Carrier 42qg24-h Manual
Have a look at the manual Carrier 42qg24-h Manual online for free. It’s possible to download the document as PDF or print. UserManuals.tech offer 29 Carrier manuals and user’s guides for free. Share the user manual or guide on Facebook, Twitter or Google+.
18 12. INSTALLATION OF INDOOR UNITS 12.1 PREPARATION STEPS OF INDOOR UNIT BEFORE INSTALLATION a. Put packed unit as shown. Remove plastic strap (item 1) from cardboard. d. Lift insert grille to the top of the unit with both hands and it will be automatically separated from unit. e. Disassemble terminal block cover by removing two screws from grille frame. b. Slide unit from carton (item 1) Lift unit with Styrofoam Parts from carton box Remove Styrofoam parts • By pulling right and left Styrofoam you will find small carton box containing electrical connection cords and remote control with its accessories. • Turn the unit up, you will find the mounting bracket. f. Pull the triangle marks located at bottom of the grille frame. g. Lift grille frame to top of the unit. c. Remove the screw-fixing wall mounting bracket with the unit. Remove the wall-mounting bracket from the unit by pushing up the indicated marks ( ▲) at the bottom of the body. h. Fix the optional plastic holder of the remote control on the wall by using optional anchor screw and screw 1 3 2 Removal of wall hang bracket REMOVE SCREW
19 INSTALLATION OF INDOOR UNITS (Cont.) 12-2 INSTALLATION STEPS OF INDOOR UNIT STEP (1): Selecting Wall Hole Location Back Piping In case of passing refrigerant piping lines, electrical cables and condensate drain line behind the unit, drill a hole of 8 cm behind the unit in one of the following locations as per sequence: Location (A): behind unit right. Location (B): behind unit Left. Side or bottom piping In case of passing refrigerant piping lines, electrical cables and condensate drain line from unit right side or from unit bottom, detach the knockout in either the side or bottom of the unit. Step (2): Making Wall Hole Precautions: Before making a hole, check carefully that : - The wall is flat and perpendicular. If the wall is not flat and perpendicular, the indoor unit can be unstable and condensate drain can spill. - No studs or pipes are directly run behind the spot to be cut. - No electrical wiring or conduits are located. • Drill a hole of 80 mm to pass the refrigerant lines, drain hose and electrical cables. The wall hole can be made as required in either location (A) or (B). When making wall hole, make sure to drill outwards at a downward angle, so that the height difference between the entrance and exit of the hole is at least 5-10 mm. Step (3): Cutting Sleeve For Wall Hole • Measure the thickness of the wall from the inside edge to the outside edge and cut PVC pipe at a slight angle 6mm shorter than the thickness of the wall. Step (4): Mounting Sleeve Into Wall Hole • After making hole, a sleeve must be mounted into wall hole and its width to be equal to wall thickness to pass refrigerant lines, drain hose and electrical cables through it. Step (5) : Installing the wall hang bracket • Allow the clearance space around the unit, which permits adequate air circulation, easy access to the unit for easy service and maintenance. • Fix wall hang bracket on the wall so that it is leveled vertically and horizontally by using the five self-tapping screws supplied with the unit in the plastic page 2 (Two) screws to fix bracket top. 1 (One) screws to fix bracket mid, 2 (Two) screws to fix bracket bottom, Use a plumb line if necessary to adjust leveling of the wall hang. Wall Hole Locations 5-10 mm Wall Wall Indoor side Outdoor side Cut Wall Sleeve Indoor side Outdoor Side Wall Sleeve Space Around Unit Indoor Unit
20 INSTALLATION OF INDOOR UNITS (Cont.) INSTALLATION STEPS OF INDOOR UNIT (Cont.) NOTES: a. Fasten the wall hang bracket to the wall with all the 5 (Five) screws supplied with unit. This correct fixation will prevent motion of bracket after fixation, which can cause noisy unit operation. b. The wall hang bracket must be leveled in both horizontal and vertical directions after fixation without tilting to the right or lift to avoid water dropping from the unit onto the floor. See Fig. c. Install the wall hang bracket so that three is no gap between it and the wall to avoid vibrations and sound during unit operation. d. Check that the wall hang bracket does not move. This can cause noise during operation. Step (6): Electrical wiring of indoor unit See chapter (18) : Connecting Electrical Wiring. Step (7): Forming refrigerant piping drain hose and electrical cables of indoor unit. • As per the selected location of wall hole, form and tie together with vinyl tape the refrigerant piping, electrical cables and drain hose. The drain hose should be at the bottom. • For left piping fit the refrigerant piping, electrical cords and drain hose into the recess at back of indoor unit. Notes: a. Do not crush or kink the indoor unit piping. Avoid tight bending with a bending radius less than 100 mm. b. Do not bend the same part of the pipe too often. c. Do not remove the flare nuts from the indoor unit piping until the piping is ready for connection with refrigerant piping lines. X An Uneven Installation Indoor unit piping Drain hose Bind with vinyl tape Left Piping Indoor unit piping Connection cables
21 INSTALLATION OF INDOOR UNITS (Cont.) INSTALLATION STEPS OF INDOOR UNIT (Cont.) Step (8): Passing refrigerant piping, electrical cords and drain hose of indoor unit through wall sleeve. • Passing refrigerant piping lines through the wall sleeve is done before hooking the indoor unit body onto the top of the wall hang bracket. • For left piping, hang the unit onto the top of the wall hang bracket and incline the unit using a tool such as a screw driver set between the middle area of body and bottom right of the wall hang bracket. Connecting the piping can be done more easily if the unit is inclined. Warning: Do not supply power to the indoor unit until all refrigerant piping and electrical wiring to the outdoor unit are completed. Step (9): Installing the Indoor Unit Body to the Wall Mounting Bracket • Snap the marking places of the body (A, B) onto the hole of the bracket. NOTES: • In case of removing the unit from the wall hang bracket after installing it onto the wall, remove it by pushing up the indicated marks ( ▼) at the bottom of the body. • After installation of unit, if there is a significant gap between the unit and wall, securing 2 screws to the body and wall- mounting bracket can adjust it. Refer to the screw hole location (C, D) in the Figure. Screw holes can be only seen after removing the grille frame. A B C D 340 270 270 195 Dimensions in mm AB CD Wall Hole Wall mounting bracket Hook
22 13. REMOTE CONTROL INSTALLATION 13.1 HOW TO INSERT BATTERIES: (a) Remove the cover of battery compartment at the back of the remote control by pressing the tab toward inside, in the direction of the arrow. (b) Mount the two-battery size AAA 1.5 Volt supplied with the remote control. Then close the cover of the battery component. Note: During mounting of batteries check battery symbols (+, -) indicated in batteries compartment. NOTES: 1. The remote control uses two alkaline batteries (1.5V, LRO03x2). 2. Do not use used batteries or batteries of different types, as this may cause the air conditioner to malfunction. 3. Batteries should only be changed after turning OFF the air conditioner. 4. The average battery life during normal use is approximately one year. 6. When the symbol appears in the display of the remote control, this indicates that the batteries are exhausted and required to be replaced 13-2 INSTRUCTION: WHEN DIRECTING THE TRANSMITTER OF WIRELESS REMOTE CONTROL TO THE RECEIVER OF INDOOR UNIT FROM A CERTAIN LOCATION, CHECK THE FOLLOWING POINTS: 1- Avoid direct sunlight on the receiver of indoor unit, which may interfere with good signal reception 2- No obstructions such as curtains or plants should be between the remote control and the receiver of indoor unit. 3- The maximum operating range for the remote control is approximately 5 meters. 4- The remote control must be directed toward the receiver of indoor unit when pressing the buttons of the desired functions. An acoustical acknowledgement sound (beep) will indicate that signal has been received.
23 14. OUTDOOR UNIT INSTALLATION 14.1 PREPARATION STEPS BEFORE INSTALLATION a. Put packed unit as shown. b. Lift unit from cardboard. c. Remove service door (item 2) by removing one screw (item 1). Detach the cable clamp by removing one screw. 14.2 INSTALLATION STEPS WALL INSTALLATION STEPS FLOOR INSTALLATION STEPS Wall Support Dimensions (mm) Floor Support Dimensions. (mm) fix wall support into the wall Put unit on the wall support. If the outdoor unit installed other than on the ground, connect it to a 15-16 mm inside diameter hose. This is needed because drain water flows out of the outdoor unit during heating operation. (Only for heat pump unit) Put outdoor unit on the floor support 1 215 Floor Support 888 443 80 32 42 557 162 412 215 443 886 415 132 132 2
24 15. CONNECTING REFRIGERANT PIPING LINES 15-1 INSTRUCTIONS FOR CONNECTIING REFRIGERANT PIPING LINES Avoid excessive height difference between indoor and outdoor units. Avoid excessive length of refrigerant piping lines between indoor and outdoor units - All bends must be considered when connecting indoor unit with outdoor unit by required length of refrigerant piping lines. - Do not remove the protective caps from the couplings until the refrigerant piping lines are ready for connection with both indoor and outdoor units. This is to keep piping clean. - The installer must carefully unroll the tubing and run it between the indoor and outdoor units. ● Do not bend the pipe more than three times at one place. ● When extending the rolled pipe, straighten the pipe by unwinding it. When forming the pipe. Be careful not to crush it. Flattening or kinking of refrigerant piping must be avoided When making a bend, the installer cuts insulation and slides it away from the bend area. Using a tube bender makes the bend and then the insulation is replaced gluing it together. Insulation Copper Piping Not Recommended Recommended
25 CONNECTING REFRIGERANT PIPING LINES (Cont.) INSTRUCTIONS FOR CONNECTIING REFRIGERANT PIPING LINES (Cont.) The minimum radius of bending must not be less than 100 mm to avoid damage of tubing. Once the tubing is bent, the installer must not unbend at the same point as this causes work hardening of copper tubing and makes it more difficult to reshape Avoid disconnecting refrigerant connections after they have been tightened to avoid refrigerant leaks. When there is excessive tubing, it must be coiled horizontally so that the flow of refrigerant is from the top to bottom of the coil and towards the outdoor unit. The excessive tubing must not be coiled vertically since the vertical coil affects the oil return to the compressor. For bends having a radius smaller than 300 mm, the use of a tuber bender with a minimum wheel diameter of 120 mm is a must. The tube bender wheel grooves should have the same diameters as the refrigerant pipes. Avoid excessive number of bends in refrigerant piping lines during connections with both the indoor and outdoor units. This is to avoid reduction of cooling efficiency. Bends with tube diameter bigger than ½” or a bending radius than 300 mm should be made with a dime. Having this radius. Radius of Bending Excessive tubing must be coiled horizontally
26 L CONNECTING REFRIGERANT PIPING LINES (Cont.) 15.2 USE OF REFRIGERANT PIPING LINES The following data refers to the use of refrigerant piping lines of diameters equivalent to that use in units where: L = Maximum length of refrigerant piping lines between outdoor and indoor unit. H = Maximum vertical distance between outdoor and indoor units. (A) OUTDOOR UNIT BELOW INDOOR UNIT: a. Suction line should rise above height of Indoor unit to shape a liquid trap in an inverted loop before descending to outdoor unit to prevent liquid refrigerant from draining into compressor during shutdown. b. Slop tubing towards the outdoor unit with a fall of at least (6mm) to (305mm). (B) OUTDOOR UNIT ABOVE INDOOR UNIT: • If height is less than or equal 4 meters, one oil trap must be at the suction line at the base of suction riser near the Indoor unit to facilitate oil return to the compressor to ensure efficiency of compressor mechanical parts. • If height is more than 4 meters, more than one oil trap must exist at the suction line, the first one will be at the suction line near to the indoor unit and the following one will be 4 meters from the first one and so on. (C) OUTDOOR UNIT ON THE SAME LEVEL AS INDOOR UNIT: An oil trap shall be at the suction line at the base of suction riser near the Indoor unit to facilitate oil return to the compressor to ensure efficiency of compressor mechanical parts. Meters System Model L H 53QG18 20 10 53QG24 20 10 Liquid Trap Suction LineOutdoor Unit Meters System Model L H 53QG18 20 10 53QG24 20 10 Meters System Model L 53QG18 20 53QG24 20 Outdoor Unit Indoor UnitSlop Oil TrapLiquid Suction Indoor Unit H Max. 4m Liquid Line Slop H Outdoor Unit Indoor Unit Oil Trap Liquid Suction
27 CONNECTING REFRIGERANT PIPING LINES (Cont.) 15-3 LENGTHS AND DIAMETERS OF REFRIGERANT PIPING LINES FOR ALL MODELS S L 5/8” 3/8” S = Suction line diameter. L = Liquid line diameter. 15.4 REFRIGERANT CHARGE. • For refrigerant piping lines of length more than 3 meters, add 25 grams of refrigerant per extra meter from 3 meters refrigerant piping lines: Example 1 = For 8 meter lines, refrigerant added = (8-3) x 25 = 125 grams. Example 2 = For 12 meter lines, refrigerant added = (12-3) x 25 = 225 grams. Note: (1) The outdoor unit is factory supplied with refrigerant charge for use with refrigerant piping lines of length 3 meters and with added 100 grams for air and moisture purge from the system. (2) Charge the refrigerant accurately. (3) Refrigerant overcharge may cause a serious trouble of compressor.