Carrier 42qg24-h Manual
Have a look at the manual Carrier 42qg24-h Manual online for free. It’s possible to download the document as PDF or print. UserManuals.tech offer 29 Carrier manuals and user’s guides for free. Share the user manual or guide on Facebook, Twitter or Google+.
8 6. SPLIT SYSTEM DESCRIPTION 1: Remote control signal receiver. 2: Operating status leds. 6: Supply air outlet 3: Supply air flap 7: Characteristics nameplate. 4: Air return. 8: Inter connecting tubing. 5: Air filter. 9: Condensate drain line. Indoor Unit 38 7 2 1 9 4 5 Outdoor Unit 6
9 7. INSTALLATION ACCESSORIES 7.1 STANDARD INSTALLATION ACCESSORIES Supplied from the factory DESCREPTION CONFIGURATION QTY USAGE Battery 1.5 volt size AAA alkaline type 2 To operate the wireless remote control Wireless remote control and Plastic holder for remote 1 To operate the air conditioner To mount remote control on the wall Owner manual 1 To illustrate control functions of operation Installation Manual 1 To illustrate installation instructions. Insulation Tube. 1 To insulate half unions and Flare nuts after connecting refrigerant piping lines to the indoor and outdoor units. Wall hang bracket 1 For indoor unit installation on the wall. Self tapping screw 5 x L50 5 For wall hang bracket installation Tapping Screws 2 For adjustment the gap between indoor unit and wall. Drain Elbow 1 Outdoor unit Condensate drain 7.2 OPTIONAL ACCESSORIES Supplied from the factory as per the requirement DESCREPTION CONFIGURATION QTY USAGE Wall support for outdoor unit 1 To mount outdoor unit on the wall Floor support for outdoor unit 1 To mount outdoor unit on the ground or floor Insulated refrigerant piping lines with flare couplings of lengths 4-6-8-10-12 meter 1 To connect Freon between outdoor and indoor units and refrigerant piping lines Optional air filters (Carbon air filter + Photo-catalytic air filter) Set of 2 To eliminate odor and cigarette smoke in the room air respectively. PTC starting device 1 To start the compressor in outdoor unit at low voltage down 187V
10 INSTALLATION ACCESSORIES (Cont.) 7.4 OTHER INSTALLATION ACCESSORIES Not supplied from the factory but must be used in the field to complete installation. DESCREPTION USAGE Electrical Connection Cords To electrically connect the indoor unit, the outdoor unit and circuit breaker ـ Wall Sleeve ـ Wall Cap ـ Sealer putty To fill the gap between the wall hole and the lump of refrigerant piping lines, electrical connection cables and condensate drain line. ـ Finishing tape PVC film To tie together the refrigerant piping lines, electrical connection cables and condensate drain line. ـ Vinyl tape To stick pipe insulation. ـ Drain hose ID 16-17mm To remove condensate water, from the indoor unit to the outside. ـ Refrigerant piping lines To connect Freon R22 between outdoor and indoor units ـ Pipe insulation To insulate suction and liquid refrigerant piping lines - Refrigerant R22 To adjust refrigerant charge for long refrigerant piping lines (more than 3 meter) - Refrigerant Oil To be added for long refrigerant piping lines (more than 10 meters) - Clamps or saddles To secure the lump of refrigerant piping lines, electrical cables and condensate drain line
11 8. INSTALLATION CHART 1) Installing outdoor unit 5) Connecting refrigerant piping lines 9) Air purging with a vacuum pump 2) Drilling hole thru the wall 6) Connecting condensate drain line 10) Refrigerant leak test 3) Installing indoor unit 7) Connecting electrical wiring 11) Opening service valves 4) Processing pipes 8) Finishing outer pipe covering 12) Finishing installation 13) Test Running 14) Description of operation Outdoor unit
12 9. SELECTING INSTALLATION LOCATION FOR INDOOR UNIT 9.1 CONSIDERATIONS FOR SELECTING INSTALLATION LOCATION Avoid excessive height difference between indoor and outdoor units Avoid excessive length of refrigerant piping lines between indoor and outdoor units Location of Indoor Unit Relative to Space to be Air-Conditioned. The installation location should permit the unit to deliver air to all of the space to be uniformly air-conditioned. Avoid direct sunlight that may affect performance of the unit Avoid heat sources such as steam or flame that may affect performance of the unit. Avoid obstructions such as Curtains, Furniture and Cloths…etc. These obstructions can affect motion of supply air and/or return air, which in turn affects unit efficiency and airflow. 175CM OR MORE
13 SELECTING INSTALLATION LOCATION FOR INDOOR UNIT (Cont.) CONSIDERATIONS FOR SELECTING INSTALLATION LOCATION (Cont.) Avoid an installation location, which has an environment with oil vapors. Avoid an installation location which has an environment affected by high frequency waves generated as from radio equipment’s welders and medical equipment’s. Avoid installation location on humid walls or positions with water hazard, e.g. laundry premises. Check that the wall surface is flat enough to allow easy and safe installation. The wall structure should be strong enough to carry the unit weight and avoid deformation, rupture or vibration during operation. Choose an installation location that allows easy installation. Choose an installation location that allows for free air circulation service and maintenance minimum clearances. Choose an installation location where condensate water from indoor unit can easily be piped to an appropriate drain Location of Wall Hole The wall hole (required to pass refrigerant piping lines, electrical cables and drain hose) should be according to the selected installation location.
14 SELECTING INSTALLATION LOCATION FOR INDOOR UNIT (Cont.) 9.2 POSSIBLE OUTLET LOCATIONS OF REFRIGERANT PIPING LINES FROM INDOOR UNIT Possible outlet locations of refrigerant piping lines from indoor unit. The refrigerant piping lines can be connected in one of the following Four outlet locations as indicated by (1), (2), (3) and (4) When the piping is connected to the direction of (1) or (2) or (4), Detach the knock – out either at the side or at the bottom of the unit. See fig. (2) NOTE: The recommended outlet location to pass refrigerant piping lines, electrical cables and condensate drain line either from behind unit right or from behind unit left to keep appearance of installation and to facilitate installation. The unit hides the refrigerant lines; electrical cables and condensate drain line. * Note: In case of impossibility of mounting the indoor unit directly on the wall, use floor support for indoor unit SROUTLET LOCATION NOTES 1 UNIT RIGHT Remove right side knock-out 2 UNIT BOTTOM Remove bottom knock-out 3 UNIT BACK Do not remove side or bottom knock-out 4 UNIT LEFT Remove left side knock-out Fig. (1) 4 3 2 1 4 2 1 Fig. (2)
15 10. SELECTING INSTALLATION LOCATION FOR OUTDOOR UNIT 10.1 INSTALLATION LOCATIONS The condensing unit can be installed in any outside location, on a wall, roof or on a ground level. 10.2 CONSIDERATIONS FOR SELECTING INSTALLATION LOCATIONS Avoid excessive distance between outdoor and indoor units Avoid excessive height between outdoor and indoor units Avoid any obstruction of the unit air outlet and intake or any obstacle that is too close Avoid multiple unit installation with units facing each other. Avoid unnecessary turns and bends in the refrigerant piping lines.
16 SELECTING INSTALLATION LOCATION FOR OUTDOOR UNIT (Cont.) CONSIDERATIONS FOR SELECTING INSTALLATION LOCATION (Cont.) Avoid dripping into passageways. Avoid soiling of pipe ends Avoid allowing piping to get wet before connection Avoid disconnecting the refrigerant connections after installation, this will cause refrigerant leaks Avoid connecting the condensate drain line to the outdoor unit. a. Weight of Outdoor Unit The installation location of outdoor unit should be able to support operating weight of outdoor unit, and not cause vibration. b. Effect of Direct Sunlight The installation location of outdoor unit is preferable to be far away from the direct sunlight. c. Effect of heat sources, steam or flammable gas The installation location of outdoor unit should be far away from heat sources, steam or flammable gas. d. Cleanness of location The installation location of outdoor unit should be free of dust or any material, which can cause clogging of condenser coil. When installing unit on the ground, select a location not subjected to flooding. When the installation is made on the rooftop or other places subject to strong wind : When the outdoor unit is to be installed on the rooftop or at the places where there are no other buildings around. it is required to avoid the strong wind from blowing directly into the air outlet of the outdoor unit so as to prevent the negative impacts on cooling or heating performances due to insufficient airflow of the outdoor unit heat exchanger and to prevent from faulty performances. When there are walls in the vicinity, the air outlet should face the wall and keep a space of 500mm from the wall. When the air outlet is affected by the strong wind, the installation position should be changed so as to make the air outlet at a straight angle from the wind direction.
17 11. INSTALLATION LOCATION CHECK LIST (A) INDOOR UNIT - The installation location is close to the outdoor unit - The wall hole (required to pass refrigerant piping, electrical cables and drain line) is on the unit right back - The installation location permit the unit to deliver air to all of the space to be air-conditioned - The installation location is far away from any sunlight - The installation location is far away from any heat sources - The installation location avoid obstructions, which affect motion of supply and/or return air to the unit - The installation location permit free service space around the unit right, left and top (B) OUTDOOR UNIT - The electrical power supply is close to the outdoor unit - The installation location is close to the indoor unit - The installation location is able to support operating weight of outdoor unit - The installation location is far away from any sunlight - The installation location is free of dust or any material, which can cause clogging of outdoor coil - The installation location allow sufficient space for air circulation around the unit - The installation location allow sufficient space for service and maintenance around the unit (C) REFRIGERANT PIPING LINES BETWEEN INDOOR AND OUTDOOR UNITS - The excessive length of refrigerant piping lines is avoided - The excessive height between indoor and outdoor units is avoided