Home > American Water Heater > Gas Heater > American Water Heater NonCondensing UltraLow NOx Outdoor Natural Gas GT110UNE user manual

American Water Heater NonCondensing UltraLow NOx Outdoor Natural Gas GT110UNE user manual

    Download as PDF Print this page Share this page

    Have a look at the manual American Water Heater NonCondensing UltraLow NOx Outdoor Natural Gas GT110UNE user manual online for free. It’s possible to download the document as PDF or print. UserManuals.tech offer 32 American Water Heater manuals and user’s guides for free. Share the user manual or guide on Facebook, Twitter or Google+.

    							11  Page
    WARNING FOR INSTALLATIONS
    FOR YOUR SAFETY, READ BEFORE INSTALLATION:
    Do not install the heater where water, debris or 
    flammable vapors may get into the flue terminal. 
    This may cause damage to the heater and void the 
    warranty.
    Do not have the vent terminal pointing toward 
    any opening into a building.  Do not locate your 
    heater in a pit or location where gas and water 
    can accumulate.
    Do not install this water heater under an 
    overhang less than 3 ft. (914 mm) from its top 
    or eaves.  The area under an overhang must be 
    open to three sides (Outdoor models only).
    Do not install the water heater vent terminator 
    within 1 ft. (305 mm) in the USA of any air intake 
    or building opening, and within 3 ft. (914 mm) 
    in Canada of any air intake or building opening 
    (Outdoor models only, refer to p. 16).
    Do not install next to a dryer or any source 
    of airborne debris that can be trapped inside 
    the combustion chamber, unless the system is 
    direct-vented.
     
    ProhibitedProhibited
    1 ft. (305 mm) USA3 ft. (914 mm) Canada1 ft. (305 mm) USA3 ft. (914 mm) Canada
    1 ft. (305 mm) USA3 ft. (914 mm) Canada3 ft.
    (914 mm)
    Installation
    Installation Manual
    Water heater vent terminator must be at least 2 
    ft. (610 mm) away from an inside corner for both 
    outdoor installation and direct-vent installation.
    Inside
    Corner
    2 ft.
    (610 mm)  
    						
    							12  Page
    HIGH-ALTITUDE INSTALLATIONS
    Check the elevation where your water heater is installed.  Set DIPswitches shown in the table below 
    depending on the altitude.
    Bank of DIPswitches
    110U (T-KJr2U) and 310U (T-K4U) models
                        Computer board
    WARNING
    DO NOT adjust any DIPswitches on the upper bank for the 510U (T-D2U) 
    model.
    NOTE: The dark squares indicate the direction the DIPswitches should be set to.
    Lower bank of DIPswitches
       510U (T-D2U) model
           Computer board
    Installation
    Installation Manual
    Outdoor models
    0 to 2,000 ft. 
    (DEFAULT)
    2,000 to
    4,000 ft.
    4,000 to
    6,000 ft.
    110U (T-KJr2U) and 
    310U (T-K4U) modelsNo. 3 : OFF
    No. 4 : OFF
    No. 5 : OFF
    No. 3 : OFF
    No. 4 : OFF
    No. 5 : ON
    No. 3 : ON
    No. 4 : OFF
    No. 5 : ON
    510U (T-D2U) model
    (Lower bank of
      DIPswitches)No. 2 : OFF
    No. 3 : OFF
    No. 4 : OFF
    No. 2 : OFF
    No. 3 : OFF
    No. 4 : ON
    No. 2 : ON
    No. 3 : OFF
    No. 4 : ON
    OFF
    ON123 456 78910
    OFF
    ON1 2345678910
    OFF
    ON1 23 456 78910
    OFF
    ON1 23 456
    OFF
    ON1 23 456
    OFF
    ON1 23 456
    Indoor models
     0 to 2,000 ft.
     (DEFAULT)
    2,000 to 
    3,000 ft.
    3,000 to
    5,000 ft.
    5,000 to
    7,500 ft.
    7,500 to
    10,100 ft.
    110U (T-KJr2U) and 
    310U (T-K4U) modelsNo. 3 : OFF
    No. 4 : OFF
    No. 5 : OFF
    No. 3 : OFF
    No. 4 : ON
    No. 5 : OFF
    No. 3 : OFF
    No. 4 : OFF
    No. 5 : ON
    No. 3 : OFF
    No. 4 : ON
    No. 5 : ON
    No. 3 : ON
    No. 4 : ON
    No. 5 : ON
    510U (T-D2U) model
    (Lower bank of
      DIPswitches)No. 2 : OFF
    No. 3 : OFF
    No. 4 : OFF
    No. 2 : OFF
    No. 3 : ON
    No. 4 : OFF
    No. 2 : OFF
    No. 3 : OFF
    No. 4 : ON
    No. 2 : OFF
    No. 3 : ON
    No. 4 : ON
    No. 2 : ON
    No. 3 : ON
    No. 4 : ON
    OFF
    ON1 23 456 78910
    OFF
    ON1 23 456 78910
    OFF
    ON1 2345678910
    OFF
    ON1 2345678910
    OFF
    ON1 23 456
    OFF
    ON1 23 456
    OFF
    ON1 23 456
    OFF
    ON1 23 456
    Altitude
    DIPswitches
    OFF
    ON1 2345678910
    OFF
    ON1 23 456
    Installation altitude
     The maximum certified
    or allowable installed
    altitude is 10,100 ft. for
    indoor models and 6,000 ft.
    for outdoor models.  
    						
    							13  Page
    VENTING INSTRUCTIONS
    For indoor models
    -General-
    The water heater must be vented in accordance with the section “Venting of Equipment" of the latest 
    edition	of	the	 National	 Fuel	Gas	Code:	 ANSI	Z223.1/NFPA	 54	in	the	 United	 States	and/or	 Section	 7	of	 the	
    CAN/CSA B149.1 Natural Gas Installation Code in Canada, as well as applicable local building codes.
    The manufacturer recommends the NovaVent line.  However, the following are also UL listed 
    manufacturers: ProTech Systems Inc. (FasNSeal), Metal-Fab Inc., and Heat-Fab Inc. (Saf-T Vent).
    General rules for venting water heaters are:
    •	Place the water heater as close as possible to the vent termination.
    •	The vent collar of the water heater must be fastened directly to an unobstructed vent pipe.
    •	Do not weld the vent pipe to the water heater’s vent collar.
    •	Do not cut the vent collar of the unit.
    •	The vent must be easily removable from the top of the water heater for normal service and 
    inspection of the unit.
    •	The water heater vent must not be connected to any other gas appliance or vent stack.
    •	Avoid using an oversized vent pipe or using extremely long runs of the pipe.
    •	For rooftop venting, a rain cap or other form of termination that prevents rain water from 
    entering into the water heater must be installed.
    •	Do not common vent or connect any vent from other appliances to the water heater vent.
    General rules for vent terminations:
    •	Avoid locating the water heater vent termination near any air intake devices.  These fans can 
    pick up the exhaust flue products from the water heater and return them to the building.  This 
    can create a health hazard.
    •	Locate the vent termination so that it cannot be blocked by any debris, at any time.  Most codes 
    require that the termination must be at least 12 in. (305 mm) above grade, but the installer may 
    determine if it should be higher depending on the job site condition and applicable codes.
    •	A proper sidewall termination is recommended when the water heater is vented through a 
    sidewall.
    •	Regarding the clearances from the exhaust termination to the air inlet or opening, refer to the 
    next few pages.
    •	Improper venting of this appliance can result in excessive levels of carbon 
    monoxide which can result in severe personal injury or death.
    •	Improper installation can cause nausea or asphyxiation, severe injury or death 
    from carbon monoxide and flue gases poisoning.  Improper installation will 
    void product warranty.
    DANGER
    When installing the vent system, all applicable national and local codes must be 
    followed.  If you install thimbles, fire stops or other protective devices and they 
    penetrate any combustible or noncombustible construction, be sure to follow all 
    applicable national and local codes.CAUTION
    Installation
    Installation Manual  
    						
    							14   Page
    -Vent length and No. of Elbows-
    This is a Category III appliance and must be vented accordingly.  The vent system must be sealed airtight. 
    All seams and joints without gaskets must be sealed with high heat resistant silicone sealant or UL listed 
    aluminum adhesive tape having a minimum temperature rating of 350 °F (177 °C).  For best results, a vent 
    system should be as short and straight as possible.
    •	This water heater is a Category III appliance and must be vented accordingly with any 4 in. (102 
    mm) vent approved for use with Category III or Special BH type gas vent.
    •	Follow the vent pipe manufacturer’s instructions when installing the vent pipe.
    •	Do not common vent this appliance with any other vented appliance. (Do not terminate vent 
    into a chimney. If the vent must go through the chimney, the vent must run all the way through 
    the chimney with Category III approved or Special BH vent pipe.)
    •	When the horizontal vent run exceeds 5 ft. (1.5 m), support the vent run at 3 ft. (0.9 m) intervals 
    with overhead hangers.
    •	The maximum length of exhaust vent piping must not exceed 50 ft. (15.2 m) (deducting 5 ft. (1.5 
    m) for each elbow used in the venting system). Do not use more than 5 elbows.
    -DIPswitch settings for Vent length-
    For Indoor and direct-vent models
    Vent typeDiameterMax. No. of ElbowsMax. Vertical and Horizontal (Total) Vent Length
    Intake3 in. (76 mm)550 ft. (15.2 m )
    Exhaust4 in. (102 mm)550 ft. (15.2 m )
    *For each elbow added, deduct 5 ft. (1.5m) from max. vent length.
    No. of ElbowsMax. Vertical or Horizontal Vent Length
    050 ft. (15.2 m)
    145 ft. (13.7 m)
    240 ft. (12.2 m)
    335 ft. (10.7 m)
    430 ft. (9.1 m)
    525 ft. (7.6 m)
    Excludes elbow termination, rain caps, or the 4 in. (102 mm) Concentric termination
    Set DIPswitches shown in the table below depending on the vent length.
    110U Indoor (T-KJr2U-IN) 
    310U Indoor (T-K4U-IN) 
    510U Indoor (T-D2U-IN) 
    (Upper bank of DIPswitches)Vent length
    No. 6 : ON
    No. 7 : OFF
    No. 3 : ON
    No. 4 : OFF
    0 to 7 ft
    No. 6 : ON
    No. 7 : ON
    No. 3 : ON
    No. 4 : ON
    8 to 50 ft
    (DEFAULT)
    OFF
    ON12 34 5678
    OFF
    ON1 2 34 5678
    OFF
    ON1 2 34 56 78910
    OFF
    ON1 2 34 56 78910
    Installation
    Installation Manual  
    						
    							15  Page
    Venting Illustrations-
    For the 110U Indoor (T-KJr2U-IN), 310U Indoor (T-K4U-IN) and 510U Indoor (T-D2U-IN) models
    For details of the optional items, refer to the Installation  manual for each Optional item.
    Horizontal Installation with 
    Direct-vent concentric termination
    Wall
    Direct-vent concentric termination
    Installation of Direct-vent 
    conversion kit with water heater
    Water heater
    Intake port of Direct-vent conversion kit(For details see p. 10.)
    Plate of Direct-vent conversion kit
    Horizontal Installation
    Hanger
    Wall
    Sidewall vent termination
    Vertical condensation drain**
    Backflowpreventer*
    Vertical Installation 
    Backflow preventer*
    Rain cap
    Roof
    Vertical condensation drain**
    Roof flashing
    Installation
    Installation Manual
    *Backflow preventer (Recommended for freezing weather conditions: 36 °F (2 °C) and below).
    **Vertical condensation drain must be installed in accordance with local codes.
    See	the	picture	below	for	detailed	connection	instructions	to	Direct-vent	conversion	kit.
    Vertical Installation 
    (With direct-venting)
    Roof
    Vertical	condensation	drain**
    Backflow	preventer* Fire stop
    Roof	flashing
    Rain cap
    Horizontal Installation
    (With direct-venting)
    Sidewall vent termination
    Backflow	preventer*
    Vertical	condensation	drain**
    Wall
    Hanger
    Hanger  
    						
    							16  Page
    -Vent termination clearances-
    CanadaU.S.A
    Direct-vent and other 
    than Direct-vent
    Direct- 
    vent
    Other than  
    Direct-vent
    AClearance above grade, veranda, porch, deck, or 
    balcony1 foot1 foot1 foot
    B Clearance to window or door that may be opened3 feet1 foot 
    4 feet from below or 
    side opening. 1 foot 
    from above opening.
    CClearance to permanently closed window***
    D
    Vertical clearance to ventilated soffit located above 
    the vent terminator within a horizontal distance 
    of 2 feet (61cm) from the center line of the 
    terminator
    ***
    EClearance to unventilated soffit***
    FClearance to outside corner***
    GClearance to inside corner***
    HClearance to each side of center line extended 
    above meter/regulator assembly 3 feet**
    IClearance to service regulator vent outlet3 feet**
    J
    Clearance to non-mechanical air supply inlet to 
    building or the combustion air inlet to any other 
    application
    3 feet1 foot
    4 feet from below or 
    side opening. 1 foot 
    from above opening.
    KClearance to mechanical air supply inlet.6 feet3 feet3 feet
    LClearance above paved sidewalk or paved driveway  
    located on public property7 feet*7 feet
    MClearance under veranda, porch deck, or balcony1 foot**
       *For	clearances	 not	specified	 in	ANSI	 Z223.1	 /	NFPA	 54	or	CAN/CSA-B149.1,	 please	use	clearances	 in	accordance	
    with local installation codes and the requirements of the gas supplier.
    INSIDE CORNER DETAIL
    V
    Gas meter / regulator
    V
    V
    V
    V
    V
    V
    V
    V
    V
    X
    X
    X
    Vent terminal
    Air supply inlet
    Area where is not permittedG
    A
    E
    D
    B
    L
    C
    F
    B
    B
    B
    BA
    J
    OPERABLEFIXEDCLOSED
    B
    H
    M
    K
    OPERABLE
    FIXEDCLOSED
    I
    Installation
    Installation Manual  
    						
    							17  Page
    -For sidewall terminations-
    -For rooftop terminations-
    For multiple sidewall exhaust terminations (e.g. multi-
    unit systems), an exhaust termination must be at least 1 
    ft. (305mm) away from another exhaust termination.  An 
    exhaust termination must also be at least 2 ft. (610 mm) 
    away from an inside corner. (If the adjacent wall is less than 
    2 ft. (610 mm) of length, the minimum required distance 
    away from the inside corner will be equal to the length of 
    that adjacent wall.)
    For multiple-unit, direct-vent sidewall terminations that 
    combine the intake and exhaust into a single penetration, 
    space each direct-vent termination at least 1 ft. (305 mm) 
    away from each other, no matter the orientation.  A direct-
    vent termination must also be at least 2 ft. (610 mm) away 
    from an inside corner. (If the adjacent wall is less than 2 ft. 
    (610 mm) of length, the minimum required distance away 
    from the inside corner will be equal to the length of that 
    adjacent wall.)
    For direct-vent sidewall 
    terminations that use two 
    separate penetrations for 
    the intake and exhaust, 
    distance the intake and 
    exhaust terminations at 
    least 3 ft. (915 mm) away 
    from each other, no 
    matter the orientation.
    For multiple-unit rooftop terminations (whether for standard or direct-vent installations) space all 
    exhaust and intake terminations in accordance with local codes.  An exhaust termination must be spaced 
    from a wall or surface in accordance with local codes as well.  In the absence of such a code, an exhaust 
    termination must be a horizontal distance of at least 2 ft. (610 mm) away from a wall or surface.
    Exhaust and/or 
    direct-vent sidewall 
    terminations should 
    be at least 2 ft. (610 
    mm) away from an 
    opposite surface/
    wall.  Do not place 
    the termination 
    directly in front of 
    an opening into a 
    building.
    Please follow all local and national codes in regards to proper termination 
    clearances.  In the absence of such codes, the above clearances can be used as 
    guidelines.  Local codes supersede these guidelines.CAUTION
    A: In accordance with local codes
    Air intake
    A
    Exhaust	termination
    A
    A
    A
    A
    Air intake
    		2ft.(610 mm) min
    Exhaust termination
     3 ft.(915 mm) min
    Air supply inlet
    3 ft. (915 mm)min
    3 ft. (915 mm)min
    Exhaust termination
    Installation
    Installation Manual
    Exhaust terminationInsidecorner
     1 ft.(305 mm) min
     2 ft.(610 mm) min1 ft. (305 mm)min
    Combinedintake andexhausttermination
    Insidecorner
     1 ft. (305 mm) min
     2 ft.(610 mm) min1 ft. (305 mm)       min
    Exhausttermination2 ft. (610 mm)  min  
    						
    							18   Page
    GAS SUPPLY AND GAS PIPE SIZING
    -General-
    •	The minimum and maximum inlet gas pressures are:
    •	Inlet gas pressures that fall outside the range of values listed above may adversely affect the 
    performance of the water heater.  These pressures are measured when the water heater is in full 
    operation.
    •	Inlet gas pressure must not exceed the above maximum values; gas pressure above the specified range 
    will cause dangerous operating conditions and damage to the unit.
    •	Until testing of the main gas line supply pressure is completed, ensure the gas line to the water heater 
    is disconnected to avoid any damage to the water heater.
    -Gas connections-
    1. Install a manual gas shutoff valve between the water heater and the gas supply line.
    2. When the gas connections are completed, it is necessary to perform a gas leak test either by applying 
    soapy water to all gas fittings and observing for bubbles or by using a gas leak detection device.
    •	The water heater and its individual shutoff valve must be disconnected from the gas supply 
    piping system during any pressure testing of that system at test pressures in excess of 1/2 psi 
    (3.5 kPa).
    •	The water heater must be isolated from the gas supply piping system by closing its individual 
    manual shutoff valve during any pressure testing of the gas supply piping system at test 
    pressures equal to or less than 1/2 psi (3.5 kPa).
    3. Always purge the gas line of any debris and/or water before connecting to the gas inlet.
    Size  the gas pipe appropriately to supply the necessary volume of gas required 
    for	 the	 water	 heater	 using	ANSI	Z223.1/NFPA	 54	in	the	 USA	 or	CAN/CSA	 B149.1	in	
    Canada or local codes.  Otherwise, flow capabilities and output temperatures will 
    be limited.
    NOTICE
    Gas typeInlet gas pressure
    Natural GasMin. 5.0” W.C. (1.24 kPa) – Max. 10.5” W.C. (2.61 kPa)
    •	Check that the type of gas matches the rating plate first.
    •	Ensure that any and all gas regulators used are operating properly and 
    providing gas pressures within the specified range shown below.  Excess gas 
    inlet pressure may cause serious accidents.
    •	Conversion of this unit from natural gas to propane or vice versa will void 
    all warranty.  Contact your local distributor to get the correct unit for your 
    gas type.  The manufacturer is not liable for any property and/or personal 
    damage resulting from gas conversions.
    CAUTION
    Installation
    Installation Manual  
    						
    							19    Page
    -Natural Gas Supply Piping-
    Maximum delivery capacity of cubic feet of gas per hour of IPS pipe carrying Natural Gas with 0.60 specific gravity 
    based on pressure drop of 0.5" W.C.
    Based on energy content of 1,000 BTU/Cubic ft.: The water heater requires 140 Cubic ft./hr for the 110U (T-KJr2U) 
    model, 190 Cubic ft./hr for the 310U (T-K4U) model, and 199 Cubic ft./hr for the 510U (T-D2U) model.
    Based on Energy Content of 1,000 BTU/Cubic ft:
    Divide each appliance's BTU/h requirement by 1,000 BTU/ft3 to get the appliances ft3/h requirement.
    Take into account the distance the appliance is from the gas meter, look in the above gas chart to properly 
    size the line.
    For sections of the gas line supplying gas to more than one appliance (Ex: Point A to Point B), add up the cubic 
    ft. per hour requirements of the appliances that are being supplied by that section, and size to the farthest 
    appliance.
    For Example: The section from A to B supplies gas to the furnace, range and dryer.  Adding up the BTU/h 
    requirements and dividing by 1,000 yields a cubic ft. per hour requirement of 220 cubic ft. of gas per hour.  The 
    farthest appliance is the range, which is 50 ft. away from the meter.  Looking at the above chart, and under 
    the column of 50 ft., Section A to B needs to be 1" in order to supply 220 cubic ft.
         Water
         heater
    199,000 BTU/hDryer
     35,000 BTU/h
    Gas meterFurnace
    120,000 BTU/h
          Range
    65,000 BTU/h
    AB
    C
    10' Length
    1/2" Pipe size
    15' Length
    1/2" Pipe size
    15' Length
    1" Pipe size
    10' Length
    3/4" Pipe size
    10' Length
    1" Pipe size5' Length
    1-1/4" Pipe size
    10' Length
    3/4" Pipe size5' Length
    1-1/4" Pipe size
    Gas  sizing  example    
        (Natural Gas)
    Installation
    Installation Manual
    Pipe SizeLength
    Diameter10'20'30'40'50'60'70'80'90'100'125'150'200'
    3/4"363249200171152138127118111104938472
    1"684470377323286259239222208197174158135
    1 1/4"1,404965775663588532490456428404358324278
    1 1/2"2,1031,4451,161993880798734683641605536486416
    2"4,0502,7842,2351,9131,6961,5361,4131,3151,2341,1651,033936801
    Unit: Cubic feet per hour  
    						
    							20  Page
    -Measuring inlet gas pressure-
    The water heater cannot perform properly without sufficient inlet gas pressure.  Below are instructions on 
    how to check the inlet gas pressure.  THIS IS ONLY TO BE DONE BY A LICENSED PROFESSIONAL.
    WATER CONNECTIONS
    All pipes, pipe fittings, valves and other components, including soldering materials, must be suitable for 
    potable water systems.
    1. A manual shutoff valve must be installed on the cold water inlet to the water heater between the main 
    water supply line and the water heater.
    2. In addition, a manual shutoff valve is also recommended on the hot water outlet of the unit.  If the 
    water heater is installed within, or subjected to, a closed loop water system, a thermal expansion tank 
    or code approved device to handle thermal expansion must be installed.
    1. Turn off all electric power to the water heater if service is to be performed.
    2. Turn the manual gas valve located on the outside of the unit clockwise to the 
    off position.
    •	Do not use this water heater if any part has been submersed under water. 
    Immediately call a licensed professional to inspect the water heater to replace 
    any damaged parts.
    •	Do not reverse the hot outlet and cold inlet connections to the water heater.  
    This will not properly activate the water heater.CAUTION
    1. Shut off the manual gas valve on the gas supply line.
    2. Remove the screw for the pressure port located on the gas 
    inlet of the water heater shown in the diagram on the right.
    3. Connect the manometer to the pressure port.
    4. Re-open the manual gas valve.  Check to see that there 
    are no gas leaks.  Open some of the fixtures that use the 
    highest flow rate to turn on the water heater.
    5. Check the inlet gas pressure.  When the water heater is on 
    maximum and minimum burn, the manometer should read 
    from 5.0” to 10.5” W.C. (1.24 to 2.61 kPa) for Natural gas.
    3. Before installing the water heater, flush 
    the water line to remove all debris, and 
    after installation is complete, purge 
    the air from the line.  Failure to do so 
    may cause damage to the heater.
    4. There is a wire mesh filter within 
    the cold inlet to trap debris from 
    entering your heater.  This will need 
    to be cleaned periodically to maintain 
    optimum flow. (Refer to p. 41.)
    Pressure port
    Cold inletHot outlet
    Gas inlet
    As Close as 
    Possible
    Pressure relief valve
    Installation
    Installation Manual  
    						
    All American Water Heater manuals Comments (0)

    Related Manuals for American Water Heater NonCondensing UltraLow NOx Outdoor Natural Gas GT110UNE user manual