Home
>
American Water Heater
>
Gas Heater
>
American Water Heater NonCondensing UltraLow NOx Outdoor Natural Gas GT110UNE user manual
American Water Heater NonCondensing UltraLow NOx Outdoor Natural Gas GT110UNE user manual
Have a look at the manual American Water Heater NonCondensing UltraLow NOx Outdoor Natural Gas GT110UNE user manual online for free. It’s possible to download the document as PDF or print. UserManuals.tech offer 32 American Water Heater manuals and user’s guides for free. Share the user manual or guide on Facebook, Twitter or Google+.
11 Page WARNING FOR INSTALLATIONS FOR YOUR SAFETY, READ BEFORE INSTALLATION: Do not install the heater where water, debris or flammable vapors may get into the flue terminal. This may cause damage to the heater and void the warranty. Do not have the vent terminal pointing toward any opening into a building. Do not locate your heater in a pit or location where gas and water can accumulate. Do not install this water heater under an overhang less than 3 ft. (914 mm) from its top or eaves. The area under an overhang must be open to three sides (Outdoor models only). Do not install the water heater vent terminator within 1 ft. (305 mm) in the USA of any air intake or building opening, and within 3 ft. (914 mm) in Canada of any air intake or building opening (Outdoor models only, refer to p. 16). Do not install next to a dryer or any source of airborne debris that can be trapped inside the combustion chamber, unless the system is direct-vented. ProhibitedProhibited 1 ft. (305 mm) USA3 ft. (914 mm) Canada1 ft. (305 mm) USA3 ft. (914 mm) Canada 1 ft. (305 mm) USA3 ft. (914 mm) Canada3 ft. (914 mm) Installation Installation Manual Water heater vent terminator must be at least 2 ft. (610 mm) away from an inside corner for both outdoor installation and direct-vent installation. Inside Corner 2 ft. (610 mm)
12 Page HIGH-ALTITUDE INSTALLATIONS Check the elevation where your water heater is installed. Set DIPswitches shown in the table below depending on the altitude. Bank of DIPswitches 110U (T-KJr2U) and 310U (T-K4U) models Computer board WARNING DO NOT adjust any DIPswitches on the upper bank for the 510U (T-D2U) model. NOTE: The dark squares indicate the direction the DIPswitches should be set to. Lower bank of DIPswitches 510U (T-D2U) model Computer board Installation Installation Manual Outdoor models 0 to 2,000 ft. (DEFAULT) 2,000 to 4,000 ft. 4,000 to 6,000 ft. 110U (T-KJr2U) and 310U (T-K4U) modelsNo. 3 : OFF No. 4 : OFF No. 5 : OFF No. 3 : OFF No. 4 : OFF No. 5 : ON No. 3 : ON No. 4 : OFF No. 5 : ON 510U (T-D2U) model (Lower bank of DIPswitches)No. 2 : OFF No. 3 : OFF No. 4 : OFF No. 2 : OFF No. 3 : OFF No. 4 : ON No. 2 : ON No. 3 : OFF No. 4 : ON OFF ON123 456 78910 OFF ON1 2345678910 OFF ON1 23 456 78910 OFF ON1 23 456 OFF ON1 23 456 OFF ON1 23 456 Indoor models 0 to 2,000 ft. (DEFAULT) 2,000 to 3,000 ft. 3,000 to 5,000 ft. 5,000 to 7,500 ft. 7,500 to 10,100 ft. 110U (T-KJr2U) and 310U (T-K4U) modelsNo. 3 : OFF No. 4 : OFF No. 5 : OFF No. 3 : OFF No. 4 : ON No. 5 : OFF No. 3 : OFF No. 4 : OFF No. 5 : ON No. 3 : OFF No. 4 : ON No. 5 : ON No. 3 : ON No. 4 : ON No. 5 : ON 510U (T-D2U) model (Lower bank of DIPswitches)No. 2 : OFF No. 3 : OFF No. 4 : OFF No. 2 : OFF No. 3 : ON No. 4 : OFF No. 2 : OFF No. 3 : OFF No. 4 : ON No. 2 : OFF No. 3 : ON No. 4 : ON No. 2 : ON No. 3 : ON No. 4 : ON OFF ON1 23 456 78910 OFF ON1 23 456 78910 OFF ON1 2345678910 OFF ON1 2345678910 OFF ON1 23 456 OFF ON1 23 456 OFF ON1 23 456 OFF ON1 23 456 Altitude DIPswitches OFF ON1 2345678910 OFF ON1 23 456 Installation altitude The maximum certified or allowable installed altitude is 10,100 ft. for indoor models and 6,000 ft. for outdoor models.
13 Page VENTING INSTRUCTIONS For indoor models -General- The water heater must be vented in accordance with the section “Venting of Equipment" of the latest edition of the National Fuel Gas Code: ANSI Z223.1/NFPA 54 in the United States and/or Section 7 of the CAN/CSA B149.1 Natural Gas Installation Code in Canada, as well as applicable local building codes. The manufacturer recommends the NovaVent line. However, the following are also UL listed manufacturers: ProTech Systems Inc. (FasNSeal), Metal-Fab Inc., and Heat-Fab Inc. (Saf-T Vent). General rules for venting water heaters are: • Place the water heater as close as possible to the vent termination. • The vent collar of the water heater must be fastened directly to an unobstructed vent pipe. • Do not weld the vent pipe to the water heater’s vent collar. • Do not cut the vent collar of the unit. • The vent must be easily removable from the top of the water heater for normal service and inspection of the unit. • The water heater vent must not be connected to any other gas appliance or vent stack. • Avoid using an oversized vent pipe or using extremely long runs of the pipe. • For rooftop venting, a rain cap or other form of termination that prevents rain water from entering into the water heater must be installed. • Do not common vent or connect any vent from other appliances to the water heater vent. General rules for vent terminations: • Avoid locating the water heater vent termination near any air intake devices. These fans can pick up the exhaust flue products from the water heater and return them to the building. This can create a health hazard. • Locate the vent termination so that it cannot be blocked by any debris, at any time. Most codes require that the termination must be at least 12 in. (305 mm) above grade, but the installer may determine if it should be higher depending on the job site condition and applicable codes. • A proper sidewall termination is recommended when the water heater is vented through a sidewall. • Regarding the clearances from the exhaust termination to the air inlet or opening, refer to the next few pages. • Improper venting of this appliance can result in excessive levels of carbon monoxide which can result in severe personal injury or death. • Improper installation can cause nausea or asphyxiation, severe injury or death from carbon monoxide and flue gases poisoning. Improper installation will void product warranty. DANGER When installing the vent system, all applicable national and local codes must be followed. If you install thimbles, fire stops or other protective devices and they penetrate any combustible or noncombustible construction, be sure to follow all applicable national and local codes.CAUTION Installation Installation Manual
14 Page -Vent length and No. of Elbows- This is a Category III appliance and must be vented accordingly. The vent system must be sealed airtight. All seams and joints without gaskets must be sealed with high heat resistant silicone sealant or UL listed aluminum adhesive tape having a minimum temperature rating of 350 °F (177 °C). For best results, a vent system should be as short and straight as possible. • This water heater is a Category III appliance and must be vented accordingly with any 4 in. (102 mm) vent approved for use with Category III or Special BH type gas vent. • Follow the vent pipe manufacturer’s instructions when installing the vent pipe. • Do not common vent this appliance with any other vented appliance. (Do not terminate vent into a chimney. If the vent must go through the chimney, the vent must run all the way through the chimney with Category III approved or Special BH vent pipe.) • When the horizontal vent run exceeds 5 ft. (1.5 m), support the vent run at 3 ft. (0.9 m) intervals with overhead hangers. • The maximum length of exhaust vent piping must not exceed 50 ft. (15.2 m) (deducting 5 ft. (1.5 m) for each elbow used in the venting system). Do not use more than 5 elbows. -DIPswitch settings for Vent length- For Indoor and direct-vent models Vent typeDiameterMax. No. of ElbowsMax. Vertical and Horizontal (Total) Vent Length Intake3 in. (76 mm)550 ft. (15.2 m ) Exhaust4 in. (102 mm)550 ft. (15.2 m ) *For each elbow added, deduct 5 ft. (1.5m) from max. vent length. No. of ElbowsMax. Vertical or Horizontal Vent Length 050 ft. (15.2 m) 145 ft. (13.7 m) 240 ft. (12.2 m) 335 ft. (10.7 m) 430 ft. (9.1 m) 525 ft. (7.6 m) Excludes elbow termination, rain caps, or the 4 in. (102 mm) Concentric termination Set DIPswitches shown in the table below depending on the vent length. 110U Indoor (T-KJr2U-IN) 310U Indoor (T-K4U-IN) 510U Indoor (T-D2U-IN) (Upper bank of DIPswitches)Vent length No. 6 : ON No. 7 : OFF No. 3 : ON No. 4 : OFF 0 to 7 ft No. 6 : ON No. 7 : ON No. 3 : ON No. 4 : ON 8 to 50 ft (DEFAULT) OFF ON12 34 5678 OFF ON1 2 34 5678 OFF ON1 2 34 56 78910 OFF ON1 2 34 56 78910 Installation Installation Manual
15 Page Venting Illustrations- For the 110U Indoor (T-KJr2U-IN), 310U Indoor (T-K4U-IN) and 510U Indoor (T-D2U-IN) models For details of the optional items, refer to the Installation manual for each Optional item. Horizontal Installation with Direct-vent concentric termination Wall Direct-vent concentric termination Installation of Direct-vent conversion kit with water heater Water heater Intake port of Direct-vent conversion kit(For details see p. 10.) Plate of Direct-vent conversion kit Horizontal Installation Hanger Wall Sidewall vent termination Vertical condensation drain** Backflowpreventer* Vertical Installation Backflow preventer* Rain cap Roof Vertical condensation drain** Roof flashing Installation Installation Manual *Backflow preventer (Recommended for freezing weather conditions: 36 °F (2 °C) and below). **Vertical condensation drain must be installed in accordance with local codes. See the picture below for detailed connection instructions to Direct-vent conversion kit. Vertical Installation (With direct-venting) Roof Vertical condensation drain** Backflow preventer* Fire stop Roof flashing Rain cap Horizontal Installation (With direct-venting) Sidewall vent termination Backflow preventer* Vertical condensation drain** Wall Hanger Hanger
16 Page -Vent termination clearances- CanadaU.S.A Direct-vent and other than Direct-vent Direct- vent Other than Direct-vent AClearance above grade, veranda, porch, deck, or balcony1 foot1 foot1 foot B Clearance to window or door that may be opened3 feet1 foot 4 feet from below or side opening. 1 foot from above opening. CClearance to permanently closed window*** D Vertical clearance to ventilated soffit located above the vent terminator within a horizontal distance of 2 feet (61cm) from the center line of the terminator *** EClearance to unventilated soffit*** FClearance to outside corner*** GClearance to inside corner*** HClearance to each side of center line extended above meter/regulator assembly 3 feet** IClearance to service regulator vent outlet3 feet** J Clearance to non-mechanical air supply inlet to building or the combustion air inlet to any other application 3 feet1 foot 4 feet from below or side opening. 1 foot from above opening. KClearance to mechanical air supply inlet.6 feet3 feet3 feet LClearance above paved sidewalk or paved driveway located on public property7 feet*7 feet MClearance under veranda, porch deck, or balcony1 foot** *For clearances not specified in ANSI Z223.1 / NFPA 54 or CAN/CSA-B149.1, please use clearances in accordance with local installation codes and the requirements of the gas supplier. INSIDE CORNER DETAIL V Gas meter / regulator V V V V V V V V V X X X Vent terminal Air supply inlet Area where is not permittedG A E D B L C F B B B BA J OPERABLEFIXEDCLOSED B H M K OPERABLE FIXEDCLOSED I Installation Installation Manual
17 Page -For sidewall terminations- -For rooftop terminations- For multiple sidewall exhaust terminations (e.g. multi- unit systems), an exhaust termination must be at least 1 ft. (305mm) away from another exhaust termination. An exhaust termination must also be at least 2 ft. (610 mm) away from an inside corner. (If the adjacent wall is less than 2 ft. (610 mm) of length, the minimum required distance away from the inside corner will be equal to the length of that adjacent wall.) For multiple-unit, direct-vent sidewall terminations that combine the intake and exhaust into a single penetration, space each direct-vent termination at least 1 ft. (305 mm) away from each other, no matter the orientation. A direct- vent termination must also be at least 2 ft. (610 mm) away from an inside corner. (If the adjacent wall is less than 2 ft. (610 mm) of length, the minimum required distance away from the inside corner will be equal to the length of that adjacent wall.) For direct-vent sidewall terminations that use two separate penetrations for the intake and exhaust, distance the intake and exhaust terminations at least 3 ft. (915 mm) away from each other, no matter the orientation. For multiple-unit rooftop terminations (whether for standard or direct-vent installations) space all exhaust and intake terminations in accordance with local codes. An exhaust termination must be spaced from a wall or surface in accordance with local codes as well. In the absence of such a code, an exhaust termination must be a horizontal distance of at least 2 ft. (610 mm) away from a wall or surface. Exhaust and/or direct-vent sidewall terminations should be at least 2 ft. (610 mm) away from an opposite surface/ wall. Do not place the termination directly in front of an opening into a building. Please follow all local and national codes in regards to proper termination clearances. In the absence of such codes, the above clearances can be used as guidelines. Local codes supersede these guidelines.CAUTION A: In accordance with local codes Air intake A Exhaust termination A A A A Air intake 2ft.(610 mm) min Exhaust termination 3 ft.(915 mm) min Air supply inlet 3 ft. (915 mm)min 3 ft. (915 mm)min Exhaust termination Installation Installation Manual Exhaust terminationInsidecorner 1 ft.(305 mm) min 2 ft.(610 mm) min1 ft. (305 mm)min Combinedintake andexhausttermination Insidecorner 1 ft. (305 mm) min 2 ft.(610 mm) min1 ft. (305 mm) min Exhausttermination2 ft. (610 mm) min
18 Page GAS SUPPLY AND GAS PIPE SIZING -General- • The minimum and maximum inlet gas pressures are: • Inlet gas pressures that fall outside the range of values listed above may adversely affect the performance of the water heater. These pressures are measured when the water heater is in full operation. • Inlet gas pressure must not exceed the above maximum values; gas pressure above the specified range will cause dangerous operating conditions and damage to the unit. • Until testing of the main gas line supply pressure is completed, ensure the gas line to the water heater is disconnected to avoid any damage to the water heater. -Gas connections- 1. Install a manual gas shutoff valve between the water heater and the gas supply line. 2. When the gas connections are completed, it is necessary to perform a gas leak test either by applying soapy water to all gas fittings and observing for bubbles or by using a gas leak detection device. • The water heater and its individual shutoff valve must be disconnected from the gas supply piping system during any pressure testing of that system at test pressures in excess of 1/2 psi (3.5 kPa). • The water heater must be isolated from the gas supply piping system by closing its individual manual shutoff valve during any pressure testing of the gas supply piping system at test pressures equal to or less than 1/2 psi (3.5 kPa). 3. Always purge the gas line of any debris and/or water before connecting to the gas inlet. Size the gas pipe appropriately to supply the necessary volume of gas required for the water heater using ANSI Z223.1/NFPA 54 in the USA or CAN/CSA B149.1 in Canada or local codes. Otherwise, flow capabilities and output temperatures will be limited. NOTICE Gas typeInlet gas pressure Natural GasMin. 5.0” W.C. (1.24 kPa) – Max. 10.5” W.C. (2.61 kPa) • Check that the type of gas matches the rating plate first. • Ensure that any and all gas regulators used are operating properly and providing gas pressures within the specified range shown below. Excess gas inlet pressure may cause serious accidents. • Conversion of this unit from natural gas to propane or vice versa will void all warranty. Contact your local distributor to get the correct unit for your gas type. The manufacturer is not liable for any property and/or personal damage resulting from gas conversions. CAUTION Installation Installation Manual
19 Page -Natural Gas Supply Piping- Maximum delivery capacity of cubic feet of gas per hour of IPS pipe carrying Natural Gas with 0.60 specific gravity based on pressure drop of 0.5" W.C. Based on energy content of 1,000 BTU/Cubic ft.: The water heater requires 140 Cubic ft./hr for the 110U (T-KJr2U) model, 190 Cubic ft./hr for the 310U (T-K4U) model, and 199 Cubic ft./hr for the 510U (T-D2U) model. Based on Energy Content of 1,000 BTU/Cubic ft: Divide each appliance's BTU/h requirement by 1,000 BTU/ft3 to get the appliances ft3/h requirement. Take into account the distance the appliance is from the gas meter, look in the above gas chart to properly size the line. For sections of the gas line supplying gas to more than one appliance (Ex: Point A to Point B), add up the cubic ft. per hour requirements of the appliances that are being supplied by that section, and size to the farthest appliance. For Example: The section from A to B supplies gas to the furnace, range and dryer. Adding up the BTU/h requirements and dividing by 1,000 yields a cubic ft. per hour requirement of 220 cubic ft. of gas per hour. The farthest appliance is the range, which is 50 ft. away from the meter. Looking at the above chart, and under the column of 50 ft., Section A to B needs to be 1" in order to supply 220 cubic ft. Water heater 199,000 BTU/hDryer 35,000 BTU/h Gas meterFurnace 120,000 BTU/h Range 65,000 BTU/h AB C 10' Length 1/2" Pipe size 15' Length 1/2" Pipe size 15' Length 1" Pipe size 10' Length 3/4" Pipe size 10' Length 1" Pipe size5' Length 1-1/4" Pipe size 10' Length 3/4" Pipe size5' Length 1-1/4" Pipe size Gas sizing example (Natural Gas) Installation Installation Manual Pipe SizeLength Diameter10'20'30'40'50'60'70'80'90'100'125'150'200' 3/4"363249200171152138127118111104938472 1"684470377323286259239222208197174158135 1 1/4"1,404965775663588532490456428404358324278 1 1/2"2,1031,4451,161993880798734683641605536486416 2"4,0502,7842,2351,9131,6961,5361,4131,3151,2341,1651,033936801 Unit: Cubic feet per hour
20 Page -Measuring inlet gas pressure- The water heater cannot perform properly without sufficient inlet gas pressure. Below are instructions on how to check the inlet gas pressure. THIS IS ONLY TO BE DONE BY A LICENSED PROFESSIONAL. WATER CONNECTIONS All pipes, pipe fittings, valves and other components, including soldering materials, must be suitable for potable water systems. 1. A manual shutoff valve must be installed on the cold water inlet to the water heater between the main water supply line and the water heater. 2. In addition, a manual shutoff valve is also recommended on the hot water outlet of the unit. If the water heater is installed within, or subjected to, a closed loop water system, a thermal expansion tank or code approved device to handle thermal expansion must be installed. 1. Turn off all electric power to the water heater if service is to be performed. 2. Turn the manual gas valve located on the outside of the unit clockwise to the off position. • Do not use this water heater if any part has been submersed under water. Immediately call a licensed professional to inspect the water heater to replace any damaged parts. • Do not reverse the hot outlet and cold inlet connections to the water heater. This will not properly activate the water heater.CAUTION 1. Shut off the manual gas valve on the gas supply line. 2. Remove the screw for the pressure port located on the gas inlet of the water heater shown in the diagram on the right. 3. Connect the manometer to the pressure port. 4. Re-open the manual gas valve. Check to see that there are no gas leaks. Open some of the fixtures that use the highest flow rate to turn on the water heater. 5. Check the inlet gas pressure. When the water heater is on maximum and minimum burn, the manometer should read from 5.0” to 10.5” W.C. (1.24 to 2.61 kPa) for Natural gas. 3. Before installing the water heater, flush the water line to remove all debris, and after installation is complete, purge the air from the line. Failure to do so may cause damage to the heater. 4. There is a wire mesh filter within the cold inlet to trap debris from entering your heater. This will need to be cleaned periodically to maintain optimum flow. (Refer to p. 41.) Pressure port Cold inletHot outlet Gas inlet As Close as Possible Pressure relief valve Installation Installation Manual