11 Page WARNING FOR INSTALLATIONS FOR YOUR SAFETY, READ BEFORE INSTALLATION: Do not install the heater where water, debris or flammable vapors may get into the flue terminal. This may cause damage to the heater and void the warranty. Do not have the vent terminal pointing toward any opening into a building. Do not locate your heater in a pit or location where gas and water can accumulate. Do not install this water heater under an overhang less than 3 ft. (914 mm) from its top or eaves. The...
Page 12
12 Page HIGH-ALTITUDE INSTALLATIONS Check the elevation where your water heater is installed. Set DIPswitches shown in the table below depending on the altitude. Bank of DIPswitches 110U (T-KJr2U) and 310U (T-K4U) models Computer board WARNING DO NOT adjust any DIPswitches on the upper bank for the 510U (T-D2U) model. NOTE: The dark squares indicate the direction the DIPswitches should be set to. Lower bank of DIPswitches 510U (T-D2U) model Computer board Installation...
Page 13
13 Page VENTING INSTRUCTIONS For indoor models -General- The water heater must be vented in accordance with the section “Venting of Equipment" of the latest edition of the National Fuel Gas Code: ANSI Z223.1/NFPA 54 in the United States and/or Section 7 of the CAN/CSA B149.1 Natural Gas Installation Code in Canada, as well as applicable local building codes. The manufacturer recommends the NovaVent line. However, the following are also UL listed manufacturers: ProTech Systems Inc....
Page 14
14 Page -Vent length and No. of Elbows- This is a Category III appliance and must be vented accordingly. The vent system must be sealed airtight. All seams and joints without gaskets must be sealed with high heat resistant silicone sealant or UL listed aluminum adhesive tape having a minimum temperature rating of 350 °F (177 °C). For best results, a vent system should be as short and straight as possible. • This water heater is a Category III appliance and must be vented accordingly with any 4 in....
Page 15
15 Page Venting Illustrations- For the 110U Indoor (T-KJr2U-IN), 310U Indoor (T-K4U-IN) and 510U Indoor (T-D2U-IN) models For details of the optional items, refer to the Installation manual for each Optional item. Horizontal Installation with Direct-vent concentric termination Wall Direct-vent concentric termination Installation of Direct-vent conversion kit with water heater Water heater Intake port of Direct-vent conversion kit(For details see p. 10.) Plate of Direct-vent conversion kit Horizontal...
Page 16
16 Page -Vent termination clearances- CanadaU.S.A Direct-vent and other than Direct-vent Direct- vent Other than Direct-vent AClearance above grade, veranda, porch, deck, or balcony1 foot1 foot1 foot B Clearance to window or door that may be opened3 feet1 foot 4 feet from below or side opening. 1 foot from above opening. CClearance to permanently closed window*** D Vertical clearance to ventilated soffit located above the vent terminator within a horizontal distance of 2 feet (61cm) from the...
Page 17
17 Page -For sidewall terminations- -For rooftop terminations- For multiple sidewall exhaust terminations (e.g. multi- unit systems), an exhaust termination must be at least 1 ft. (305mm) away from another exhaust termination. An exhaust termination must also be at least 2 ft. (610 mm) away from an inside corner. (If the adjacent wall is less than 2 ft. (610 mm) of length, the minimum required distance away from the inside corner will be equal to the length of that adjacent wall.) For...
Page 18
18 Page GAS SUPPLY AND GAS PIPE SIZING -General- • The minimum and maximum inlet gas pressures are: • Inlet gas pressures that fall outside the range of values listed above may adversely affect the performance of the water heater. These pressures are measured when the water heater is in full operation. • Inlet gas pressure must not exceed the above maximum values; gas pressure above the specified range will cause dangerous operating conditions and damage to the unit. • Until testing of the main gas...
Page 19
19 Page -Natural Gas Supply Piping- Maximum delivery capacity of cubic feet of gas per hour of IPS pipe carrying Natural Gas with 0.60 specific gravity based on pressure drop of 0.5" W.C. Based on energy content of 1,000 BTU/Cubic ft.: The water heater requires 140 Cubic ft./hr for the 110U (T-KJr2U) model, 190 Cubic ft./hr for the 310U (T-K4U) model, and 199 Cubic ft./hr for the 510U (T-D2U) model. Based on Energy Content of 1,000 BTU/Cubic ft: Divide each appliance's BTU/h requirement by...
Page 20
20 Page -Measuring inlet gas pressure- The water heater cannot perform properly without sufficient inlet gas pressure. Below are instructions on how to check the inlet gas pressure. THIS IS ONLY TO BE DONE BY A LICENSED PROFESSIONAL. WATER CONNECTIONS All pipes, pipe fittings, valves and other components, including soldering materials, must be suitable for potable water systems. 1. A manual shutoff valve must be installed on the cold water inlet to the water heater between the main water supply...