Home
>
American Water Heater
>
Gas Heater
>
American Water Heater Heavy Duty Commercial Gas BCG3 User Manual
American Water Heater Heavy Duty Commercial Gas BCG3 User Manual
Have a look at the manual American Water Heater Heavy Duty Commercial Gas BCG3 User Manual online for free. It’s possible to download the document as PDF or print. UserManuals.tech offer 32 American Water Heater manuals and user’s guides for free. Share the user manual or guide on Facebook, Twitter or Google+.

31 FIGURE 25. If the Temperature-Pressure Relief Valve on water heater weeps or discharges periodically, this may be due to thermal expansion. NOTE: Excessive water pressure is the most common cause of Temperature-Pressure Relief Valve leakage. Excessive water system pressure is most often caused by "thermal expansion" in a "closed system." See Closed Water Systems and Thermal Expansion on page 12. The Temperature- Pressure Relief Valve is not intended for the constant relief of thermal expansion. Temperature-Pressure Relief Valve leakage due to pressure build up in a closed system that does not have a thermal expansion tank installed is not covered under the limited warranty. Thermal expansion tanks must be installed on all closed water systems. DO NOT PLUG THE TEMPERATURE-PRESSURE RELIEF VALVE OPENING. THIS CAN CAUSE PROPERTY DAMAGE, SERIOUS INJURY OR DEATH. Explosion Hazar d Temperature-Pressure Relief Valve must comply with ANSI Z21.22- CSA 4.4 and ASME code. Properly sized temperature- pressure relief valve must be installed in opening provided. Can result in overheating and excessive tank pressure. Can cause serious injury or death. ANODE ROD INSPECTION Property Damage Hazard Avoid water heater damage. Inspection and replacement of anode rod required. CAUTION The anode rod is used to protect the tank from corrosion. Most hot water tanks are equipped with an anode rod. The submerged rod sacrifices itself to protect the tank. Instead of corroding tank, VENTING SYSTEM Examine the venting system every six months for obstructions and/or deterioration of the vent piping. Remove all soot or other obstructions from chimney which will retard free draft. REMOTE STORAGE TANK TEMPERATURE CONTROL The water temperature in the remote storage tank (if used) is controlled by the storage tank temperature control. The sensing element is mounted in the hot water storage tank, see Water Piping Diagram section. A change in water temperature in the storage tank lower than the tank temperature control setting will cause the sensor to activate the circulating pump. The pump then circulates the water through the heater where the thermostat senses the drop in water temperature and activates main burner operation of the water heater. If the storage tank temperature control is out of calibration, replace with new control. SHOULD OVERHEATING OCCUR OR THE GAS SUPPLY FAIL TO SHUT OFF, TURN OFF THE MANUAL GAS CONTROL VALVE TO THE WATER HEATER. TEMPERATURE-PRESSURE RELIEF VALVE TEST Burn hazard. Hot water discharge. Keep clear of Temperature- Pressure Relief V alve discharge outlet. It is recommended that the Temperature-Pressure Relief Valve should be checked to ensure that it is in operating condition every 6 months. When checking the Temperature-Pressure Relief Valve operation, make sure that (1) no one is in front of or around the outlet of the Temperature-Pressure Relief Valve discharge line, and (2) that the water discharge will not cause any property damage, as the water may be extremely hot. Use care when operating valve as the valve may be hot. To check the pressure relief valve , lift the lever at the end of the valve several times, see Figure 25. The valve should seat properly and operate freely. If after manually operating the valve, it fails to completely reset and continues to release water, immediately close the cold water inlet to the water heater and drain the water heater, see Draining And Flushing on page 32. Replace the Temperature-Pressure Relief Valve with a properly rated/sized new one, see Temperature- Pressure Relief Valve on pages 12-13 for instructions on replacement. MAINTENANCE

32 5. Ensure the drain hose is secured before and during the entire flushing procedure. Flushing is performed with system water pressure applied to the water heater. 6. Open the water heater drain valve to flush the storage tank. 7. Flush the water heater storage tank to remove sediment and allow the water to flow until it runs clean. 8. Close the water heater drain valve when flushing is completed. 9. Remove the drain hose. 10. Fill the water heater - see Filling The Water Heater in this manual. 11. Turn on the electrical supply to place the water heater back in operation. 12. Allow the water heater to complete several heating cycles to ensure it is operating properly. RECOMMENDED PROCEDURE FOR PERIODIC REMOVAL OF LIME DEPOSITS FROM TANK TYPE COMMERCIAL WATER HEATERS The amount of calcium carbonate (lime) released from water is in direct proportion to water temperature and usage, see chart. The higher the water temperature or water usage, the more lime deposits are dropped out of the water. This is the lime scale which forms in pipes, heaters and on cooking utensils. Lime accumulation not only reduces the life of equipment but also reduces efficiency of the heater and increases fuel consumption. The usage of water softening equipment greatly reduces the hardness of the water. However, this equipment does not always remove all of the hardness (lime). For this reason it is recommended that a regular schedule for deliming be maintained. The time between cleaning will vary from weeks to months depending upon water conditions and usage. The depth of lime buildup should be measured periodically. Heaters equipped with cleanouts will have about 2" of lime buildup when the level of lime has reached the bottom of the cleanout opening. A schedule for deliming should then be set up,based on the amount of time it would take for a 1" buildup of lime. It is recommended that the water heater initially be inspected after 6 months. Example 1: Initial inspection after 6 months shows 1/2" of lime accumulation. Therefore, the heater should be delimed once a year. Example 2: Initial inspection after 6 months shows 2" of lime accumulation. Therefore, the heater should be delimed every 3 months. FIGURE 26. water ions attack and eat away the anode rod. This does not affect water’s taste or color. The rod must be maintained to keep tank in operating condition. Anode rod deterioration depends on water conductivity, not necessarily water condition. A corroded or pitted anode rod indicates high water conductivity and should be checked and/or replaced more often than an anode rod that appears to be intact. Replacement of a depleted anode rod can extend the life of your water heater. Inspection should be conducted by a qualified technician, and at a minimum should be checked annually after the warranty period. Artificially softened water is exceedingly corrosive because the process substitutes sodium ions for magnesium and calcium ions. The use of a water softener may decrease the life of the water heater tank. The anode rod should be inspected after a maximum of three years and annually thereafter until the condition of the anode rod dictates its replacement. Anode replacement is not covered by warranty. NOTE: artificially softened water requires the anode rod to be inspected annually. DRAINING AND FLUSHING Burn harzard. Hot water discharge. Keep hands clear of drain valve discharge. It is recommended that the water heater storage tank be drained and flushed every 6 months to reduce sediment buildup. The water heater should be drained if being shut down during freezing temperatures. See Features And Components in this manual for the location of the water heater components described below. TO DRAIN THE WATER HEATER STORAGE TANK: 1. Turn off the electrical supply to the water heater. 2. Turn off the gas supply at the Main Gas Shutoff Valve if the water heater is going to be shut down for an extended period. 3. Ensure the cold water inlet valve is open. 4. Open a nearby hot water faucet and let the water run until the water is no longer hot. 5. Close the cold water inlet valve to the water heater. 6. Connect a hose to the water heater drain valve and terminate it to an adequate drain. 7. Open the water heater drain valve and allow all the water to drain from the storage tank. 8. Close the water heater drain valve when all water in the storage tank has drained. 9. Close the hot water faucet opened in Step 4. 10. If the water heater is going to be shut down for an extended period, the drain valve should be left open. TO FLUSH THE WATER HEATER STORAGE TANK: 1. Turn off the electrical supply to the water heater. 2. Ensure the cold water inlet valve is open. 3. Open a nearby hot water faucet and let the water run until the water is no longer hot. Then close the hot water faucet. 4. Connect a hose to the drain valve and terminate it to an adequate drain.

33 Do not smoke or have open flame or sparks in vicinity of heater. Do not mix UN•LIME with other chemicals. Do not allow contact with magnesium, aluminum or galvanized metals. Chemical Hazard • Product contains phosphoric acid. • Keep out of reach of children. • Use rubber or neoprene gloves. Contains phosphoric acid. In case of external contact, flush with cool water. If irritation persists, get medical attention. If swallowed, give 1 or 2 glasses of water or milk and call physician. Get immediate medical attention for eyes. Keep out of reach of children. NOTE: THE USE OF RUBBER OR NEOPRENE GLOVES IS RECOMMENDED, ESPECIALLY IF YOU HAVE ANY OPEN SORES OR CUTS TO AVOID UNNECESSARY IRRITATION OR DISCOMFORT. 1. Turn off fuel and/or power supply to heater. Also, turn off power to any electrical device or equipment, which is attached, or part of the system. 2. Open hot water side of faucet closest to heater and allow water to run until it is cool enough to handle safely. 3. Close cold water inlet valve to heater. 4. Connect hose to drain valve at bottom of heater and start draining heater into suitable floor drain area. 5. Remove pressure relief valve while heater is draining. N OT E: D o not replac e pre s sure reli ef valve unt il deliming is completed. Pressure relief valve opening will also act as a vent in c ase of possible c ontact bet ween the delimer and the anode rod(s), which may produce flammable hydrogen-air mixtures. 6. If pressure relief valve appears to be limed-up, place it in a clean glass or plastic container adequate in size so that you can pour enough UN•LIME® into container to cover the valve and allow space for foaming. When foaming stops, run fresh cool water into the container and rinse the pressure relief valve for a few minutes. 7. If heater does not drain completely after a reasonable length of time, turn off the main water supply valve to stop water from entering the tank due to a by-pass problem or defective cold water inlet valve. Also, check for clogged drain valve opening. Heater must be completely drained before introducing UN•LIME. 8. Remove the cleanout cover and place a clean plastic bucket next to the cleanout opening. Partially open the cold water inlet valve to allow time to accomplish the following and then close the valve. DELIMING SOLVENTS UN•LIME is recommended for deliming. UN•LIME is a patented food grade acid which is safe to handle and does not create the harmful fumes which are associated with other products. UN•LIME may be obtained from your dealer, distributor or water heater manufacturer. Order Part Number 9005416105, 1 gallon, packed 4 gallons per case or Part Number 9005417105, 5 gallon container. NOTE: Un•Lime is not available for use in Canada. Hydrochloric base acids are not recommended for use on glass lined tanks. Observe handling instructions on label of product being used. TANK CLEANOUT PROCEDURE The following practices will ensure longer life and enable the unit to operate at its designed efficiency: 1. Once a month the heater should be flushed. Open drain valve and allow two gallons of water to drain from heater. Inlet water valve should remain open to maintain pressure in tank. 2. A cleanout opening is provided for periodic cleaning of the tank. Gas must be shut off and heater drained before opening cleanout. To clean heater through cleanout opening, proceed as follows: 3. Drain heater. 4. Remove outer cover plate from lower side of heater jacket. 5. Remove six (6) hex head screws securing tank cleanout plate and remove plate. 6. Remove lime, scale, or sediment using care not to damage the glass lining. 7. Inspect cleanout plate gasket, if new gasket is required, replace with part no. 9004099215. 8. Install cleanout plate. Be sure to draw plate up tight by tightening screws securely. 9. Replace outer jacket cover plate. In some water areas the sediment might not be removed by this method and may result in the water heater making rumbling or boiling noises. To dissolve and remove these more stubborn mineral deposits, UN•LIME Professional Delimer should be used. DELIMING USING FLO- JUG METHOD UN•LIME in the 5 gallon size is recommended for deliming of all models. Contact your local dealer, distributor or, water heater manufacturer: Prepare the Water Heater To delime the water heater using the Flo-Jug method, first prepare the heater for deliming. Explosion Hazard Flammable hydrogen gases may be present . Keep all ignition sources away from faucet when turning on hot water.

34 FIGURE 27. PILOT BURNER At least once a year, check the pilot burner, Figure 29, and the main burner, Figure 30, for proper operation. See Figure 28 for the location of the Pilot Burner and the Main Burners. For access to pilot, unfasten two screws to burner cover and remove. Locate the burner with pilot and remove screw holding burner to manifold. Unfasten pilot tubing from valve and slide out burner and pilot. Servicing of the pilot burner includes keeping pilot free of lint, cleaning the burner head, the primary air opening and the orifice of the pilot burner. FIGURE 28. FIGURE 29. Pilot burner flame is affected by:. 1. Low gas pressure. • Adjust pilot flame by means of the pilot gas adjustment located on the gas control valve. See Figure 31. • The pilot flame should envelop sensing device with 5/8” (1.6cm) flame, Figure30. Remove pilot adjustment cover screw, Figure 31. Turn inner adjustment screw clockwise to decrease, or counterclockwise to increase pilot flame. Be sure to replace cover screw on gas control valve after adjustment to prevent possible gas leakage. 2. Clogged pilot burner orifice. • Clean or replace orifice. A clogged orifice will restrict gas flow. While the water is being run through the tank, insert a stiff wire, copper tube flattened at one end or an opened wire coat hanger through the cleanout opening and scrape out any loose deposits of scale or sediment. This is an economical way to avoid unnecessary usage of the deliming solution. Repeat the opening and closing of the cold water inlet valve as necessary but be sure the heater is completely drained when ready to introduce the UN•LIME. Upon completion, reinstall the cleanout cover and use a new cleanout cover gasket (part number 9004099215). Remove the drain valve. 9. Install the long plastic male adapter insert fitting into the drain valve opening of heater after applying Teflon tape or paste to threads. Tighten firmly by hand and use wrench or adjustable pliers to check for secure connection. Do not over tighten to avoid damage to threads and fittings. Prepare the Up-N-Down Transfer Kit The next step is the preparation on the Up-N-Down Transfer Kit, if you have not already done so: 1. With the 5 gallon Up-N-Down container in the vertical position, unscrew the plastic vent cap in the handle and pierce the plastic membrane over the vent boss under the cap to allow the container to vent. Note: If your container does not have the vent cap and vent b o s s, dr ill a 3 /16 ” h o l e in t he handl e. W hen you have fi nishe d deliming you will be able to plug this drilled vent with the stainless steel screw that is supplied with the kit. 2. Remove the container’s cap and cut the plastic membrane located in the 3/4” IPT opening in the cap. Take care to not damage the threads. 3. Find the 3/4” male adapter, apply teflon tape to the threaded end and screw it into the 3/4” IPT opening in the cap. 4. Put cap with male adapter back on the container and slide 3/4” hose over end of male adapter and fasten in place using hose clamp provided. Delime using Flo-Jug Method 5. Slide the hose clamp over end of hose and slide hose over the male adapter in the water heater drain opening and secure in place using hose clamp. 6. Lift container to the “Pour” Position, see Figure 27, being careful to keep the vent in the handle above the liquid level and pour the UN•LIME into the heater. 7. Lower container, you may have to place the container on its empty carton to prevent the UN•LIME from flowing back into the container. 8. Let UN•LIME remain in the heater for 5 minutes and then lower the container to the “Drain” Position, see Figure 27. 9. Deliming activity is indicated by foaming on the surface of the UN•LIME. If there is deliming activity, repeat steps 6 thru 8. Normally, lime removal will be completed within one hour. Severe build-up of lime may take longer than an hour to complete descaling. Note: To check UN•LIME for continued use, place some scale or white chalk in a glass with a small amount of UN•LIME. If the material is vigorously dissolved by the UN•LIME, it can be reused; if not, the UN•LIME should be replaced.

35 GAS CONTROL VALVE Figure 31 shows the two types of combination gas control valves used on these heaters. If gas control valve becomes defective, repairs should not be attempted. A new valve should be installed in place of defective one. LP VALVE NATURAL VALVEFIGURE 31. SERVICE The installer may be able to observe and correct certain problems which may arise when the unit is put into operation. HOWEVER, it is recommended that only a qualified service technician or qualified agencys, using appropriate test equipment, be allowed to service the heater. As preliminary step, check wiring against diagram, check for grounded, broken or loose wires. Check all wire ends to be sure that they are making good contact.ELECTRICAL SERVICING LABEL ALL WIRES PRIOR TO DISCONNECTION WHEN SERVICING CONTROLS. WIRING ERRORS CAN CAUSE IMPROPER AND DANGEROUS OPERATION. VERIFY PROPER OPERATION AFTER SERVICING. Pilot sensing device must sense a flame before sparking will stop. Loose wires or a draft may cause intermittent or abnormal sparking. To eliminate this condition, first correct loose wiring condition, and then, if necessary, increase pilot flame. MAIN BURNER The main burner, Figure 30, should display the following characteristics: • Cause rapid ignition and carry over of flame across entire burner. • Give reasonably quiet operation during ignition, burning and extinction. • Cause no excessive lifting of flame from burner ports. If the preceding burner characteristics are not evident, check for accumulation of lint or other foreign material that restricts or other foreign material that restricts or blocks air openings to burner or heater. To clean main burners: 1. Remove main burners from unit. 2. Check that burner venturi and ports are free of foreign matter. 3. Clean burners with bristle brush and/or vacuum cleaner DO NOT distort burner ports or pilot location. 4. Reinstall burners in unit. Make sure front and rear of burners are installed correctly in burner support brackets. Also check for good flow of combustion and ventilating air to the unit. TYPICAL PILOT AND MAIN BURNER FLAMES FIGURE 30.

36 receptacle. Do not push meter leads into harness receptacle. This opens the pins and will create connection problems. See the following EFFIKAL RVGP-KSF-SERIES FLUE DAMPER TROUBLE SHOOTING GUIDE. Green LED Flash Code a Indicates Next Syste m A ction Reco mmended Service Act ion OFF No “Call for Heat” Not applicab le None Flash Fast Power up - in ter nal check Not applicab le None Heartbeat Norma l startu p – ig niti on seque nce starte d (incl udi ng prep urge) Not appl icab le None 4 Seco nds ON the n “ x” fl ash es Devi ce in run mode. “ x” = flame cu rre nt to t he ne arest μ A. Not appl icab le None 2 5 minute Retry D elay - Pil ot f lame n ot d etected d uring tri al for i gnit ion In iti ate n ew tri al for i gnit ion after retry del ay compl eted. If system fai ls to ligh t o n n e xt tri al for i gniti on ch eck gas s uppl y, pi lot bu rner, spark a nd flame sense wi rin g, fl ame rod co ntami nat ed or ou t o f posi tion , b urn er gro und connecti on. 3 Recycle - Fl ame fail ed during r un Initi ate n ew tri al for i gnit ion . Fl ash code wi ll rema in t hro ug h t he i gn it ion tri al u ntil fl ame is proved. If system fai ls to ligh t o n n e xt tri al for i gniti on , ch eck gas s uppl y, pi lot bu rner, fl ame se nse wi ring, con tami nati on of fl ame rod, b urn er ground co nnecti on. 4 Flame sen sed out of seq ue nce If situati on sel f corrects wi thin 10 seco nds, co ntrol ret urn s to normal seque nce. If fl am e o ut of seque nce remai ns l on ger t han 10 seco nds, co ntrol will resu me n orm al operati on 1 ho ur aft er error i s corrected. Ch eck for pi lot f lame. Repl ace gas val ve i f pilot f lame presen t. If n o pil ot fl ame, cyc le “Call for Heat.” If error repeats, re place con trol. 6 Control In ter nal Error Control remai ns i n wai t mode. W hen the fa ult corrects, co ntrol resumes normal operati on. Cycl e “Call for Heat”. If error repeats, repl ace control . 7 Flame rod sh orted to gro und Control remai ns i n wai t mode. W hen the fa ult corrects, co ntrol resumes normal operati on. Ch eck fl ame sense l ead wire for damage or s horti ng. C heck t hat fl ame rod i s in proper posi tion . Ch eck fl ame rod cerami c for cracks, damage or tracking. 8 Low seco ndary v oltage su ppl y Con trol remai ns i n wai t mo de. When the fa ult corrects, co ntrol resumes normal operati on. Ch eck tra nsforme r and AC l in e for proper i np ut vol tage to t he co ntrol . Ch eck wi th full system l oad on the tran sformer. a Fl ash Code Desc ripti on s: - Fl ash Fast: rapi d blin ki ng. - Heartbeat: Consta nt ½ sec ond bri ght, ½ seco nd di m cycl es. - 4 seco nd sol id on pulse fol lowed by “x ” 1 seco nd fl ash es indi cates fl ame cu rrent to the nearest μ A. This i s on ly avail able in r un mo de. - A si ngl e fl ash code numbe r signifi es th at the L ED fl ashes X ti mes at 2H z, remai ns o ff for two seco nd s, a nd t he n repeats t he seque nce. TROUBLESHOOTING IGNITION MODULE Before calling your service agent, the following checklist should be examined to eliminate obvious problems from those requiring replacement or servicing. • Check that “main manual gas shut-off valve” is fully open and that gas service has not been interrupted. • Check that after following the water OPERATING INSTRUCTIONS, the “Top Knob” of the gas control valve is in “ON” position. • Check electrical supply to the water heater for possible blown (or tripped) fusing or power interruption. • Is the water temperature in tank below the thermostat dial setting on the thermostat (calling for heat)? • It is possible that the high limit (E.C.O.) has functioned to shut off the water heater . See FEATURES - Water Temperature Control for reset procedure. Contact your serviceman if limit continues to function to shut off water heater. FLUE DAMPER Do not turn damper open manually or motor damage will result, use the service switch. All readings are taken from harness

37 PIN END VIEW 24 V.A.C. NORMAL SEQUENCE OF OPERATION B. DAMPER HAS OPENED, NO COMBUSTION VOLTAGE ACROSS: 4 & 1; 4 & 2; 4 & 3: 1. Check for power at ignition module terminals. If 24VAC power is present damper is working properly. 2. Defective component in water heater after the flue damper. 3. If 24 VAC is not present at the ignition module, look for loose or broken connections between damper and ignition module. 4. If the connections from damper to ignition module seem proper, replace damper assembly. If a damper assembly is not available, place the service switch in the hold open position. This should keep the damper in the open position and allow the customer to have automatic heat, until a replacement damper can be installed. C. DAMPER ROTATES CONTINUOUSLY Change the entire damper assembly D. DAMPER STICKS 1. Make sure no screws obstruct the damper blade. 2. Make sure damper pipe assembly is not egg shaped. 3. Make sure damper rod is not rubbing on pipe assembly. See figure on front page of this insert sheet ABNORMAL OPERATION A. NOTHING WORKING NO VOLTAGE ACROSS: 4 & 1 1. High Limit has tripped and is OPEN. Determine reason for tripping of high limit 2. Bad Transformer 3. Loose or broken connections 4. Blown fuse or circuit breaker 5. Disconnect switch off 6. Harness not plugged into water heater receptacle A. FLUE DAMPER OPEN OR OPENING (Unit is calling for heat and damper disc should be in vertical position) VOLTAGE ACROSS: 4 & 1 All Times that High Limit is closed 4 & 2 Calling for Heat Open or Opening 4 & 3 During Combustion Damper Open+ B. FLUE DAMPER CLOSED (Unit is not calling for heat and damper disc should be in horizontal position) NOTE: POSITION 4 IS COMMON AND POSITION 3 IS HOT 24VAC VOLTAGE ACROSS: 4 & 1 All Times that High Limit is closed NO VOLTAGE ACROSS: 4 & 3 or 4 & 2 1.Thermostat not calling for heat. EFFIKAL RVGP-KSF-SERIES FLUE DAMPER TROUBLE SHOOTING GUIDE Do not turn damper open manually or motor damage will result, use the service switch. All readings are taken from harness receptacle. Do not push meter leads into harness receptacle. This opens the pins and will create connection problems. WARNING Do not negate the action of any existing safety or operational controls. IMPORTANT: DAMPER MUST BE OPEN BEFORE COMBUSTION TAKES PLACE. If all steps have been tried and damper problems persists call Product Service and Support\ 800-456-9805. NOTE: DAMPER DISC SHOWN IN OPEN POSITION. Effikal Pinouts Adapter wire & wire colors Function colors in* 1. Brown 24 VAC HOT Black 2. Orange Signal In Yellow 3. Yellow Signal Out Red 4. Black 24 VAC Common White

38 COMPLAINTCAUSE REMEDY USER QUALIFIED SERVICE AGENCY Water not hot enough. Thermostat set too low. Set thermostat dial to a higher temperature. Upper and/or lower temperature probe out of calibration. Call qualified service agency. Check continuity and resistance (Ohms) of upper and lower thermostat probes. Replace probes if out of specification. Insufficient hot water Thermostat set too low. Set thermostat dial to a higher temperature. Upper and/or lower temperature probe out of calibration. Call qualified service agency. Check continuity and resistance (Ohms) of upper and lower thermostat probes. Replace probes if out of specification.. Main manual gas shutoff valve partially closed. Open main manual gas shutoff valve to fullest extent. Heater too small for demand. Space usage to give heater time to restore water temperature. Heater recovery is slower. Call qualified service agency. Check gas input. If incorrect, adjust gas pressure or replace main burner orifice. Draft hood not installed or one or more baffles. Call qualified service agency. Install draft hood or baffles as furnished with unit. Water temperature too hot. Thermostat set too high.Set thermostat to a lower setting. Heater makes sounds: sizzling. Condensation on outside of tank - normal. Rumbling. Sediment accumulation on bottom of tank. Drain a quantity of water through drain valve. If rumbling persists, call a qualified service agency. Delime heater. Ticking or metallic sounds. Expansion and contraction- normal. Pounding / water hammer. Air chambers in piping have become waterlogged. Thermal expansion tank damaged, improperly charged, or improperly sized. Drain piping system and refill. Heater must be off while this is being done. Check thermal expansion tank charge pressure when the water system pressure is zero. Follow the manufacturer's instructions for proper charging of the thermal expansion tank. Combustion noises. Too much primary air. Adjust shutters. Overtired heater. Incorrect burners or orifice for types of gas used. Call qualified service agency. Check and correct as necessary. Water leaks. Drain valve not closed tightly. If drain valve cannot be closed tightly, replace. If leakage source cannot be corrected or identified, call qualified service agency. Shut off gas supply to heater and close cold water inlet valve to heater. Repair or in case of suspected tank leakage, be certain to confirm before replacing heater. Gas odors. Heater is overtired.Shut off gas supply to heater and call qualified service agency. Check for sooted flue passage. Check for obstructed vent line. Check backdraft or lack of draft. Draft hood may be improperly installed or not sized properly. Possible gas leaks. Shut off gas supply to heater and call gas company at once. TROUBLESHOOTING CHECKLIST

39 c. A sulfate reducing bacteria which has accumulated within the water heater (this harmless bacteria is nontoxic to humans). d. An excess of active hydrogen in the tank. This is caused by the corrosion protective action of the anode rod. Smelly water may be eliminated or reduced in some water heater models by replacing the anode rod(s) with one of less active material, and then chlorinating water heater tank and all water lines. Contact the local water heater supplier or service agency for further information concerning an Anode Rod Replacement Kit and this chlorination treatment. If smelly water persists after anode rod replacement and chlorination treatment, we can only suggest that chlorination or aeration of the water supply be considered to eliminate the water problem. Do not remove the anode rod leaving the tank unprotected. By doing so, all warranty on the water heater tank is voided. “AIR” IN HOT WATER FAUCETS HYDROGEN GAS: Hydrogen gas can be produced in a hot water system that has not been used for a long period of time (generally two weeks or more). Hydrogen gas is extremely flammable and explosive. To prevent the possibility of injury under these conditions, we recommend the hot water faucet, located farthest away, be opened for several minutes before any electrical appliances which are connected to the hot water system are used (such as a dishwasher or washing machine). If hydrogen gas is present, there will probably be an unusual sound similar to air escaping through the pipe as the hot water faucet is opened. There must be no smoking or open flame near the faucet at the time it is open. HIGH WATER TEMPERATURE SHUT OFF SYSTEM This water heater is equipped with a manual reset type high limit (Energy Cutout) switch. The high limit switch interrupts the main burner gas flow should water temperature reach 203°F (95°C). In the event of high limit switch operation, the water heater cannot be restarted unless the water temperature is reduced to approximately 120F (49C). The high limit reset button on the front of the thermostat then needs to be depressed. See Figure 2 for the location of the reset button. START UP CONDITIONS SMOKE/ODOR It is not uncommon to experience a small amount of smoke and odor during the initial start-up. This is due to burning off of oil from metal parts, and will disappear in a short while. STRANGE SOUNDS Possible noises due to expansion and contraction of some metal parts during periods of heat-up and cool-down do not necessarily represent harmful or dangerous conditions. Condensation causes sizzling and popping within the burner area during heating and cooling periods and should be considered normal. See “Condensation" section in this manual. CONDENSATION Whenever the water heater is filled with cold water, some condensate will form while the burner is on. A water heater may appear to be leaking when in fact the water is condensation. This usually happens when: a. A new water heater is filled with cold water for the first time. b. Burning gas produces water vapor in water heaters, particularly high efficiency models where flue temperatures are lower. c. Large amounts of hot water are used in a short time and the refill water in the tank is very cold. Moisture from the products of combustion condense on the cooler tank surfaces and form drops of water which may fall onto the burner or other hot surfaces to produce a “sizzling” or “frying” noise. OPERATIONAL CONDITIONS HOT WATER ODOR In each water heater there is installed at least one anode rod for corrosion protection of the tank. Certain water conditions will cause a reaction between this rod and the water. The most common complaint associated with the anode rod is one of a “rotten egg smell” in the hot water. The smell is a result of four factors which must all be present for the odor to develop: a. A concentration of sulfate in the supply water. b. Little or no dissolved oxygen in the water. FOR YOUR INFORMATION

40 WATER PIPING DIAGRAMS NOTES: 1 . Pref erred piping diagram. 2 . The t emperat ure and pressure relief valve setting shall not exceed pressure rating of any component in the syst em. 3 . Servic e v alv es are s hown f or serv icing unit. However , local codes shall govern t heir usage. 4 . The Tank Temperat ure Cont rol should be wired t o and control the pump between t he wat er heat er(s) and the storage t ank(s). 5 . The wat er heat er’s operat ing thermost at should be set 5 degrees F higher t han the Tank Temperat ure Cont rol.MUL TI FLUE - (1 UNIT) WITH VE RTICAL STORAGE TANK LEGEND TEMPERA TURE & PRESSURE RELIEF V ALVEPRESSURE RELIEF V ALVECIRCULA TING PUMPTA NK TE M PER AT URE CO NTR O LDRAIN FULL POR T BALL VALV E TEMPERA TURE GAGEW ATER FLOW SWITCH CHECK V ALVE W ARNING: THIS DRA WING SHOWS SUGGESTEDPIPING CONFIGURA TION AND OTHER DEVICES; CHECK WITH LOCAL CODES AND ORDINANCES FOR ADDITIONAL REQUIREMENTS. FINISHED FLOOR HOT W ATER T O FIXTURES COLD WATER SUPPLY EXPANSION TANK ALT. COLD WATER CONNECTION HOT WATER RETURN FROM FIXTURES PIPE T&P TO OPEN DRAIN