circuit breaker These slack connections lead to voltage drop and unit malfunctions. Every wire must be connected firmly. WARNING !