Home
>
American Water Heater
>
Gas Heater
>
American Water Heater Heavy Duty Commercial Gas BCG3 User Manual
American Water Heater Heavy Duty Commercial Gas BCG3 User Manual
Have a look at the manual American Water Heater Heavy Duty Commercial Gas BCG3 User Manual online for free. It’s possible to download the document as PDF or print. UserManuals.tech offer 32 American Water Heater manuals and user’s guides for free. Share the user manual or guide on Facebook, Twitter or Google+.

11 INSULATION BLANKET Do not obstruct water heater air intake with insulating blanket. Gas and carbon monoxide detectors are available. Install water heater in accordance with the instruction manual. Breathing carbon monoxide can cause brain damage or death. Always read and understand instruction manual. Breathing Hazard - Carbon Monoxide Ga s Insulation blankets are available to the general public for external use on gas water heaters but are not necessary with these products. The purpose of an insulation blanket is to reduce the standby heat loss encountered with storage tank heaters. The water heaters covered by this manual meet or exceed the Energy Policy Act standards with respect to insulation and standby heat loss requirements, making an insulation blanket unnecessary. Should you choose to apply an insulation blanket to this heater, you should follow these instructions. See the Features and Components section of this manual for identification of components mentioned below. Failure to follow these instructions can restrict the air flow required for proper combustion, potentially resulting in fire, asphyxiation, serious personal injury or death. • DO NOT apply insulation to the top of the water heater, as this will interfere with safe operation of the draft hood. • DO NOT cover the gas control valve, thermostat or the Temperature-Pressure Relief Valve. • DO NOT allow insulation to come within 2” (5 cm) of the burners, to prevent blockage of combustion air flow to the burners. • DO NOT allow insulation to come within 9 inches (23 cm) of floor, (within 2 inches (5 cm) of bottom cover) to prevent blockage of combustion air flow to the burners.. • DO NOT cover the instruction manual. Keep it on the side of the water heater or nearby for future reference. • DO obtain new warning and instruction labels from the manufacturer for placement on the blanket directly over the existing labels. • DO inspect the insulation blanket frequently to make certain it does not sag, thereby obstructing combustion air flow. HARD WATER Where hard water conditions exist, water softening or the threshold type of water treatment is recommended. This will protect the dishwashers, coffee urns, water heaters, water piping and other equipment. See the Maintenance Section in this manual for sediment and lime scale removal procedures. CIRCULATION PUMPS A circulating pump is used when a system requires a circulating loop or there is a storage tank used in conjunction with the water heater. See Water Piping Diagrams in this manual for installation location of circulating pumps. See the Circulation Pump Wiring Diagrams in this manual for electrical hookup information. Install in accordance with the current edition of the National Electrical Code, NFPA 70 or the Canadian Electrical Code, CSA C22.1. All-bronze circulating pumps are recommended for used with commercial water heaters. Some circulating pumps are manufactured with sealed bearings and do not require further lubrication. Some circulating pumps FIGURE 6. NSF LEG KIT The NSF Leg Kit (part number 9003425205) is needed only for applications that must conform to NSF/ANSI Standard 5. Installation of the NSF leg kit will increase the height of the unit and all connection points by 3 inches. See Figure 7. Follow these steps to install the Leg Kit: 1. Unit needs to be lifted in a way not to damage unit or laid on it’s side to access the bottom of the legs. 2. Slide leg extension under leg and the bolt up through the bottom hole located in the bottom of the leg. 3. Once in place, screw nut down and secure. 4. Front of leg should line up with front of leg extension as shown to make sure weight of unit is distributed through the leg extension. FIGURE 7.

12 Breathing Hazard - Carbon Monoxide Gas Breathing carbon monoxide can cause brain damage or death. Always read and understand instruction manual. Under no circumstances should the input exceed the rate shown on the water heater ’s rating label. Overfiring could result in damage to the water heater and sooting. Gas and carbon monoxide detectors are available. Installations above 2000 feet (610 meters) require replacement of burner orifices in accordance with current edition of the National Fuel Gas Code (ANSI Z223.1). For Canadian installations consult Canadian Installations Code CAN/CSA B149.1. Failure to replace orifices will result in improper and inefficient operation of the water heater resulting in the production of increased levels of carbon monoxide gas in excess of safe limits which could result in serious personal injury or death. Yo u s h o u l d c o n t a c t y o u r g a s s u p p l i e r f o r a n y s p e c i f i c c h a n g e s which may be required in your area. As the elevation above sea level is increased, there is less oxygen per cubic foot of air. Therefore, the heater input rate should be reduced at high altitudes for satisfactory operation w i t h t h e r e d u c e d o x y g e n s u p p l y . F a i l u r e t o m a k e t h i s r e d u c t i o n would result in an over firing of the heater causing sooting, poor combustion and/or unsatisfactory heater performance. Ratings specified by manufacturers for most appliances apply for elevations up to 2000 feet (610m). For elevations above 2000 feet (610), ratings must be reduced at the rate of 4% for each 1000 feet (305m) above sea level. For example, if a heater is rated at 78,000 Btuh (22.9 Kwh) at sea level, to rate the heater at 4000 feet (1219m), you subtract 4 (once for each thousand feet) x.04 (4% input reduction) x 78,000 (original rating) from the original rating. Therefore, to calculate the input rating at 4,000 feet (1219m): 4 x .04 x 78,000 = 12,480 Btuh (3.7 Kwh), 78,000 (22.9 Kwh) - 12 , 4 8 0 (3 .7 Kw h) = 6 5 , 5 2 0 B t u h (19 . 2 Kw h) . A t 6 0 0 0 f e e t (18 2 9 m) the correct input rating should be 59,280 Btuh (17.4 Kwh). must be periodically oiled. Refer to the pump manufacturer’s instructions for lubrication requirements. CIRCULA TING PUMP WIRING DIAGRAM ST ORAGE TA NK OR BUILDING RECIRCULA TION FIELD SUPPLIED TEMPERATURE CONTROL INST ALLED IN THE STORAGE TA NK OR CIRCULA TING LOOP RETURN LINE CIRC PUMP MOT OR L1 HOT L2 NEUTRAL 120 V AC POWER CIRCULA TING PUMP WIRING DIAGRAM DISHW ASHER LOOP WITH TOGGLE SWITCH FIELD SUPPLIED TEMPERATURE CONTROL INSTALLED IN THE CIRCULA TING LOOP RETURN LINE DISHW ASHER T OGGLE SWITCH CIRC PUMP MOT OR L1 HOT L2 NEUTRAL 120 V AC POWER NOTE: USE SEPARATE 120 VAC POWER SUPPLY FOR PUMP CIRCUIT . DO NOT SHARE POWER WITH WATER HEATER AS THIS MAY CAUSE ELECTRICAL LINE NOISE AND LEAD T O ERRATIC CONTROL SYSTEM OPERATION. NOTE: USE SEPARATE 120 VAC POWERSUPPLY FOR PUMP CIRCUIT. DO NOT SHARE POWER WITH WATER HEATER AS THIS MAY CAUSE ELECTRICAL LINE NOISE AND LEAD TO ERRATIC CONTROL SYSTEM OPERATION. FIGURE 8. CIRCULA TING PUMP WIRING DIAGRAM ST ORAGE TA NK OR BUILDING RECIRCULA TION FIELD SUPPLIED TEMPERATURE CONTROL INST ALLED IN THE STORAGE TA NK OR CIRCULA TING LOOP RETURN LINE CIRC PUMP MOT OR L1 HOT L2 NEUTRAL 120 V AC POWER CIRCULA TING PUMP WIRING DIAGRAM DISHW ASHER LOOP WITH TOGGLE SWITCH FIELD SUPPLIED TEMPERATURE CONTROL INSTALLED IN THE CIRCULA TING LOOP RETURN LINE DISHW ASHER T OGGLE SWITCH CIRC PUMP MOT OR L1 HOT L2 NEUTRAL 120 V AC POWER NOTE: USE SEPARATE 120 VAC POWER SUPPLY FOR PUMP CIRCUIT . DO NOT SHARE POWER WITH WATER HEATER AS THIS MAY CAUSE ELECTRICAL LINE NOISE AND LEAD T O ERRATIC CONTROL SYSTEM OPERATION. NOTE: USE SEPARATE 120 VAC POWERSUPPLY FOR PUMP CIRCUIT. DO NOT SHARE POWER WITH WATER HEATER AS THIS MAY CAUSE ELECTRICAL LINE NOISE AND LEAD TO ERRATIC CONTROL SYSTEM OPERATION. FIGURE 9. HIGH ALTITUDE INSTALLATIONS Fire and Explosion Hazar d Gas and carbon monoxide detectors ar e available. Overfiring could result in fire or explosion. Under no circumstances should the input exceed the rate shown on the water heater ’s rating label.

13 4. When installing multiple water heaters in the same gas supply system it is recommended that individual positive lock-up gas pressure regulators be installed at each unit. POWER SUPPLY The water heaters covered in this manual require a 120 VAC, 1Ø (single phase), 60Hz, 15 amp power supply and must also be electrically grounded in accordance with local codes or, in the absence of local codes, with the National Electrical Code, ANSI/ NFPA 70 or the Canadian Electrical Code, CSA C22.1. WATER TEMPERATURE CONTROL AND MIXING VALVES Wa ter temperature over 125°F (52°C) can cause severe burns instantly resulting in severe injury or death. Children, the elderly and th e physically or mentally disabled are at highest risk for scald injur y. Feel water before bathing or showering. Te mperature limiting devices such as mixing valves must be installe d when required by codes and to ensure safe temperatures at fixtures . Water heated to a temperature which will satisfy clothes washing, dish washing, and other sanitizing needs can scald and cause permanent injury upon contact. Short repeated heating cycles caused by small hot water uses can cause temperatures at the point of use to exceed the water heater’s temperature setting by up to 20°F (11°C). Some people are more likely to be permanently injured by hot water than others. These include the elderly, children, the infirm and the physically/mentally disabled. Table 5 shows approximate time-to-burn relationship for normal adult skin. If anyone using hot water provided by the water heater being installed fits into one of these groups or if there is a local code or state law requiring a certain water temperature at the point of use, then special precautions must be taken. In addition to using the lowest possible temperature setting that satisfies the demand of the application a Mixing Valve should be installed at the water heater (see Figure 10) or at the hot water taps to further reduce system water temperature. Mixing valves are available at plumbing supply stores. Consult a Qualified Installer or Service Agency. Follow mixing valve manufacturer’s instructions for installation of the valves. TABLE 5. Water Temperature °F Time for 1st Degree Burn (Less Severe Burns) Time for Permanent Burns2nd & 3rd Degree (Most Severe Burns) 11 0 (normal shower temp.) 11 6 (pain threshold) 11 6 35 minutes 45 minutes 122 1 minute 5 minutes 131 5 seconds 25 seconds 140 2 seconds 5 seconds 149 1 second 2 seconds 154 instantaneous 1 second (U.S. Government Memorandum, C.P.S.C., Peter L. Armstrong, Sept. 15,1978) GAS SUPPLY SYSTEMS Low pressure building gas supply systems are defined as those systems that cannot under any circumstances exceed 14” W.C. (1/2 PSI Gauge). These systems do not require pressure regulation. Measurements should be taken to insure that gas pressures are stable and fall within the requirements stated on the water heater rating plate. Readings should be taken with all gas burning equipment off (static pressure) and with all gas burning equipment running at maximum rate (dynamic pressure). The gas supply pressure must be stable within 1.5” W.C. from static to dynamic pressure to provide good performance. Pressure drops that exceed 1.5” W.C. may cause rough starting, noisy combustion or nuisance outages. Increases or spikes in static pressure during off cycles may cause failure to ignite or in severe cases damage to appliance gas valves. If your low pressure system does NOT meet these requirements, the installer is responsible for the corrections. High Pressure building supply systems use pressures that exceed 14” W.C. (1/2 PSI Gauge). These systems must use field supplied regulators to lower the gas pressure to less than 14” W.C. (1/2 PSI Gauge). Water heaters require gas regulators that are properly sized for the water heater input and deliver the rating plate specified pressures. Gas supply systems where pressure exceeds 5 PSI often require multiple regulators to achieve desired pressures. Systems in excess of 5 PSI building pressure should be designed by gas delivery professionals for best performance. Water heaters connected to gas supply systems that exceed 14” W.C. (1/2 PSI Gauge) at any time must be equipped with a gas supply regulator. All models require a minimum gas supply pressure of 4.5" W.C. for natural gas and 11.0" W.C. for propane gas. The minimum supply pressure is measured while gas is flowing (dynamic pressure). The supply pressure should never fall below 4.5" W.C. for natural gas and 11.0" W.C. for propane gas. The supply pressure should be measured with all gas fired appliances connected to the common main firing at full capacity. If the supply pressure drops more than 1.5” W.C. as gas begins to flow to the water heater then the supply gas system including the gas line and/or the gas regulator may be restricted or undersized. See Supply Gas Regulator section and Gas Piping section of this manual. The gas valve on all models has a maximum gas supply pressure limit of 14” W.C. The maximum supply pressure is measured while gas is not flowing (static pressure). SUPPLY GAS REGULATOR The maximum allowable gas supply pressure for this water heater is 14 inches W.C. (3.48 kPa). Install a positive lock-up gas pressure regulator in the gas supply line if inlet gas pressure can exceed 14 inches W.C. (3.48 kPa) at any time. Regulators must be sized/used according to manufacturer’s specifications. If a positive lock-up regulator is required follow these instructions: 1. Positive lock-up gas pressure regulators must be rated at or above the input Btu/hr rating of the water heater they supply. 2. Positive lock-up gas pressure regulator(s) should be installed no closer than 3 equivalent feet (1 meter) and no farther than 8 equivalent feet (2.4 meters) from water heater’s inlet gas connection. 3. After installing the positive lock-up gas pressure regulator(s) an initial nominal supply pressure setting of 7.0” W.C. while the water heater is operating is recommended and will generally provide good water heater operation. Some addition adjustment maybe required later to maintain a steady gas supply pressure. INSTALLATION REQUIREMENTS

14 HOT WATER OUTLET TO TA NK INLET CHECK VA LVE MIXING VA LVE COLD WA TER INLET TEMPERED WA TER OUTLET 12” TO 15” (30-38 cm) CHECK VA LVE FIGURE 10. DISHWASHING MACHINES All dishwashing machines meeting the National Sanitation Foundation requirements are designed to operate with water flow pressures between 15 and 25 pounds per square inch (103 kPa and 173 kPa). Flow pressures above 25 pounds per square inch (173 kPa), or below 15 pounds per square inch (103 kPa), will result in improperly sanitized dishes. Where pressures are high, a water pressure reducing or flow regulating control valve should be used in the 180°F (82°C) line to the dishwashing machine and should be adjusted to deliver water pressure between these limits. The National Sanitation Foundation also recommends circulation of 180°F (82°C) water. The circulation flow rate should be just enough to provide 180°F (82°C) water at the point of take-off to the dishwashing machine. Adjust flow by throttling a full port ball valve installed in the circulating line on the outlet side of the pump. Never throttle flow on the suction side of a pump. See Water Piping Diagrams in this manual. NOTE: These water heaters meet the NSF Standard 5 for sanitary installations when used with the leg kit part number 9003425205. CLOSED WATER SYSTEMS Water supply systems may, because of code requirements or such conditions as high line pressure, among others, have installed devices such as pressure reducing valves, check valves, and back flow preventers. Devices such as these cause the water system to be a closed system. THERMAL EXPANSION As water is heated, it expands (thermal expansion). In a closed system the volume of water will grow when it is heated. As the volume of water grows there will be a corresponding increase in water pressure due to thermal expansion. Thermal expansion can cause premature tank failure (leakage). This type of failure is not covered under the limited warranty. Thermal expansion can also cause intermittent Temperature-Pressure Relief Valve operation: water discharged from the valve due to excessive pressure build up. This condition is not covered under the limited warranty. The Temperature-Pressure Relief Valve is not intended for the constant relief of thermal expansion. A properly sized thermal expansion tank must be installed on all closed systems to control the harmful effects of thermal expansion. Contact a local plumbing service technician to have a thermal expansion tank installed. See Water Line Connections on page 21 and the Water Piping Diagrams beginning on page 40. TEMPERATURE-PRESSURE RELIEF VALVE Explosion Hazard Te mperature-Pressure Relief Valve must comply with ANSI Z21.22- CSA 4.4 and ASME code. Properly sized temperature- pressure relief valve must be installed in opening provided. Can result in overheating and excessive tank pressure . Can cause serious injury or death. This water heater is provided with a properly rated/sized and certified combination Temperature-Pressure Relief Valve (T&P valve) by the manufacturer. The valve is certified by a nationally recognized testing laboratory that maintains periodic inspection of production of listed equipment of materials as meeting the requirements for Pressure Relief Valves for Hot Water Supply Systems, ANSI Z21.22 • CSA 4.4, and the code requirements of ASME. If replaced, the new T&P valve must meet the requirements of local codes, but not less than a combination Temperature- Pressure Relief Valve rated/sized and certified as indicated in the above paragraph. The new valve must be marked with a maximum set pressure not to exceed the marked hydrostatic working pressure of the water heater (150 psi = 1,035 kPa) and a discharge capacity not less than the water heater Btu/hr or kW input rate as shown on the water heater’s model rating label. NOTE: In addition to the factory installed Temperature-Pressure Relief Valve on the water heater, each remote storage tank that may be installed and piped to a water heating appliance must also have its own properly sized, rated and approved Temperature- Pressure Relief Valve installed. Call the toll free technical support phone number listed on the back cover of this manual for technical assistance in sizing a Temperature-Pressure Relief Valve for remote storage tanks. For safe operation of the water heater, the Temperature-Pressure Relief Valve must not be removed from its designated opening nor plugged. The Temperature-Pressure Relief Valve must be installed directly into the fitting of the water heater designed for the pressure relief valve . Install discharge piping so that any discharge will exit the pipe within 6 inches (15.2 cm) above an adequate floor drain, or external to the building. In cold climates it is recommended that it be terminated at an adequate drain inside the building. Be certain that no contact is made with any live electrical part. The discharge opening must not be blocked or reduced in size under any circumstances. Excessive length, over 30 feet (9.14 m), or use of more than four elbows can cause restriction and reduce the discharge capacity of the valve.

15 No valve or other obstruction is to be placed between the Temperature-Pressure Relief Valve and the tank. Do not connect discharge piping directly to the drain unless a 6” (15.2 cm) air gap is provided. To prevent bodily injury, hazard to life, or property damage, the relief valve must be allowed to discharge water in adequate quantities should circumstances demand. If the discharge pipe is not connected to a drain or other suitable means, the water flow may cause property damage. Water Damage Hazard Temperature-Pressure Relief V alve discharge pipe must terminate at adequate drain. CAUTION T&P Valve Discharge Pipe Requirements: • Shall not be smaller in size than the outlet pipe size of the valve, or have any reducing couplings or other restrictions. • Shall not be plugged or blocked. • Shall not be exposed to freezing temperatures. • Shall be of material listed for hot water distribution. • Shall be installed so as to allow complete drainage of both the Temperature-Pressure Relief Valve and the discharge pipe. • Must terminate a maximum of six inches above a floor drain or external to the building. In cold climates, it is recommended that the discharge pipe be terminated at an adequate drain inside the building. • Shall not have any valve or other obstruction between the pressure relief valve and the drain. Burn hazard. Hot water discharge. Keep clear of Temperature- Pressure Relief V alve discharge outlet. The Temperature-Pressure Relief Valve must be manually operated at least twice a year. Caution should be taken to ensure that (1) no one is in front of or around the outlet of the Temperature-Pressure Relief Valve discharge line, and (2) the water manually discharged will not cause any bodily injury or property damage because the water may be extremely hot. If after manually operating the valve, it fails to completely reset and continues to release water, immediately close the cold water inlet to the water heater, follow the draining instructions in this manual, and replace the Temperature- Pressure Relief Valve with a properly rated/sized new one. NOTE: The purpose of a Temperature-Pressure Relief Valve is to prevent excessive temperatures and pressures in the storage tank. The T&P valve is not intended for the constant relief of thermal expansion. A properly sized thermal expansion tank must be installed on all closed systems to control thermal expansion, see Closed Water Systems and Thermal Expansion on page 14. If you do not understand these instructions or have any questions regarding the Temperature-Pressure Relief Valve call the toll free number listed on the back cover of this manual for technical assistance. CONTAMINATED AIR Breathing Hazard - Carbon Monoxide Ga s Install water heater in accordance with the Instruction Manual and NFPA 54 or CAN/CSA-B149.1. To avoid injur y, combustion and ventilation air must be taken from outdoors. Do not place chemical vapor emitting products near water heater . Breathing carbon monoxide can cause brain damage or death. Always read and understand instruction manual. Corrosion of the flue ways and vent system may occur if air for combustion contains certain chemical vapors. Such corrosion may result in failure and risk of asphyxiation. Combustion air that is contaminated can greatly diminish the life span of the water heater and water heater components such as hot surface igniters and burners. Propellants of aerosol sprays, beauty shop supplies, water softener chemicals and chemicals used in dry cleaning processes that are present in the combustion, ventilation or ambient air can cause such damage. Do not store products of this sort near the water heater. Air which is brought in contact with the water heater should not contain any of these chemicals. If necessary, uncontaminated air should be obtained from remote or outdoor sources. The limited warranty is voided when failure of water heater is due to a corrosive atmosphere. (See limited warranty for complete terms and conditions). AIR REQUIREMENTS Breathing Hazard - Carbon Monoxide Ga s Install water heater in accordance with the Instruction Manual and NFPA 54 or CAN/CSA-B149.1. To avoid injur y, combustion and ventilation air must be taken from outdoors. Do not place chemical vapor emitting products near water heater . Breathing carbon monoxide can cause brain damage or death. Always read and understand instruction manual. For safe operation an adequate supply of fresh uncontaminated air for combustion and ventilation must be provided. An insufficient supply of air can cause recirculation of combustion products resulting in contamination that may be hazardous to life. Such a condition often will result in a yellow, luminous burner flame, causing sooting of the combustion chamber, burners and flue tubes and creates a risk of asphyxiation. Do not install the water heater in a confined space unless an adequate supply of air for combustion and ventilation is brought in to that space using the methods described in the Confined Space section that follows. Never obstruct the flow of ventilation air. If you have any doubts or questions at all, call your gas supplier. Failure to provide the proper amount of combustion air can result in a fire or explosion and cause property damage, serious bodily injury or death.

16 DIRECT VENT APPLIANCES Appliances installed in a Direct Vent configuration that derive all air for combustion from the outdoor atmosphere through sealed intake air piping are not factored in the total appliance input Btu/ hr calculations used to determine the size of openings providing fresh air into confined spaces. EXHAUST FANS Where exhaust fans are installed, additional air shall be provided to replace the exhausted air. When an exhaust fan is installed in the same space with a water heater, sufficient openings to provide fresh air must be provided that accommodate the requirements for all appliances in the room and the exhaust fan. Undersized openings will cause air to be drawn into the room through the water heater’s vent system causing poor combustion. Sooting, serious damage to the water heater and the risk of fire or explosion may result. It can also create a risk of asphyxiation. LOUVERS AND GRILLES The free areas of the fresh air openings in the instructions that follow do not take in to account the presence of louvers, grilles or screens in the openings. The required size of openings for combustion, ventilation and dilution air shall be based on the “net free area” of each opening. Where the free area through a design of louver or grille or screen is known, it shall be used in calculating the size of opening required to provide the free area specified. Where the louver and grille design and free area are not known, it shall be assumed that wood louvers will have 25% free area and metal louvers and grilles will have 75% free area. Non motorized louvers and grilles shall be fixed in the open position.UNCONFINED SPACE An Unconfined Space is one whose volume IS NOT LESS THAN 50 cubic feet per 1,000 Btu/hr (4.8 cubic meters per kW) of the total input rating of all appliances installed in the space. Rooms communicating directly with the space, in which the appliances are installed, through openings not furnished with doors, are considered a part of the unconfined space. Makeup air requirements for the operation of exhaust fans, kitchen ventilation systems, clothes dryers and fireplaces shall also be considered in determining the adequacy of a space to provide combustion, ventilation and dilution air. UNUSUALLY TIGHT CONSTRUCTION In unconfined spaces in buildings, infiltration may be adequate to provide air for combustion, ventilation and dilution of flue gases. However, in buildings of unusually tight construction (for example, weather stripping, heavily insulated, caulked, vapor barrier, etc.) additional air must be provided using the methods described in the Confined Space section that follows. CONFINED SPACE A Confined Space is one whose volume is less than 50 cubic feet per 1,000 Btu/hr (4.8 cubic meters per kW) of the total input rating of all appliances installed in the space. Openings must be installed to provide fresh air for combustion, ventilation and dilution in confined spaces. The required size for the openings is dependent on the method used to provide fresh air to the confined space and the total Btu/hr input rating of all appliances installed in the space. VENTING INSTALLATION VENTING THE INSTRUCTIONS IN THIS SECTION ON VENTING MUST BE FOLLOWED TO AVOID CHOKED COMBUSTION OR RECIRCULATION OF FLUE GASES. SUCH CONDITIONS CAUSE SOOTING OR RISKS OF FIRE AND ASPHYXIATION. Heater must be protected from freezing downdrafts. Remove all soot or other obstructions from the chimney that will retard a free draft. Type B venting is recommended with these heaters. For typical venting application see TECHNICAL DATA VENTING on pages 19 and 20. This water heater must be vented in compliance with all local codes, the current revision of the National Fuel Gas Code (ANSI-Z223.1) and with the Category I Venting Tables. If any part of the vent system are exposed to ambient temperatures below 40°F it must be insulated to prevent condensation. • Do not connect the heater to a common vent or chimney with solid fuel burning equipment. This practice is prohibited by many local building codes as is the practice of venting gas fired equipment to the duct work of ventilation systems. • Where a separate vent connection is not available and the vent pipe from the heater must be connected to a common vent with an oil burning furnace, the vent pipe should enter the smaller common vent or chimney at a point above the large vent pipe. VENT REDUCER Model BCG370T120 is shipped with a 6" to 5" flue outlet adapter. Models (A)BCG3100T250, (A)BCG365T250 and (A) BCG3100T275 are shipped with a 8" to 6" flue outlet adapter. Each adapter fits on top of the installed flue damper. Use only vent reducers supplied with the unit. The venting must comply with the current editions of the NATIONAL FUEL GAS CODE, ANSI Z223.1/ NFPA 54 or NATURAL GAS AND PROPANE INSTALLATION CODE CAN/CSA-B149.1 FIGURE 11. FIGURE 12.

17 MULTIPLE HEATER MANIFOLD Figure 13 and tables on pages 19 and 20 should be used for horizontally manifolding two or more heaters. FIGURE 13. FRESH AIR OPENINGS FOR CONFINED SPACES The following instructions shall be used to calculate the size, number and placement of openings providing fresh air for combustion, ventilation and dilution in confined spaces. The illustrations shown in this section of the manual are a reference for the openings that provide fresh air into confined spaces only. DO NOT refer to these illustrations for the purpose of vent installation. See Venting Installation on page 16 for complete venting installation instructions. OUTDOOR AIR THROUGH TWO OPENINGS FIGURE 14. The confined space shall be provided with two permanent openings, one commencing within 12 inches (300 mm) of the top and one commencing within 12 inches (300 mm) of the bottom of the enclosure. The openings shall communicate directly with the outdoors. See Figure 14. Each opening shall have a minimum free area of 1 square inch per 4,000 Btu/hr (550 mm 2 per kW) of the aggregate input rating of all appliances installed in the enclosure. Each opening shall not be less than 100 square inches (645 cm 2). OUTDOOR AIR THROUGH ONE OPENING FIGURE 15. Alternatively a single permanent opening, commencing within 12 inches (300 mm) of the top of the enclosure, shall be provided. See Figure 14. The water heater shall have clearances of at least 1 inch (25 mm) from the sides and back and 6 inches (l50 mm) from the front of the water heater. The opening shall directly communicate with the outdoors or shall communicate through a vertical or horizontal duct to the outdoors or spaces that freely communicate with the outdoors and shall have a minimum free area of the following: 1. 1 square inch per 3000 Btu/hr (733 mm 2 per kW) of the total input rating of all appliances located in the enclosure, and 2. Not less than the sum of the areas of all vent connectors in the space. OUTDOOR AIR THROUGH TWO HORIZONTAL DUCTS FIGURE 16. The confined space shall be provided with two permanent horizontal ducts, one commencing within 12 inches (300 mm) of the top and one commencing within 12 inches (300 mm) of the bottom of the enclosure. The horizontal ducts shall communicate directly with the outdoors. See Figure 16. Each duct opening shall have a minimum free area of 1 square inch per 2,000 Btu/hr (1100 mm 2 per kW) of the aggregate input rating of all appliances installed in the enclosure. When ducts are used, they shall be of the same cross sectional area as the free area of the openings to which they connect. The minimum dimension of rectangular air ducts shall be not less than 3 inches.

18 When ducts are used, they shall be of the same cross sectional area as the free area of the openings to which they connect. The minimum dimension of rectangular air ducts shall be not less than 3 inches. AIR FROM OTHER INDOOR SPACES FIGURE 18. The confined space shall be provided with two permanent openings, one commencing within 12 inches (300 mm) of the top and one commencing within 12 inches (300 mm) of the bottom of the enclosure. See Figure 18. Each opening shall communicate directly with an additional room(s) of sufficient volume so that the combined volume of all spaces meets the criteria for an Unconfined Space. Each opening shall have a minimum free area of 1 square inch per 1,000 Btu/hr (2200 mm 2 per kW) of the aggregate input rating of all appliances installed in the enclosure. Each opening shall not be less than 100 square inches (645 cm 2). OUTDOOR AIR THROUGH TWO VERTICAL DUCTS The illustrations shown in this section of the manual are a reference for the openings that provide fresh air into confined spaces only. DO NOT refer to these illustrations for the purpose of vent installation. See Venting Installation on page 14 for complete venting installation instructions. FIGURE 17. The confined space shall be provided with two permanent vertical ducts, one commencing within 12 inches (300 mm) of the top and one commencing within 12 inches (300 mm) of the bottom of the enclosure. The vertical ducts shall communicate directly with the outdoors. See Figure 17. Each duct opening shall have a minimum free area of 1 square inch per 4,000 Btu/hr (550 mm 2 per kW) of the aggregate input rating of all appliances installed in the enclosure.

19 TYPE B GAS VENT Multiple Gas Fired Tank-Type Heaters When venting multiple tank type heaters using Type B vent pipe, follow the installation diagram (Figure 13) and tables below which give sizing and data based upon NFPA 54/ANSI Z223. TABLE 6. TECHNICAL DATA VENTING MODEL (A)BCG370T120 Input: 120,000 Btuh \ Total Vent Height (Feet)Draft Hood: 5” 6810 15203050100 Input Btuh Rise Vent Connector Diameter (inches) 120,000 1 Ft.77 766666 120,000 2 Ft.66 666665 120,000 3 Ft.66 666555 Number of Heaters Combined Input in Thousands of Btuh Manifold and Common Vent Diameter (In inches) 2240 1088777673360 1010 1010 8877 4 480 1212 12101010 88 MODEL (A)BCG380T150 Input: 154,000 Btuh \ Total Vent Height (Feet) Draft Hood: 6” 6810 15203050100 Input Btuh Rise Vent Connector Diameter (in inches) 154,000 1 Ft.88 777777 154,000 2 Ft.77 777666 154,000 3 Ft.77 766666 Numbers of Heaters Combined Input in Thousands of Btuh Manifold and Common Vent Diameter (in inches) 2308 1010 10 887773462 1212 12101010 88 4 616 1414 12121210 110 MODEL BCG380T180, BCG3100T199, BCG380T199, & (A)BCG3100T200 Input: 180,000, 199,000 Btuh \ Total Vent Height (Feet) Draft Hood: 6” 6810 15203050100 Input Btuh Rise Vent Connector Diameter (in inches) 180,000 1 Ft.88 888777 199,000 -- 888887 180,000 2 Ft.88 777777 199,000 88 887777 180,000 3 Ft.77 777766 199,000 88 777776 Number of Heaters Combined Input in Thousands of Btuh Manifold & Common Vent Diameter 2 360 1010 1010 8877 398 1210 101010 887 3 540 1412 1212101010 8 597 1414 121212101010 4 720 1414 141212121010 796 1614 141412121210